10kv 3 Cores Cold Shrink Cable Connector Set Straight Joint Kit
10kv 3 Cores Cold Shrink Cable Connector Set Straight Joint Kit image
Get Latest Price Request a quote
- Overview
- Product Description
- Detailed Photos
- Product Parameters
- Recommended Product
- Company Profile
- Packaging & Shipping
- FAQ
Basic Info.
Packaging & Delivery
Product Description
Cold-shrinkable cable termination kit & straight joint kit
0.6/1KV-Cold Shrinkable Cable Accessories
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
0.6/1kV 3-cores Cold Shrinkable Termination Kits | VLZ-1/3.0 | 10~16 | 0.6/1kV 3-cores Cold Shrinkable Joint | VLJ-1/3.0 | 10~16 |
VLZ-1/3.1 | 25~50 | VLJ-1/3.1 | 25~50 | ||
VLZ-1/3.2 | 70~120 | VLJ-1/3.2 | 70~120 | ||
VLZ-1/3.3 | 150~240 | VLJ-1/3.3 | 150~240 | ||
VLZ-1/3.4 | 300~400 | VLJ-1/3.4 | 300~400 | ||
0.6/1kV 4-cores Cold Shrinkable Termination Kits | VLZ-1/4.0 | 10~16 | 0.6/1kV 4-cores Cold Shrinkable Joint | VLJ-1/4.0 | 10~16 |
VLZ-1/4.1 | 25~50 | VLJ-1/4.1 | 25~50 | ||
VLZ-1/4.2 | 70~120 | VLJ-1/4.2 | 70~120 | ||
VLZ-1/4.3 | 150~240 | VLJ-1/4.3 | 150~240 | ||
VLZ-1/4.4 | 300~400 | VLJ-1/4.4 | 300~400 | ||
0.6/1kV 5-cores Cold Shrinkable Termination Kits | VLZ-1/5.0 | 10~16 | 0.6/1kV 5-cores Cold Shrinkable Joint | VLJ-1/5.0 | 10~16 |
VLZ-1/5.1 | 25~50 | VLJ-1/5.1 | 25~50 | ||
VLZ-1/5.2 | 70~120 | VLJ-1/5.2 | 70~120 | ||
VLZ-1/5.3 | 150~240 | VLJ-1/5.3 | 150~240 | ||
VLZ-1/5.4 | 300~400 | VLJ-1/5.4 | 300~400 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage Test | 4kV/1min,No breakdown no flashover | Pass,meet the requirements | |||
Power Frequency Voltage Test | 2.4kV/4 hours,No breakdown no flashover | Pass,meet the requirements |
8.7/15KV-Cold Shrinkable Cable Accessories
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
8.7/15kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-10/1.1 | 25~50 |
VLN-10/3.2 | 70~120 | VLN-10/1.2 | 70~120 | ||
VLN-10/3.3 | 150~240 | VLN-10/1.3 | 150~240 | ||
VLN-10/3.4 | 300~400 | VLN-10/1.4 | 300~400 | ||
VLN-10/3.5 | 500~630 | VLN-10/1.5 | 500~630 | ||
8.7/15kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-10/1.1 | 25~50 |
VLW-10/3.2 | 70~120 | VLW-10/1.2 | 70~120 | ||
VLW-10/3.3 | 150~240 | VLW-10/1.3 | 150~240 | ||
VLW-10/3.4 | 300~400 | VLW-10/1.4 | 300~400 | ||
VLW-10/3.5 | 500~630 | VLW-10/1.5 | 500~630 | ||
8.7/15kV 3-cores Cold Shrinkable Joint | VLJ-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Joint | VLJ-10/1.1 | 25~50 |
VLJ-10/3.2 | 70~120 | VLJ-10/1.2 | 70~120 | ||
VLJ-10/3.3 | 150~240 | VLJ-10/1.3 | 150~240 | ||
VLJ-10/3.4 | 300~400 | VLJ-10/1.4 | 300~400 | ||
VLJ-10/3.5 | 500~630 | VLJ-10/1.5 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 39kV 5min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 15kV, Discharge volume≤10pc | Pass | |||
Impulse Voltage Test | Under 95kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 23kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC) | Under 15kV, Discharge volume≤10pc | Pass | |||
Constant load Cycle Test | The conductor applied voltage 23kV, and heated to (95-100ºC). In which the temperature stability 2h, cooling 3h, a total of 60 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC,and at ambient temperature) | Under 15kV, Discharge volume≤10pc | Pass | |||
Thermal Stability Test | Under 23 KA, Short circuit 2 times, No visible damage | Pass | |||
Dynamic Stability Test | Under 81 KA, Short circuit 1 time, No visible damage | Pass | |||
Impulse Voltage Test | 95kV, ±10 times | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 23kV, 15min | Not Flashover and Not Breakdown | |||
Tide Temperature Test | 11kV, 300h | Not Flashover,Not Breakdown and No Overcurrent Release | |||
Salt Spray Test | 11kV, 1000h | Not Flashover,Not Breakdown and No Overcurrent Release |
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
