1/2/3/4/5 Core PVC XLPE Insulated Armoured Sta/Swa Electric Wire Power Cable
1/2/3/4/5 Core PVC XLPE Insulated Armoured Sta/Swa Electric Wire Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Low Voltage Cable
1. Application
The cable is used in electric transmission and distribution system operating at AC rated voltage up to and including 1.8/3 KV
2. Operating Characteristic
1) The rated voltage U0/U of cable is 0.6/1KV.
2) The long time allowable working temperature of conductor is 70 °C FOR cable with PVC insulation, 90 °C for cable with XLPE insulation.
3) The cable laying temperature is not less than 0°C, and the allowable bending radius of a cable is not less 20 times than cable overall diameter for single core unarmored cable, 15 times of that for single core armored, 12 times of that for 3 cores armored cable.
2. Construction
3. Cores and Nominal Cross Section Area:
| Rated voltage 0.6/1kV Single core Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 0.7 | 5.6 | 45 | 35 | ||||||
| 2.5 | 0.7 | 0.7 | 6.0 | 56 | 41 | ||||||
| 4 | 0.7 | 0.7 | 6.5 | 74 | 49 | ||||||
| 6 | 0.7 | 0.7 | 7.0 | 95 | 59 | ||||||
| 10 | 0.7 | 0.7 | 8.2 | 139 | 79 | ||||||
| 16 | 0.7 | 0.7 | 9.1 | 197 | 102 | ||||||
| 25 | 0.9 | 0.9 | 10.6 | 293 | 143 | 0.9 | 0.2 | 1.8 | 14.0 | 451 | 301 |
| 35 | 0.9 | 0.9 | 11.6 | 386 | 178 | 0.9 | 0.2 | 1.8 | 15.0 | 558 | 349 |
| 50 | 1.0 | 1.0 | 13.0 | 507 | 225 | 0.9 | 0.2 | 1.8 | 16.4 | 698 | 416 |
| 70 | 1.1 | 1.1 | 14.9 | 708 | 300 | 0.9 | 0.2 | 1.8 | 18.3 | 926 | 519 |
| 95 | 1.1 | 1.1 | 16.8 | 959 | 394 | 0.9 | 0.2 | 1.8 | 20.0 | 1194 | 628 |
| 120 | 1.2 | 1.2 | 18.5 | 1193 | 479 | 0.9 | 0.2 | 1.8 | 21.7 | 1450 | 737 |
| 150 | 1.4 | 1.4 | 20.6 | 1470 | 590 | 0.9 | 0.2 | 1.8 | 23.6 | 1745 | 865 |
| 185 | 1.6 | 1.6 | 22.8 | 1831 | 730 | 0.9 | 0.2 | 1.8 | 25.6 | 2122 | 1021 |
| 240 | 1.7 | 1.7 | 25.7 | 2380 | 933 | 0.9 | 0.2 | 1.9 | 28.5 | 2706 | 1259 |
| 300 | 1.8 | 1.8 | 28.3 | 2960 | 1144 | 0.9 | 0.2 | 1.9 | 30.9 | 3304 | 1488 |
| 400 | 2.0 | 2.0 | 31.3 | 3755 | 1433 | 1.2 | 0.5 | 2.1 | 35.9 | 4494 | 2173 |
| Rated voltage 0.6/1kV Two cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.2 | 114 | 96 | 0.9 | 0.2 | 1.8 | 12.8 | 232 | 214 |
| 2.5 | 0.7 | 1.8 | 11.0 | 141 | 111 | 0.9 | 0.2 | 1.8 | 13.6 | 269 | 238 |
