0.6/1kv Aerial Bundle Cable (IEC, ASTM, Sans, NFC Standards)
0.6/1kv Aerial Bundle Cable (IEC, ASTM, Sans, NFC Standards) image
Get Latest Price Request a quote
Quick Details
Product Details
We can supply this conductor according to different recognized standards, such as IEC Standard, ANSI/ICEA , NFC, NBR, ITP ,customer special specification also can be satisfied.
Application: ABC cable Conllie, duplex cable, service drop, overhead cable.
The basic construction is as following:
A, 2, 3, 4 power cores consisting of strandard aluminium conductor, insulated with XLPE or PVC, PE.
B, One sheath lighting aluminium conductor with XLPE insulation(optional)
C, One messenger Al-alloy (bare or covered)
It meets or exceeds the following specification:
A, Aluminium wire, 1350-H19 for electrical purposes.
B, Aluminium conductor, concentric-lay-stranded.
C, Aluminium conductor, concentric-lay-stranded, coated steel reinforgorced(ACSR, AAC, AAAC)
D, Concentric-lay stranded 6201-T81 conductors.
E, Compressed Round Stranded Aluminium consuctors using single input wire.
Specifications:
Conductor: Aluminum
Insulation: PVC, XLPE, PE
Application: Overhead line
Core: 2.3, 4 core( Duplex, triplex, quoduplex)
|
Code word |
AWG or kcmil |
Bare Neutral Messenger | Phase Conductor | Weight Kg/km |
Allowable Ampacities(A) |
|||||||
| ACSR | Rated strength Ibs. | AAC | Insul Thick. mm |
XLPE |
PE |
|||||||
| Number | Dia mm | Number | Dia mm | Number | Dia mm | |||||||
| Setter | 1*6AWG+1*6AWG | 1 | 1.68 | 6 | 1.68 | 1190 | 1 | 4.11 | 1.14 | 111 | 85 | 70 |
| Bull | 1*1/0AWG+1*1/0AWG | 1 | 3.37 | 6 | 3.37 | 4380 | 19 | 1.89 | 1.52 | 427 | 205 | 160 |
| Shepherd | 1*6AWG+1*6AWG | 1 | 1.68 | 6 | 1.68 | 1190 | 7 | 1.56 | 1.14 | 113 | 85 | 70 |
| Eskimo | 1*4AWG+1*4AWG | 1 | 2.12 | 6 | 2.12 | 1860 | 1 | 5.19 | 1.14 | 171 | 115 | 90 |
| Terrier | 1*4AWG+1*4AWG | 1 | 2.12 | 6 | 2.12 | 1860 | 7 | 1.96 | 1.14 | 173 | 115 | 90 |
| Chow | 1*2AWG+1*2AWG | 1 | 2.67 | 6 | 2.67 | 2850 | 7 | 2.47 | 1.14 | 266 | 150 | 120 |
Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1
Table 01
| Type of conductor or core | Norminal cross-sectional area mm2 | Nubmer of wires Min. |
Diameter of conductormm | Resistanceat 20ºC Ω/km Max. | Breaking force(N) | Thickness of insulation (mm) | Outer diameter of core(mm) | |||
| Min. | Max. | Min. | Average | Min. | Min. | Max. | ||||
| Phase or auxiliary or non-strain-bearing netural(aluminium) | +16 | 6 | 4.6 | 5.1 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 7.8 |
| 25 | 6 | 5.8 | 6.3 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.4 | |
| 35 | 6 | 6.8 | 7.3 | 0.868 | 4500 | 1.6 | 1.34 | 10.0 | 10.9 | |
| 50 | 6 | 7.9 | 8.4 | 0.641 | 6200 | 1.6 | 1.34 | 11.1 | 12.0 | |
| 70 | 12 | 9.7 | 10.2 | 0.443 | 8900 | 1.8 | 1.52 | 13.3 | 14.2 | |
| 95 | 15 | 11.0 | 12.0 | 0.320 | 12300 | 1.8 | 1.52 | 14.6 | 16.0 | |
| 120 | 15 | 12.5 | 13.5 | 0.253 | 15600 | 1.8 | 1.52 | 16.3 | 17.5 | |
| 150 | 15 | 13.9 | 15.0 | 0.206 | 19200 | 1.8 | 1.52 | 17.1 | 18.6 | |
| Service connection(aluminium) | 16 | 6 | 4.6 | 5.2 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 8.0 |
| 25 | 6 | 5.6 | 6.5 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.6 | |
| Service connection(copper) | 10 | 6 | – | 4.2 | 1.83 | 3600 | 1.2 | 0.98 | 6.2 | 7.0 |
| 16 | 6 | – | 5.3 | 1.15 | 5760 | 1.2 | 0.98 | 7.2 | 8.0 | |
| 25 | 6 | – | 6.6 | 0.727 | 8750 | 1.4 | 1.16 | 8.6 | 9.6 | |
| Number and nominal diameter of wires mm |
||||||||||
| Supporting core(aluminium alloy) |
54.6 | 7×3.15 | 9.2 | 9.6 | 0.630 | 16600 | 1.6 | 1.34 | 12.3 | 13.0 |
| 70 | 7×3.50 | 10.0 | 10.4 | 0.500 | 20100 | 1.6 | 1.34 | 12.9 | 13.6 | |
| +Auxiliary conductors or cores only | ||||||||||
When a supporting core is specified in a tender invitation,the combinations listed in Table 02 below:
