0.6/1kv PVC Insulation Wire Kabel Elektrik Cable
0.6/1kv PVC Insulation Wire Kabel Elektrik Cable image
Get Latest Price Request a quote
Quick Details
Product Details
ITEM NAME : 0.6/1kv PVC Insulated Power Cable
It is used to transmit and distribute power on the power line of A.C. rated voltage 0.6/1kv.
A. Executive standard:
GB/T12706.1(equal to the standard of IEC60502)
B. Working Condition
1.Long-term working temperature allowed by cable conductor shall be no more than 70ºC.
2.Max. temperature of cable conductor shall be no more than 160ºCduring short circuit (the longest lasting time shall be no
more than 5 seconds).
3. Environment temperature for installation shall be no less than 0ºC.
C. Type, Description and Application occasion
Type |
Description |
Application occasion |
|
Cu |
Al |
||
VV |
VLV |
Power cable with PVC insulation and sheath |
To be laid indoors, in the tunnel, cable furrow or pipe. The cable can not bear mechanical force from outside. |
VV22 |
VLV22 |
Power cable with PVC insulation, PVC sheath and steel tape armored |
To be laid underground, the cable can bear certain mechanical force, but it can not bear great pulling force. |
Note:
1: We also produce flame-retardant fire resistant type power cable according to the requirement of the customer. Prefix "ZR" should be added to the original type of cable in ordering flame retardant cable; prefix "NH-" for fire resistant cable.
2: We also produce VV32, VLV32 type steel wire armored power cable according to the requirement of the customer. Magnetism-separated measure shall be adopted by single core steel wire armored cable.
D. Production Scope
Type |
Core number |
mm2 Nominal cross section area |
|
Cu |
Al |
||
VV – VV22 |
– VLV VLV22 |
1 |
1.5~500 2.5~500 10~500 |
VV – VV22 |
– VLV VLV22 |
2 |
1.5~185 2.5~185 4~185 |
VV – VV22 |
– VLV VLV22 |
3 |
1.5~300 2.5~300 4~300 |
VV – VV22 |
– VLV VLV22 |
4 |
2.5~300 2.5~300 4~300 |
VV VV22 |
VLV VLV22 |
3+1 |
4~300 4~300 |
Note:
1: We also produce cable with five cores according to the requirement of the customer.
2: Non-magnetic metal tape wrapping should be adopted as armored layer for single core armored cable for A.C. system.
E. Main Technical parameter of cable
1,Max value of conductor DC resistance shall meet the requirement of conductor of category 2 stipulated in GB/T3956 standard at 20ºC.
2,A.C. Voltage Test
For single core cable without shielding, voltage test of 3.5kV under power frequency is put on for 5 minutes between conductor and water when be immersed in the water for one hour. For multi-core cable, between each insulated conductor and other conductor, voltage test of 3.5kV under power frequency is put on for 5 minutes without puncture of insulation.
F. Approximate outer diameter and weight of cable (from table 1 to table 5)
Table 1
mm2 core number x nominal cross section area |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
||
VV |
VLV |
VV22* |
VLV22* |
|||
1×1.5 |
5.8 |
50 |
/ |
/ |
/ |
/ |
1×2.5 |
6.2 |
62 |