| 4 | 0.7 | 1.8 | 12.0 | 181 | 132 | 0.9 | 0.2 | 1.8 | 14.6 | 320 | 271 |
| 6 | 0.7 | 1.8 | 13.0 | 228 | 156 | 0.9 | 0.2 | 1.8 | 15.6 | 379 | 306 |
| 10 | 0.7 | 1.8 | 15.4 | 331 | 211 | 0.9 | 0.2 | 1.8 | 18.0 | 509 | 389 |
| 16 | 0.7 | 1.8 | 17.2 | 458 | 268 | 0.9 | 0.2 | 1.8 | 19.8 | 657 | 467 |
| 25 | 0.9 | 1.8 | 20.2 | 672 | 371 | 0.9 | 0.2 | 1.8 | 22.8 | 905 | 604 |
| 35 | 0.9 | 1.8 | 22.2 | 873 | 455 | 0.9 | 0.2 | 1.8 | 24.8 | 1130 | 712 |
| 50 | 1.0 | 1.8 | 25.0 | 1140 | 574 | 0.9 | 0.2 | 1.8 | 27.6 | 1428 | 863 |
| 70 | 1.1 | 1.9 | 29.0 | 1592 | 775 | 1.2 | 0.2 | 2.0 | 33.6 | 2262 | 1445 |
| 95 | 1.1 | 2.0 | 32.6 | 2134 | 1000 | 1.2 | 0.2 | 2.2 | 37.4 | 2899 | 1765 |
| 120 | 1.2 | 2.1 | 36.2 | 2660 | 1229 | 1.2 | 0.5 | 2.3 | 41.0 | 3504 | 2074 |
| 150 | 1.4 | 2.3 | 40.4 | 3287 | 1522 | 1.2 | 0.5 | 2.4 | 45.0 | 4202 | 2437 |
| 185 | 1.6 | 2.4 | 44.6 | 4073 | 1864 | 1.2 | 0.5 | 2.5 | 49.2 | 5079 | 2870 |
| 240 | 1.7 | 2.6 | 50.4 | 5287 | 2384 | 1.4 | 0.5 | 2.8 | 55.6 | 6457 | 3554 |
| 300 | 1.8 | 2.8 | 55.6 | 6567 | 2925 | 1.4 | 0.5 | 2.9 | 60.6 | 7822 | 4180 |
| 400 | 2.0 | 2.9 | 61.4 | 8279 | 3622 | 1.4 | 0.5 | 3.1 | 66.6 | 9692 | 5034 |
| Rated voltage 0.6/1kV Three cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.7 | 135 | 107 | 0.9 | 0.2 | 1.8 | 13.3 | 259 | 231 |
| 2.5 | 0.7 | 1.8 | 11.5 | 171 | 125 | 0.9 | 0.2 | 1.8 | 14.1 | 304 | 259 |
| 4 | 0.7 | 1.8 | 12.6 | 225 | 152 | 0.9 | 0.2 | 1.8 | 15.2 | 370 | 297 |
| 6 | 0.7 | 1.8 | 13.7 | 291 | 182 | 0.9 | 0.2 | 1.8 | 16.3 | 449 | 341 |
| 10 | 0.7 | 1.8 | 16.3 | 429 | 250 | 0.9 | 0.2 | 1.8 | 18.9 | 618 | 438 |
| 16 | 0.7 | 1.8 | 18.2 | 609 | 324 | 0.9 | 0.2 | 1.8 | 20.8 | 820 | 534 |
| 25 | 0.9 | 1.8 | 21.4 | 907 | 455 | 0.9 | 0.2 | 1.8 | 24.0 | 1154 | 703 |
| 35 | 0.9 | 1.8 | 23.6 | 1194 | 567 | 0.9 | 0.2 | 1.8 | 26.2 | 1466 | 840 |
| 50 | 1.0 | 1.8 | 26.6 | 1570 | 722 | 0.9 | 0.2 | 1.9 | 29.4 | 1891 | 1042 |
| 70 | 1.1 | 1.9 | 30.9 | 2208 | 983 | 1.2 | 0.2 | 2.1 | 35.7 | 2936 | 1711 |
| 95 | 1.1 | 2.1 | 35.0 | 2995 | 1294 | 1.2 | 0.5 | 2.2 | 39.6 | 3794 | 2093 |
| 120 | 1.2 | 2.2 | 38.8 | 3741 | 1595 | 1.2 | 0.5 | 2.4 | 43.6 | 4642 | 2496 |
| 150 | 1.4 | 2.3 | 43.1 | 4601 | 1953 | 1.2 | 0.5 | 2.5 | 47.9 | 5598 | 2950 |
| 185 | 1.6 | 2.5 | 47.8 | 5738 | 2425 | 1.4 | 0.5 | 2.7 | 53.0 | 6851 | 3538 |