Table 02
| 1 | 2 |
| Nominal cross sectional area of supporting conductor mm2 | Nominal cross-sectional areas of phase conductors mm2 |
| 54.6 | 25,35,50,70,95 |
| 70 | 70,95,120 |
| 95 | 95,120,150 |
—————————————————————————————————————————–
Aerial Bundle Conductor-ABC(South Africa Custimized Size Specification)
Table 03
| Type of conductor or core | Norminal cross-sectional area mm2 | Nubmer of wires | Diameter of conductormm | Resistanceat 20ºC Ω/km Max. | Breaking force(N) | Thickness of insulation (mm) | Outer diameter of core(mm) | |||
| Min. | Max. | Min. | Average | Min. | Min. | Max. | ||||
| Phase or auxiliary or non-strain-bearing netural(aluminium) | 16 | 7/1.65 | 4.6 | 5.1 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 7.8 |
| 25 | 7/2.15 | 5.8 | 6.3 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.4 | |
| 35 | 7/2.55 | 6.8 | 7.3 | 0.868 | 4500 | 1.6 | 1.34 | 10.0 | 10.9 | |
| 50 | 7/2.99 | 7.9 | 8.4 | 0.641 | 6200 | 1.6 | 1.34 | 11.1 | 12.0 | |
| 70 | 14/2.59 | 9.7 | 10.2 | 0.443 | 8900 | 1.8 | 1.52 | 13.3 | 14.2 | |
| 95 | 19/2.59 | 11.0 | 12.0 | 0.320 | 12300 | 1.8 | 1.52 | 14.6 | 16.0 | |
| 120 | 19/2.99 | 12.5 | 13.5 | 0.253 | 15600 | 1.8 | 1.52 | 16.3 | 17.5 | |
| 150 | 30/2.59 | 13.9 | 15.0 | 0.206 | 19200 | 1.8 | 1.52 | 17.1 | 18.6 | |
| Service connection(aluminium) | 16 | 7/1.65 | 4.6 | 5.2 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 8.0 |
| 25 | 7/2.15 | 5.6 | 6.5 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.6 | |
| Service connection(copper) | 10 | 7/1.35 | – | 4.2 | 1.83 | 3600 | 1.2 | 0.98 | 6.2 | 7.0 |
| 16 | 7/1.69 | – | 5.3 | 1.15 | 5760 | 1.2 | 0.98 | 7.2 | 8.0 | |
| 25 | 7/2.19 | – | 6.6 | 0.727 | 8750 | 1.4 | 1.16 | 8.6 | 9.6 | |
| Supporting core(aluminium alloy) | 16 | 7/1.71 | 5.1 | 5.2 | 2.053 | 5070 | 1.4 | 1.16 | 7.9 | 8.0 |
| 25 | 7/2.15 | 6.4 | 6.5 | 1.314 | 8000 | 1.4 | 1.16 | 9.2 | 9.3 | |
| 35 | 7/2.48 | 6.6 | 7.5 | 0.986 | 10300 | 1.6 | 1.34 | 10.7 | 10.8 | |
| 50 | 7/2.89 | 7.7 | 8.4 | 0.720 | 14200 | 1.6 | 1.34 | 11.9 | 12.0 | |
| 54.6 | 7/3.15 | 9.2 | 9.6 | 0.630 | 16600 | 1.6 | 1.34 | 12.3 | 13.0 | |
| 70 | 7/3.50 | 10.0 | 10.4 | 0.500 | 20100 | 1.6 | 1.34 | 12.9 | 13.6 |
|
We are China 0.6/1kv Aerial Bundle Cable (IEC, ASTM, Sans, NFC Standards) manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular ABC Products
AAC Conductor XLPE Insulated ACSR Netural Duplex ABC Cable
1kv LV ABC 3 Core Bare Support African Cable
High Quality 33kv Medium Voltage Sevice Drop ABC Aerial Bundle Cable
Triplex Service Drop AAAC 6201 Alloy Neutral Conductor Artemia
Triplex Service Drop ABC Cable
0.6/1kV 3X25+1X54,6mm2 Twisted Alu ABC Aerial Bundled Overhead Cable NF C 33-209
Popular ABC Cable Products
Aluminium Service Drop Cable Overhead Electric Cable ABC Cable for Transmission
Duplex Triplex Twisted Aluminum Conductor XLPE Insulated ABC Cable
25mm Aluminum Cable XLPE /PE Insulated ABC Cable
0.6/1kv Aerial Bundled Kable ABC Cable
Duplex/Quadruplex/Triplex ABC Aerial Bundled Cable
Aerial Twisted Aluminum Core 50mm2 ABC Cable
Popular Aerial Bundle Cable Products
Standard Aluminium Conductor Bundle Cable ABC Cable
Aerial Overhead Cable Insulated XLPE Compact ABC Cable
Aerial Bundlec Cable ABC Cable for Overhead Transmission Triplex
ABC, Distribution System Overhead Cable (1000V)
Aerial Bundle Overhead Cable Low Voltage 0.6/1kv ABC Cable Overhead XLPE ABC
Al/XLPE+ACSR Insulated Overhead ABC Cable
Popular jytopcable Products
PVC Insulated Non Armoured Cable
Nyy-J 0.6/1kv PVC Power Cable to DIN/VDE Standard
Mv Aluminum or Copper Underground Electric Armoured Tr-XLPE Urd Power Cable
N2X Ry-O/N2X Ry-J Cu/PVC Power Cable to DIN/VDE0276
Yxz2V N2xry Copper XLPE Insulated Steel Wire Armoured Power Cable
Tags: ABC, ABC Cable, Aerial Bundle Cable, jytopcable