47 |
/ |
/ |
/ |
1×4 |
7.1 |
87 |
63 |
/ |
/ |
/ |
1×6 |
7.6 |
110 |
75 |
/ |
/ |
/ |
1×10 |
8.9 |
166 |
96 |
12.4 |
346 |
270 |
1×16 |
9.9 |
234 |
133 |
13.4 |
432 |
331 |
1×25 |
11.7 |
345 |
186 |
15.2 |
574 |
414 |
1×35 |
12.6 |
450 |
229 |
16.2 |
692 |
475 |
1×50 |
14.6 |
585 |
276 |
18.1 |
863 |
553 |
1×70 |
16.3 |
800 |
366 |
19.8 |
1133 |
700 |
1×95 |
18.5 |
1065 |
475 |
22.0 |
1432 |
844 |
1×120 |
20.2 |
1328 |
586 |
23.7 |
1705 |
962 |
1×150 |
22.5 |
1600 |
702 |
26.0 |
2044 |
1120 |
1×185 |
24.8 |
1990 |
850 |
28.3 |
2438 |
1296 |
1×240 |
27.8 |
2546 |
1060 |
31.5 |
3057 |
1570 |
1×300 |
30.7 |
3140 |
1292 |
34.2 |
3926 |
2070 |
1×400 |
34.7 |
4127 |
1651 |
38.0 |
5084 |
2608 |
1×500 |
39.0 |
5259 |
2016 |
43.0 |
6295 |
2936 |
Table 2
mm2 core number x nominal cross section area |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
||
VV |
VLV |
VV22 |
VLV22 |
|||
2×1.5 |
10.4 |
118 |
/ |
/ |
/ |
/ |
2×2.5 |
11.3 |
151 |
118 |
/ |
/ |
/ |
2×4 |
13.0 |
210 |
159 |
16.0 |
424 |
374 |
2×6 |
13.9 |
263 |
192 |
17.1 |
494 |
425 |
2×10 |
16.5 |
394 |
242 |
19.8 |
665 |
497 |
2×16 |
18.6 |
541 |
334 |
21.8 |
845 |
638 |
2×25 |
22.0 |
794 |
468 |
25.3 |
1154 |
827 |
2×35 |
24.2 |
1037 |
585 |
27.5 |
1436 |
982 |
2×50 |
20.3 |
1236 |
592 |
23.6 |
1580 |
940 |
2×70 |
22.7 |
1647 |
745 |
26.0 |
2210 |
1302 |
2×95 |
26.2 |
2189 |
966 |
29.1 |
2800 |
1530 |
2×120 |
28.8 |
2640 |
1144 |
32.6 |
3400 |
1850 |
2×150 |
32.2 |
3280 |
1410 |
36.2 |
4150 |
2198 |
2×185 |
35.8 |
4006 |
1703 |
39.5 |
5025 |
2592 |
Table 3
mm2 core number x nominal cross section area |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
||
VV |
VLV |
VV22 |
VLV22 |
|||
3×1.5 |
10.6 |
142 |
/ |
/ |
/ |
/ |
3×2.5 |
11.7 |
187 |
139 |
/ |
/ |
/ |
3×4 |
13.6 |
264 |
189 |
16.6 |
489 |
413 |
3×6 |
14.7 |
335 |
226 |
17.7 |
578 |
472 |
3×10 |
17.4 |
514 |
290 |
20.4 |
801 |
560 |
3×16 |
19.7 |
729 |
418 |
22.7 |
1058 |
743 |
3×25 |
23.4 |
1085 |
596 |
26.4 |
1470 |
979 |
3×35 |
25.8 |
1430 |
748 |
28.8 |
2148 |
1370 |
3×50 |
25.5 |
1820 |
839 |
28.5 |
2457 |
1489 |
3×70 |
28.4 |
2400 |
1080 |
31.7 |
3122 |
1768 |
3×95 |
32.8 |
3155 |
1418 |
36.7 |
4055 |
2218 |
3×120 |
35.7 |
3982 |
1747 |
39.6 |
4925 |
2606 |
3×150 |
40.0 |
4950 |
2135 |
44.0 |
6050 |
3154 |
3×185 |
44.4 |
6156 |
2610 |
48.6 |
7299 |
3721 |
3×240 |
49.7 |
7886 |
3308 |
53.9 |
9223 |
4584 |
3×300 |
54.3 |
9647 |
4059 |
58.7 |
11022 |
5423 |
Table 4
mm2 core number x nominal cross section area |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
mm approximate outer diameter of cable |
approximate weight of cable |
||
VV |
VLV |
VV22 |
VLV22 |
|||
4×2.5 |
12.2 |
225 |
166 |
/ |
/ |
/ |
4×4 |
15.0 |
332 |
231 |
18.0 |
581 |
480 |
4×6 |
16.2 |
430 |
270 |
19.2 |
703 |
551 |
4×10 |
19.7 |
641 |
393 |
22.7 |
891 |
637 |
4×16 |
22.0 |
902 |
499 |
25.0 |
1175 |
771 |
4×25 |
26.0 |
1438 |
766 |
29.0 |
1998 |
1347 |
4×35 |
28.7 |
1815 |
919 |
31.7 |
2585 |
1660 |
4×50 |
30.4 |
2380 |
1091 |
33.4 |
3100 |
1819 |
4×70 |
33.8 |
