Medium Voltage 33kv XLPE Insulated Unarmoured Power Cable
Medium Voltage 33kv XLPE Insulated Unarmoured Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Application:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.
Property:
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.
Specification:
Standard:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
25 |
6.0 |
2.5 |
0.12 |
1.5 |
17.6 |
0.34 |
0.49 |
1.2000 |
0.7270 |
35 |
7.0 |
2.5 |
0.12 |
1.5 |
18.5 |
0.39 |
0.60 |
0.8680 |
0.5240 |
50 |
8.3 |
2.5 |
0.12 |
1.6 |
20.0 |
0.46 |
0.74 |
0.6410 |
0.3870 |
70 |
9.7 |
2.5 |
0.12 |
1.6 |
21.5 |
0.55 |
0.96 |
0.4430 |
0.2680 |
95 |
11.3 |
2.5 |
0.12 |
1.7 |
23.3 |
0.66 |
1.23 |
0.3200 |
0.1930 |
120 |
13 |
2.5 |
0.12 |
1.7 |
24.8 |
0.77 |
1.48 |
0.2530 |
0.1530 |
150 |
14.6 |
2.5 |
0.12 |
1.8 |
26.4 |
0.87 |
1.77 |
0.2060 |
0.1240 |
185 |
15.9 |
2.5 |
0.12 |
1.8 |
28.1 |
1.01 |
2.13 |
0.1640 |
0.0991 |
240 |
18.3 |
2.6 |
0.12 |
1.9 |
30.9 |
1.23 |
2.71 |
0.1250 |
0.0754 |
300 |
20.4 |
2.8 |
0.12 |
2.0 |
33.6 |
1.48 |
3.32 |
0.1000 |
0.0601 |
400 |
23.2 |
3.0 |
0.12 |
2.1 |
37.0 |
1.81 |
4.16 |
0.0778 |
0.0470 |
500 |
26.4 |
3.2 |
0.12 |
2.2 |
41.1 |
2.24 |
5.27 |
0.0605 |
0.0366 |
630 |
30.1 |
3.2 |
0.12 |
2.3 |
45.0 |
2.73 |
6.62 |
0.0469 |
0.0283 |
2)6/10(12)kV,6.35/11(12)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
|||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
|||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
|
25 |
6.0 |
3.4 |
0.12 |
1.5 |
19.4 |
0.40 |
0.55 |
1.2000 |
0.7270 |
|
35 |
6.9 |
3.4 |
0.12 |
1.6 |
20.5 |
0.45 |
0.66 |
0.8680 |
0.5240 |
|
50 |
8.2 |
3.4 |
0.12 |
1.6 |
21.8 |
0.52 |
0.80 |
0.6410 |
0.3870 |
|
70 |
9.7 |
3.4 |
0.12 |
1.7 |
23.5 |
0.62 |
1.03 |
0.4430 |
0.2680 |
|
95 |
11.3 |
3.4 |
0.12 |
1.7 |
25.1 |
0.73 |
1.30 |
0.3200 |
0.1930 |
|
120 |
12.8 |
3.4 |
0.12 |
1.8 |
26.8 |
0.85 |
1.56 |
0.2530 |
0.1530 |
|
150 |
14.2 |
3.4 |
0.12 |
1.8 |
28.2 |
0.95 |
1.85 |
0.2060 |
0.1240 |
|
185 |
15.9 |
3.4 |
0.12 |
1.9 |
30.1 |
1.10 |
2.22 |
0.1640 |
0.0991 |
|
240 |
18.3 |
3.4 |
0.12 |
2.0 |
32.7 |
1.33 |
2.80 |
0.1250 |
0.0754 |
|
300 |
20.4 |
3.4 |
0.12 |
2.0 |
34.8 |
1.54 |
3.39 |
0.1000 |
0.0601 |
|
400 |
23.2 |
3.4 |
0.12 |
2.2 |
38.0 |
1.87 |
4.22 |
0.0778 |
0.0470 |
|
500 |
26.4 |
3.4 |
0.12 |
2.2 |
41.5 |
2.26 |
5.29 |
0.0605 |
0.0366 |
|
630 |
30.1 |
3.4 |
0.12 |
2.4 |
45.6 |
2.78 |
6.67 |