| 240 | 1.7 | 2.7 | 54.0 | 7462 | 3107 | 1.4 | 0.5 | 2.9 | 59.2 | 8711 | 4356 |
| 300 | 1.8 | 2.9 | 59.6 | 9283 | 3820 | 1.4 | 0.5 | 3.1 | 64.8 | 10655 | 5192 |
| 400 | 2.0 | 3.1 | 66.0 | 11771 | 4786 | 1.4 | 0.5 | 3.3 | 71.2 | 13284 | 6299 |
| Rated voltage 0.6/1kV Four cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 11.4 | 160 | 123 | 0.9 | 0.2 | 1.8 | 14.0 | 292 | 255 |
| 2.5 | 0.7 | 1.8 | 12.4 | 207 | 147 | 0.9 | 0.2 | 1.8 | 15.0 | 351 | 290 |
| 4 | 0.7 | 1.8 | 13.6 | 277 | 179 | 0.9 | 0.2 | 1.8 | 16.2 | 434 | 337 |
| 6 | 0.7 | 1.8 | 14.8 | 362 | 217 | 0.9 | 0.2 | 1.8 | 17.4 | 533 | 389 |
| 10 | 0.7 | 1.8 | 17.7 | 542 | 302 | 0.9 | 0.2 | 1.8 | 20.3 | 746 | 507 |
| 16 | 0.7 | 1.8 | 19.8 | 777 | 396 | 0.9 | 0.2 | 1.8 | 22.4 | 1005 | 625 |
| 25 | 0.9 | 1.8 | 23.5 | 1169 | 566 | 0.9 | 0.2 | 1.8 | 26.1 | 1440 | 838 |
| 35 | 0.9 | 1.8 | 25.9 | 1546 | 710 | 0.9 | 0.2 | 1.9 | 28.7 | 1858 | 1022 |
| 50 | 1.0 | 1.9 | 29.5 | 2054 | 923 | 1.2 | 0.2 | 2.1 | 34.3 | 2751 | 1620 |
| 70 | 1.1 | 2.1 | 34.4 | 2909 | 1275 | 1.2 | 0.2 | 2.2 | 39.0 | 3695 | 2061 |
| 95 | 1.1 | 2.2 | 38.8 | 3930 | 1661 | 1.2 | 0.5 | 2.4 | 43.6 | 4831 | 2563 |
| 120 | 1.2 | 2.3 | 43.1 | 4913 | 2051 | 1.2 | 0.5 | 2.5 | 47.9 | 5909 | 3048 |
| 150 | 1.4 | 2.5 | 48.0 | 6067 | 2537 | 1.4 | 0.5 | 2.7 | 53.2 | 7184 | 3654 |
| 185 | 1.6 | 2.7 | 53.3 | 7566 | 3148 | 1.4 | 0.5 | 2.8 | 58.3 | 8772 | 4355 |
| 240 | 1.7 | 2.9 | 60.2 | 9839 | 4033 | 1.4 | 0.5 | 3.1 | 65.4 | 11225 | 5419 |
| 300 | 1.8 | 3.1 | 66.4 | 12242 | 4957 | 1.4 | 0.5 | 3.3 | 71.6 | 13764 | 6479 |
| 400 | 2.0 | 3.3 | 73.5 | 15526 | 6212 | 1.4 | 0.5 | 3.5 | 78.7 | 17205 | 7891 |
| Rated voltage 0.6/1kV Five cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 12.2 | 186 | 140 | 0.9 | 0.2 | 1.8 | 14.8 | 328 | 281 |
| 2.5 | 0.7 | 1.8 | 13.3 | 244 | 168 | 0.9 | 0.2 | 1.8 | 15.9 | 398 | 322 |
| 4 | 0.7 | 1.8 | 14.6 | 329 | 207 | 0.9 | 0.2 | 1.8 | 17.2 | 498 | 376 |
| 6 | 0.7 | 1.8 | 16.0 | 434 | 254 | 0.9 | 0.2 | 1.8 | 18.6 | 619 | 439 |
| 10 | 0.7 | 1.8 | 19.2 | 655 | 356 | 0.9 | 0.2 | 1.8 | 21.8 | 877 | 578 |
| 16 | 0.7 | 1.8 | 21.7 | 948 | 472 | 0.9 | 0.2 | 1.8 | 24.3 | 1199 | 723 |
| 25 | 0.9 | 1.8 | 25.7 | 1432 | 679 | 0.9 | 0.2 | 1.9 | 28.5 | 1742 | 989 |