3202 |
1398 |
37.0 |
4039 |
2228 |
4×95 |
38.2 |
4300 |
1860 |
41.5 |
5200 |
2800 |
4×120 |
42.0 |
5269 |
2186 |
45.5 |
6400 |
3320 |
4×150 |
46.4 |
6554 |
2748 |
49.9 |
7806 |
3958 |
4×185 |
51.2 |
8090 |
3325 |
54.9 |
9442 |
4700 |
4×240 |
55.3 |
10355 |
4056 |
59.0 |
11887 |
5734 |
4×300 |
64.5 |
12776 |
4950 |
68.2 |
14356 |
6995 |
Table 5
mm2 core number x nominal cross section area |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
mm approximate outer diameter of cable |
kg/km approximate weight of cable |
||
VV |
VLV |
VV22 |
VLV22 |
|||
3×4+1×2.5 |
14.5 |
310 |
215 |
17.5 |
543 |
447 |
3×6+1×4 |
16.1 |
403 |
268 |
19.1 |
661 |
526 |
3×10+1×6 |
18.9 |
600 |
363 |
21.9 |
894 |
625 |
3×16+1×10 |
21.6 |
858 |
505 |
24.6 |
1195 |
807 |
3×25+1×16 |
25.0 |
1315 |
693 |
28.0 |
1679 |
1082 |
3×35+1×16 |
27.6 |
1645 |
834 |
30.6 |
2243 |
1458 |
3×50+1×25 |
29.6 |
2124 |
996 |
32.6 |
2867 |
1736 |
3×70+1×50 |
33.2 |
2867 |
1285 |
36.2 |
3698 |
2099 |
3×95+1×50 |
38.0 |
3824 |
1664 |
42.1 |
4796 |
2636 |
3×120+1×70 |
41.5 |
4784 |
2060 |
45.5 |
5900 |
3129 |
3×150+1×70 |
44.6 |
5790 |
2473 |
48.4 |
6921 |
3623 |
3×185+1×95 |
49.7 |
7164 |
3050 |
54.2 |
8437 |
4369 |
3×240+1×120 |
55.9 |
9414 |
3842 |
60.3 |
11163 |
5586 |
3×300+1×150 |
61.6 |
11749 |
4920 |
66.0 |
13465 |
6445 |
Luxing Factory : our production base
Luxing Cable Mainly Produce
300/500V 450/750V electrical wire | AAC conductor |
600/1000V PVC insulated cable | AAAC conductor |
600/1000V XLPE insulated cable | ACSR conductor |
1.8/3KV to 26/35KV power cable | OPGW |
Armored underground cable | ABC cable |
Control cable and instrumentation cables | Rubber cable |
Certificates
Strict Quality Test
Packaging & Shipping
Why choose us
1.18 years manufacturing experience
2.Professional international trade team
3.Delivery on time
4.Factory low price and high quality based on advanced technology and high work efficiency
Contact us
We are China 0.6/1kv PVC Insulation Wire Kabel Elektrik Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 16mm2 4 Core 0.6/1kv Cu/PVC Swa/PVC Power Cable Products
16mm2 4 Core 0.6/1kv Cu/PVC Swa/PVC Aluminum Core Concentric Power Cable
Popular Kabel Elektrik Products
Kabel Elektrik PVC Insulated Wire 1.5mm2 2.5mm2 4mm2 6mm2 10mm2
Popular luxingcable Products
7X1.5 Copper Control Cable/10X0.75 System Control Cable
0.75mm2, 1mm2, 1.5mm2, 2.5mm2, Copper Braid Shield XLPE Insulated Control Cable
ABC Conductor LDPE/HDPE/XLPE Insulated 1kv Low Voltage Aerial Bundled Cable ABC Cable
OEM Sizes Electrical Cable Wire 10mm, 2.5mm Electrical Wire Cable
12 Gauge Electrical Wire/Electrical Cable Wire 3.5mm/Electrical Cable 2.5 mm
Popular PVC Power Cable Products
1kv 4 Core Underground PVC Sheathed Power Cable
1kv Underground Steel Wire Armored PVC Power Cable
Multicore Underground Cable PVC Insulated Electric Power Cable
Aluminum XLPE Insulated PVC Insualted Sheated Power Cable
Tags: 16mm2 4 Core 0.6/1kv Cu/PVC Swa/PVC Power Cable, Kabel Elektrik, luxingcable, PVC Power Cable