0.0469 |
0.0283 |
3)8.7/10(15)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
|||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
|||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
|
25 |
6.0 |
4.5 |
0.12 |
1.6 |
21.8 |
0.48 |
0.63 |
1.2000 |
0.7270 |
|
35 |
6.9 |
4.5 |
0.12 |
1.7 |
22.9 |
0.54 |
0.75 |
0.8680 |
0.5240 |
|
50 |
8.2 |
4.5 |
0.12 |
1.7 |
24.2 |
0.61 |
0.89 |
0.6410 |
0.3870 |
|
70 |
9.7 |
4.5 |
0.12 |
1.8 |
25.9 |
0.72 |
1.13 |
0.4430 |
0.2680 |
|
95 |
11.3 |
4.5 |
0.12 |
1.8 |
27.5 |
0.84 |
1.40 |
0.3200 |
0.1930 |
|
120 |
12.8 |
4.5 |
0.12 |
1.9 |
29.2 |
0.96 |
1.67 |
0.2530 |
0.1530 |
|
150 |
14.2 |
4.5 |
0.12 |
1.9 |
30.6 |
1.06 |
1.96 |
0.2060 |
0.1240 |
|
185 |
15.9 |
4.5 |
0.12 |
2.0 |
32.5 |
1.22 |
2.34 |
0.1640 |
0.0991 |
|
240 |
18.3 |
4.5 |
0.12 |
2.1 |
35.1 |
1.46 |
2.93 |
0.1250 |
0.0754 |
|
300 |
20.4 |
4.5 |
0.12 |
2.1 |
37.2 |
1.68 |
3.52 |
0.1000 |
0.0601 |
|
400 |
23.2 |
4.5 |
0.12 |
2.2 |
40.2 |
2.00 |
4.35 |
0.0778 |
0.0470 |
|
500 |
26.4 |
4.5 |
0.12 |
2.3 |
43.9 |
2.43 |
5.45 |
0.0605 |
0.0366 |
|
630 |
30.1 |
4.5 |
0.12 |
2.4 |
47.8 |
2.93 |
6.83 |
0.0469 |
0.0283 |
4)12/20(24)kV, 12.7/22(24)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
25 |
|
|
|
|
|
|
|
|
|
35 |
6.9 |
5.5 |
0.12 |
1.7 |
24.9 |
0.62 |
0.83 |
0.8680 |
0.5240 |
50 |
8.2 |
5.5 |
0.12 |
1.8 |
26.4 |
0.70 |
0.98 |
0.6410 |
0.3870 |
70 |
9.7 |
5.5 |
0.12 |
1.8 |
27.9 |
0.80 |
1.21 |
0.4430 |
0.2680 |
95 |
11.3 |
5.5 |
0.12 |
1.9 |
29.7 |
0.94 |
1.50 |
0.3200 |
0.1930 |
120 |
12.8 |
5.5 |
0.12 |
1.9 |
31.2 |
1.05 |
1.77 |
0.2530 |
0.1530 |
150 |
14.2 |
5.5 |
0.12 |
2.0 |
32.8 |
1.17 |
2.07 |
0.2060 |
0.1240 |
185 |
15.9 |
5.5 |
0.12 |
2.0 |
34.5 |
1.33 |
2.45 |
0.1640 |
0.0991 |
240 |
18.3 |
5.5 |
0.12 |
2.1 |
37.1 |
1.57 |
3.04 |
0.1250 |
0.0754 |
300 |
20.4 |
5.5 |
0.12 |
2.2 |
39.4 |
1.81 |
3.66 |
0.1000 |
0.0601 |
400 |
23.2 |
5.5 |
0.12 |
2.3 |
42.4 |
2.14 |
4.49 |
0.0778 |
0.0470 |
500 |
26.4 |
5.5 |
0.12 |
2.4 |
46.1 |
2.58 |
5.61 |
0.0605 |
0.0366 |
630 |
30.1 |
5.5 |
0.12 |
2.4 |
49.8 |
3.10 |
6.99 |
0.0469 |
0.0283 |
5)18/30(36)kV,19/33(36)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
|||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
|||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
|
25 |
|
|
|
|
|
|
|
|
|
|
35 |
|
|
|
|
|
|
|
|
|
|
50 |
8.2 |
8.0 |
0.12 |
2.0 |
31.8 |
0.95 |
1.23 |
0.6410 |