| 35 | 0.9 | 1.9 | 28.6 | 1914 | 869 | 0.9 | 0.2 | 2.0 | 31.4 | 2257 | 1213 |
| 50 | 1.0 | 2.0 | 32.6 | 2546 | 1131 | 1.2 | 0.2 | 2.2 | 37.4 | 3310 | 1896 |
| 70 | 1.1 | 2.2 | 38.1 | 3607 | 1565 | 1.2 | 0.5 | 2.3 | 42.7 | 4473 | 2431 |
| 95 | 1.1 | 2.3 | 42.9 | 4876 | 2040 | 1.2 | 0.5 | 2.5 | 47.7 | 5868 | 3032 |
| 120 | 1.2 | 2.5 | 47.9 | 6120 | 2543 | 1.4 | 0.5 | 2.7 | 53.1 | 7235 | 3658 |
| 150 | 1.4 | 2.7 | 53.4 | 7556 | 3143 | 1.4 | 0.5 | 2.8 | 58.4 | 8765 | 4352 |
| 185 | 1.6 | 2.9 | 59.2 | 9419 | 3897 | 1.4 | 0.5 | 3.0 | 64.2 | 10752 | 5230 |
| 240 | 1.7 | 3.1 | 66.9 | 12249 | 4992 | 1.4 | 0.5 | 3.3 | 72.1 | 13783 | 6525 |
| 300 | 1.8 | 3.4 | 74.0 | 15273 | 6168 | 1.4 | 0.5 | 3.5 | 79.0 | 16925 | 7820 |
| 400 | 2.0 | 3.6 | 82.0 | 19369 | 7726 | 1.4 | 0.5 | 3.8 | 88.4 | 22080 | 10437 |
| Rated voltage 0.6/1kV 3+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 12.4 | 198 | 143 | 0.9 | 0.2 | 1.8 | 15.0 | 342 | 287 |
| 4/2.5 | 0.7/0.7 | 1.8 | 13.6 | 262 | 174 | 0.9 | 0.2 | 1.8 | 16.2 | 420 | 332 |
| 6/4 | 0.7/0.7 | 1.8 | 14.8 | 343 | 211 | 0.9 | 0.2 | 1.8 | 17.4 | 515 | 382 |
| 10/6 | 0.7/0.7 | 1.8 | 17.7 | 506 | 290 | 0.9 | 0.2 | 1.8 | 20.3 | 710 | 495 |
| 16/10 | 0.7/0.7 | 1.8 | 19.8 | 724 | 378 | 0.9 | 0.2 | 1.8 | 22.4 | 953 | 607 |
| 25/16 | 0.9/0.7 | 1.8 | 23.5 | 1083 | 536 | 0.9 | 0.2 | 1.8 | 26.1 | 1354 | 807 |
| 35/16 | 0.9/0.7 | 1.8 | 25.3 | 1371 | 649 | 0.9 | 0.2 | 1.9 | 28.1 | 1676 | 954 |
| 50/25 | 1.0/0.9 | 1.9 | 28.8 | 1852 | 853 | 0.9 | 0.2 | 2.0 | 31.6 | 2198 | 1199 |
| 70/35 | 1.1/0.9 | 2.0 | 33.5 | 2593 | 1158 | 1.2 | 0.2 | 2.2 | 38.3 | 3378 | 1944 |
| 95/50 | 1.1/1.0 | 2.2 | 37.9 | 3506 | 1522 | 1.2 | 0.5 | 2.3 | 42.5 | 4367 | 2383 |
| 120/70 | 1.2/1.1 | 2.3 | 42.1 | 4452 | 1897 | 1.2 | 0.5 | 2.5 | 46.9 | 5425 | 2871 |
| 150/70 | 1.4/1.1 | 2.5 | 46.9 | 5361 | 2305 | 1.4 | 0.5 | 2.6 | 51.9 | 6430 | 3373 |
| 185/95 | 1.6/1.1 | 2.6 | 51.8 | 6732 | 2851 | 1.4 | 0.5 | 2.8 | 57.0 | 7933 | 4053 |
| 240/120 | 1.7/1.2 | 2.9 | 58.8 | 8740 | 3670 | 1.4 | 0.5 | 3.0 | 63.8 | 10065 | 4995 |
| 300/150 | 1.8/1.4 | 3.1 | 64.8 | 10850 | 4504 | 1.4 | 0.5 | 3.2 | 69.8 | 12304 | 5958 |
| 400/185 | 2.0/1.6 | 3.3 | 71.8 | 13718 | 5628 | 1.4 | 0.5 | 3.5 | 77.0 | 15359 | 7269 |