0.3870 |
|
70 |
9.7 |
8.0 |
0.12 |
2.0 |
33.3 |
1.07 |
1.47 |
0.4430 |
0.2680 |
|
95 |
11.3 |
8.0 |
0.12 |
2.1 |
35.1 |
1.21 |
1.78 |
0.3200 |
0.1930 |
|
120 |
12.8 |
8.0 |
0.12 |
2.1 |
36.6 |
1.34 |
2.05 |
0.2530 |
0.1530 |
|
150 |
14.2 |
8.0 |
0.12 |
2.2 |
38.2 |
1.47 |
2.37 |
0.2060 |
0.1240 |
|
185 |
15.9 |
8.0 |
0.12 |
2.2 |
39.9 |
1.64 |
2.76 |
0.1640 |
0.0991 |
|
240 |
18.3 |
8.0 |
0.12 |
2.3 |
42.5 |
1.90 |
3.37 |
0.1250 |
0.0754 |
|
300 |
20.4 |
8.0 |
0.12 |
2.4 |
44.8 |
2.16 |
4.01 |
0.1000 |
0.0601 |
|
400 |
23.2 |
8.0 |
0.12 |
2.4 |
47.6 |
2.52 |
4.87 |
0.0778 |
0.0470 |
|
500 |
26.4 |
8.0 |
0.12 |
2.5 |
51.3 |
2.98 |
6.01 |
0.0605 |
0.0366 |
|
630 |
30.1 |
8.0 |
0.12 |
2.6 |
55.2 |
3.54 |
7.43 |
0.0469 |
0.0283 |
6)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
||||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
||||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
||
25 |
6.0 |
2.5 |
0.1 |
2.0 |
34.6 |
1.13 |
1.58 |
1.2000 |
0.7270 |
||
35 |
6.9 |
2.5 |
0.1 |
2.1 |
36.8 |
1.29 |
1.92 |
0.8680 |
0.5240 |
||
50 |
8.2 |
2.5 |
0.1 |
2.2 |
39.8 |
1.51 |
2.36 |
0.6410 |
0.3870 |
||
70 |
9.7 |
2.5 |
0.1 |
2.3 |
43.2 |
1.81 |
3.04 |
0.4430 |
0.2680 |
||
95 |
11.3 |
2.5 |
0.1 |
2.4 |
46.9 |
2.17 |
3.87 |
0.3200 |
0.1930 |
||
120 |
12.8 |
2.5 |
0.1 |
2.4 |
50.1 |
2.53 |
4.69 |
0.2530 |
0.1530 |
||
150 |
14.2 |
2.5 |
0.1 |
2.5 |
53.3 |
2.90 |
5.60 |
0.2060 |
0.1240 |
||
185 |
15.9 |
2.5 |
0.1 |
2.6 |
57.2 |
3.40 |
6.77 |
0.1640 |
0.0991 |
||
240 |
18.3 |
2.6 |
0.1 |
2.8 |
63.2 |
4.12 |
8.55 |
0.1250 |
0.0754 |
||
300 |
20.4 |
2.8 |
0.1 |
3.0 |
69.0 |
4.89 |
10.46 |
0.1000 |
0.0601 |
||
400 |
23.2 |
3.0 |
0.1 |
3.4 |
76.7 |
6.10 |
13.18 |
0.0778 |
0.0470 |
||
500 |
26.4 |
3.2 |
0.1 |
3.6 |
85.7 |
8.10 |
16.55 |
0.0605 |
0.0366 |
7)6/10(12)kV,6.35/11(12)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
|||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
|||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
|
25 |
6.0 |
3.4 |
0.1 |
2.1 |
38.7 |
1.30 |
1.75 |
1.2000 |
0.7270 |
|
35 |
6.9 |
3.4 |
0.1 |
2.2 |
40.9 |
1.47 |
2.22 |
0.8680 |
0.5240 |
|
50 |
8.2 |
3.4 |
0.1 |
2.3 |
43.9 |
1.70 |
2.50 |
0.6410 |
0.3870 |
|
70 |
9.7 |
3.4 |
0.1 |
2.4 |
47.3 |
2.02 |
3.25 |
0.4430 |
0.2680 |
|
95 |
11.3 |
3.4 |
0.1 |
2.5 |
51.0 |
2.42 |
4.12 |
0.3200 |
0.1930 |
|
120 |
12.8 |
3.4 |
0.1 |
2.6 |
54.4 |
2.79 |
4.95 |
0.2530 |
0.1530 |