| Rated voltage 0.6/1kV 3+2 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 225 | 161 | 0.9 | 0.2 | 1.8 | 15.9 | 379 | 315 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 300 | 197 | 0.9 | 0.2 | 1.8 | 17.2 | 469 | 366 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 398 | 241 | 0.9 | 0.2 | 1.8 | 18.6 | 583 | 426 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 584 | 332 | 0.9 | 0.2 | 1.8 | 21.8 | 806 | 554 |
| 16/10 | 0.7/0.7 | 1.8 | 21.8 | 844 | 439 | 0.9 | 0.2 | 1.8 | 24.4 | 1096 | 691 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1262 | 620 | 0.9 | 0.2 | 1.9 | 28.5 | 1572 | 930 |
| 35/16 | 0.9/0.7 | 1.8 | 27.5 | 1557 | 740 | 0.9 | 0.2 | 1.9 | 30.3 | 1889 | 1072 |
| 50/25 | 1.0/0.9 | 2.0 | 31.6 | 2148 | 998 | 1.2 | 0.2 | 2.1 | 36.2 | 2873 | 1724 |
| 70/35 | 1.1/0.9 | 2.1 | 36.7 | 2993 | 1350 | 1.2 | 0.2 | 2.3 | 41.5 | 3849 | 2206 |
| 95/50 | 1.1/1.0 | 2.3 | 41.5 | 4037 | 1770 | 1.2 | 0.5 | 2.4 | 46.1 | 4976 | 2709 |
| 120/70 | 1.2/1.1 | 2.4 | 46.1 | 5186 | 2223 | 1.4 | 0.5 | 2.6 | 51.3 | 6262 | 3299 |
| 150/70 | 1.4/1.1 | 2.6 | 51.5 | 6133 | 2669 | 1.4 | 0.5 | 2.8 | 56.7 | 7328 | 3863 |
| 185/95 | 1.6/1.1 | 2.8 | 57.1 | 7789 | 3341 | 1.4 | 0.5 | 3.0 | 62.3 | 9106 | 4658 |
| 240/120 | 1.7/1.2 | 3.0 | 64.5 | 10040 | 4255 | 1.4 | 0.5 | 3.2 | 69.7 | 11521 | 5736 |
| 300/150 | 1.8/1.4 | 3.3 | 71.3 | 12479 | 5251 | 1.4 | 0.5 | 3.4 | 76.3 | 14074 | 6845 |
| 400/185 | 2.0/1.6 | 3.5 | 79.0 | 15742 | 6547 | 1.4 | 0.5 | 3.7 | 85.4 | 18358 | 9163 |
| Rated voltage 0.6/1kV 4+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 235 | 165 | 0.9 | 0.2 | 1.8 | 15.9 | 389 | 319 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 315 | 202 | 0.9 | 0.2 | 1.8 | 17.2 | 483 | 371 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 416 | 247 | 0.9 | 0.2 | 1.8 | 18.6 | 601 | 432 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 620 | 344 | 0.9 | 0.2 | 1.8 | 21.8 | 842 | 566 |
| 16/10 | 0.7/0.7 | 1.8 | 21.7 | 896 | 455 | 0.9 | 0.2 | 1.8 | 24.3 | 1146 | 706 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1347 | 650 | 0.9 | 0.2 | 1.9 | 28.5 | 1657 | 960 |
| 35/16 | 0.9/0.7 | 1.9 | 28.2 | 1742 | 811 | 0.9 | 0.2 | 1.9 | 30.8 | 2067 | 1136 |
| 50/25 | 1.0/0.9 | 2.0 | 32.1 | 2347 | 1065 | 1.2 | 0.2 | 2.1 | 36.7 | 3083 | 1802 |
| 70/35 | 1.1/0.9 | 2.2 | 37.5 | 3308 | 1466 | 1.2 | 0.5 | 2.3 | 42.1 | 4161 | 2318 |
| 95/50 | 1.1/1.0 | 2.3 | 42.2 | 4456 | 1905 | 1.2 | 0.5 | 2.5 | 47.0 | 5432 | 2881 |
| 120/70 | 1.2/1.1 | 2.5 | 47.1 | 5663 | 2394 | 1.4 | 0.5 | 2.6 | 52.1 | 6736 | 3466 |
| 150/70 | 1.4/1.1 | 2.7 | 52.6 | 6857 | 2918 | 1.4 | 0.5 | 2.8 | 57.6 | 8048 | 4109 |
| 185/95 | 1.6/1.1 | 2.8 | 58.1 | 8591 | 3606 | 1.4 | 0.5 | 3.0 | 63.3 | 9931 | 4946 |
| 240/120 | 1.7/1.2 | 3.1 | 65.8 | 11159 | 4638 | 1.4 | 0.5 | 3.3 | 71.0 | 12668 | 6146 |
| 300/150 | 1.8/1.4 | 3.3 | 72.6 | 13860 | 5693 | 1.4 | 0.5 | 3.5 | 77.8 | 15518 | 7351 |
| 400/185 | 2.0/1.6 | 3.6 | 80.6 | 17573 | 7154 | 1.4 | 0.5 | 3.8 | 87.0 | 20238 | 9819 |
4. Our Factory
5. Our Honor
6. Contact Details
DAN ZHAO | Taifeng Cable Co., Ltd
Office Add: Heda Center, No.177 Tailiu Road, Shibei District, Qingdao, China
Factory Add: Taifeng Road,Da Caozhuang Administritive District,China
Tel: 86-532-85611887 | Mobile: +86-17863817629
Web: taifengcable.en.
We are China 1/2/3/4/5 Core PVC XLPE Insulated Armoured Sta/Swa Electric Wire Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 1/2/3/4/5 Core Products
Popular Electric Cable Products
Copper Conductor PVC Insulated PVC Sheathed Control Cable Kvv
Low Smoke Zero Halogen Power Cable for Size of 4X120
11kv Aluminum/Copper Conductor, XLPE/PVC Insulated Low Smoke Zero Halogen Sheath Cable
Plain Circular Solid Copper Conductor Electrical Cable Wire PVC Insulation
Popular Power Cable Products
AAC AAAC ACSR, Overhead Bare Conductor.
2016 Overhead Conductor AAC/AAAC/ACSR/Bare Conductors
0.6/1kv, 4 Core, Cu / XLPE / Swa / PVC / PE Power Cable
Construction Underground China Mv-90 Urd Cable Medium Voltage Power Mv90, Mv105
11kv Medium Voltage Overhead Cable 3X1X120mm2
Power Cable VDE Standard Nyy, Nayy, Na2xy, N2xy, N2xry Cable
Popular taifengcable Products
4mm2 Electrical DC PV Solar Cable Photovoltaic Wire Type Anti Ultraviolet Radiation PV Cables PV1-F
95mm 120mm XLPE Insulated 3 Core Low Voltage Power Cable
UL Certified 600V 8 10 12 AWG Electric Wire Thhn
Conductor Rigid DIN Cupru Fy 1.5 mm Clasa De Flexibilitate 1 Izolatie PVC
1X2.5mm2 Tinned Copper Electrical Solar Photovoltaic PV Cable
PV-1f 4AWG Sunlight Resistant Electric Electrical PV Solar Power Cable
Tags: 1/2/3/4/5 Core, Electric Cable, Power Cable, taifengcable