|
150 |
14.2 |
3.4 |
0.1 |
2.7 |
57.6 |
3.17 |
5.87 |
0.2060 |
0.1240 |
|
185 |
15.9 |
3.4 |
0.1 |
2.8 |
61.5 |
3.69 |
7.06 |
0.1640 |
0.0991 |
|
240 |
18.3 |
3.4 |
0.1 |
2.9 |
66.9 |
4.38 |
8.82 |
0.1250 |
0.0754 |
|
300 |
20.4 |
3.4 |
0.1 |
3.1 |
71.8 |
5.11 |
10.68 |
0.1000 |
0.0601 |
|
400 |
23.2 |
3.4 |
0.1 |
3.3 |
78.3 |
6.24 |
13.32 |
0.0778 |
0.0470 |
|
500 |
26.4 |
3.4 |
0.1 |
3.5 |
86.4 |
7.63 |
16.50 |
0.0605 |
0.0366 |
8)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
||||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
||||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
||
25 |
6.0 |
4.5 |
0.1 |
2.3 |
43.9 |
1.57 |
2.02 |
0.9270 |
0.7270 |
||
35 |
6.9 |
4.5 |
0.1 |
2.4 |
46.0 |
1.75 |
2.38 |
0.6680 |
0.5240 |
||
50 |
8.2 |
4.5 |
0.1 |
2.4 |
48.8 |
2.00 |
2.85 |
0.4936 |
0.3870 |
||
70 |
9.7 |
4.5 |
0.1 |
2.5 |
52.3 |
2.34 |
3.57 |
0.3420 |
0.2680 |
||
95 |
11.3 |
4.5 |
0.1 |
2.6 |
55.9 |
2.75 |
4.45 |
0.2464 |
0.1930 |
||
120 |
12.8 |
4.5 |
0.1 |
2.7 |
59.4 |
3.16 |
5.32 |
0.1955 |
0.1530 |
||
150 |
14.2 |
4.5 |
0.1 |
2.8 |
62.6 |
3.57 |
6.27 |
0.1587 |
0.1240 |
||
185 |
15.9 |
4.5 |
0.1 |
2.9 |
66.4 |
4.07 |
7.45 |
0.1271 |
0.0991 |
||
240 |
18.3 |
4.5 |
0.1 |
3.1 |
72.0 |
4.82 |
9.25 |
0.0976 |
0.0754 |
||
300 |
20.4 |
4.5 |
0.1 |
3.3 |
77.0 |
5.71 |
11.28 |
0.0778 |
0.0601 |
||
400 |
23.2 |
4.5 |
0.1 |
3.4 |
83.2 |
6.78 |
13.86 |
0.0615 |
0.0470 |
||
500 |
26.4 |
4.5 |
0.1 |
3.5 |
91.1 |
8.20 |
17.32 |
0.0487 |
0.0366 |
9)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
||||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
||||||||
mm2 |
mm |
mm |
mm2 |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
||
25 |
– |
|
|
|
|
|
|
|
|
||
35 |
6.9 |
5.5 |
0.1 |
2.4 |
50.3 |
2.00 |
2.63 |
0.8680 |
0.6680 |
||
50 |
8.2 |
5.5 |
0.1 |
2.5 |
53.3 |
2.26 |
3.11 |
0.6410 |
0.4936 |
||
70 |
9.7 |
5.5 |
0.1 |
2.6 |
56.8 |
2.62 |
3.85 |
0.4430 |
0.3420 |
||
95 |
11.3 |
5.5 |
0.1 |
2.8 |
60.6 |
3.07 |
4.77 |
0.3200 |
0.2464 |
||
120 |
12.8 |
5.5 |
0.1 |
2.9 |
64.1 |
3.49 |
5.65 |
0.2530 |
0.1955 |
||
150 |
14.2 |
5.5 |
0.1 |
3.0 |
67.3 |
3.91 |
6.61 |
0.2060 |
0.1587 |
||
185 |
15.9 |
5.5 |
0.1 |
3.1 |
71.2 |
4.44 |
7.81 |
0.1640 |
0.1271 |
||
240 |
18.3 |
5.5 |
0.1 |
3.3 |
76.8 |
5.21 |
9.64 |
0.1250 |
0.0976 |
||
300 |
20.4 |
5.5 |
0.1 |
3.3 |
81.3 |
6.10 |
11.66 |
0.1000 |
0.0778 |
||
400 |
23.2 |
5.5 |
0.1 |
3.5 |
87.7 |
7.20 |
14.28 |
0.0778 |
0.0615 |
||
500 |
26.4 |
5.5 |
0.1 |
3.8 |
96.0 |
9.15 |
17.80 |
0.0605 |
0.0487 |
10)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor |
Normal Diameter of Conductor |
Normal Thickness of Insulation |
Normal Thickness of |
Normal Thickness of Outer Sheath |
Approx. |
Approx. Net Weight |
Max. D.C. Resistance of Conductor at 20ºC |
||
Al Conductor |
Cu Conductor |
Al Conductor |
Cu Conductor |
||||||
mm2 |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
Ω/km |
Ω/km |
25 |
|
|
|
|
|
|
|
|
|
35 |
|
|
|
|
|
|
|
|
|
50 |
8.2 |
8.0 |
0.1 |
2.9 |
64.9 |
3.02 |
3.87 |
0.6410 |
0.4936 |
70 |
9.7 |
8.0 |
0.1 |
3.0 |
68.4 |
3.42 |
4.65 |
0.4430 |
0.3420 |
95 |
11.3 |
8.0 |
0.1 |
3.1 |
72.0 |
3.89 |
5.59 |
0.3200 |
0.2464 |
120 |
12.8 |
8.0 |
0.1 |
3.3 |
75.7 |
4.39 |
6.54 |
0.2530 |
0.1955 |
150 |
14.2 |
8.0 |
0.1 |
3.3 |
78.7 |
4.85 |
7.55 |
0.2060 |
0.1587 |
185 |
15.9 |
8.0 |
0.1 |
3.4 |
82.6 |
5.42 |
8.79 |
0.1640 |
0.1271 |
240 |
18.3 |
8.0 |
0.1 |
3.5 |
88.0 |
6.22 |
10.66 |
0.1250 |
0.0976 |
300 |
20.4 |
8.0 |
0.1 |
3.7 |
92.9 |
7.20 |
12.77 |
0.1000 |
0.0778 |
400 |
23.2 |
8.0 |
0.1 |
3.9 |
99.3 |
8.38 |
15.46 |
0.0778 |
0.0615 |
500 |
26.4 |
8.0 |
0.1 |
4.2 |
107.6 |
10.15 |
18.85 |
0.0605 |
0.0487 |
We are China Medium Voltage 33kv XLPE Insulated Unarmoured Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 33kv XLPE Cable Products
21/33kv Medium Voltage Copper Conductor XLPE Power Cable 1X185mm2
Middle Voltage 18/30 (33) Kv Copper Conductor XLPE Insulated Steel Tape Armored Cable
Mv 33kv Aluminum Conductor XLPE Insulated Power Cables
XLPE Power Cable 4mm 6mm 10mm 16mm 25mm 35mm 50mm
Hv18/30 (33) Kv Aluminum Conductor XLPE Insulated and PVC Sheathed Power Cable
Popular jpcable99 Products
Steel Tape Armoured Power Cable (STA Cable)
Aerial Bundled Cable, Triplex Service Drop ABC Cable
Bare Conductor AAC Cosmos/Dahlia All Aluminium Stranded Conductor
Aerial Bundle Cable ABC Cable/Aluminum Conductor.
Medium Voltage Underground XLPE Insulated Unarmoured Cable
ASTM Standard"Haiotis" ABC Cable
Popular XLPE Cable Products
Copper Conductor Copper Tape Screen XLPE Insulated 11kv Power Cable
XLPE Swa PVC Power Supply Cable Armoured 4 Core Power Cable
6.35/11 (12) Kv Three Core Copper XLPE Insulated Galvanized Steel Tape Armoured Cables
LV 4core 70mm2 XLPE Insulated Copper Cable
Single Core Copper Screen Swa XLPE Cable