18/20kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-10/1.1 | 35~70 |
VLN-20/3.2 | 95~185 | VLN-10/1.2 | 95~185 | ||
VLN-20/3.3 | 240~400 | VLN-10/1.3 | 240~400 | ||
VLN-20/3.4 | 500~630 | VLN-10/1.4 | 500~630 | ||
18/20kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-10/1.1 | 35~70 |
VLW-20/3.2 | 95~185 | VLW-10/1.2 | 95~185 | ||
VLW-20/3.3 | 240~400 | VLW-10/1.3 | 240~400 | ||
VLW-20/3.4 | 500~630 | VLW-10/1.4 | 500~630 | ||
18/20kV 3-cores Cold Shrinkable Joint | VLJ-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Joint | VLJ-10/1.1 | 35~70 |
VLJ-20/3.2 | 95~185 | VLJ-10/1.2 | 95~185 | ||
VLJ-20/3.3 | 240~400 | VLJ-10/1.3 | 240~400 | ||
VLJ-20/3.4 | 500~630 | VLJ-10/1.4 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 54kV 5min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 20kV, Discharge volume≤10pc | Pass | |||
Impulse Voltage Test | Under 125kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 35kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC) | Under 20kV, Discharge volume≤10pc | Pass | |||
Constant load Cycle Test | The conductor applied voltage 35kV, and heated to (95-100ºC). In which the temperature stability 2h, cooling 3h, a total of 60 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC,and at ambient temperature) | Under 20kV, Discharge volume≤10pc | Pass | |||
Thermal Stability Test | Under 23 KA, Short circuit 2 times, No visible damage | Pass | |||
Dynamic Stability Test | Under 81 KA, Short circuit 1 time, No visible damage | Pass | |||
Impulse Voltage Test | 125kV, ±10 times | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 30kV, 15min | Not Flashover and Not Breakdown | |||
Tide Temperature Test | 15kV, 300h | Not Flashover,Not Breakdown and No Overcurrent Release | |||
Salt Spray Test | 15kV, 1000h | Not Flashover,Not Breakdown and No Overcurrent Release |
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
26/35kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-35/1.1 | 35~70 |
VLN-35/3.2 | 120~185 | VLN-35/1.2 | 95~185 | ||
VLN-35/3.3 | 240~400 | VLN-35/1.3 | 240~400 | ||
VLN-35/3.4 | 500~630 | VLN-35/1.4 | 500~630 | ||
26/35kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-35/1.1 | 35~70 |
VLW-35/3.2 | 120~185 | VLW-35/1.2 | 95~185 | ||
VLW-35/3.3 | 240~400 | VLW-35/1.3 | 240~400 | ||
VLW-35/3.4 | 500~630 | VLW-35/1.4 | 500~630 | ||
26/35kV 3-cores Cold Shrinkable Joint | VLJ-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Joint | VLJ-35/1.1 | 35~70 |
VLJ-35/3.2 | 120~185 | VLJ-35/1.2 | 95~185 | ||
VLJ-35/3.3 | 240~400 | VLJ-35/1.3 | 240~400 | ||
VLJ-35/3.4 | 500~630 | VLJ-35/1.4 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 105kV 1min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 39kV, Discharge volume≤10pc | Pass | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 23kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Impulse Voltage Test | Under 250kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
DC Voltage | 156kV, 15min | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 104kV, 4h | Not Flashover and Not Breakdown |
View more products,you can click photos…
66~500kV High Voltage Cable Accessories 1~35kV Heat Shrink Cable Accessories Grounding Box
Customized Silicone Rubber Protector Heat Shrinkable Tubing Explosion Proof Box
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China 10kv 3 Cores Cold Shrink Cable Connector Set Straight Joint Kit manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 10kv 3 Cores Cold Shrink Cable Connector Set Straight Joint Kit Products
Popular Cold Shrink Joint Kit Products
Outdoor Cold Shrinkable Termination Kits Indoor Cable Cold Shrink Joint Kit
Cold Shrink Silicone Rubber Joint Kit Cable Accessories Cold Shrink Cable Straight Joint
35kv Single Core Cold Shrinkable Joint Cable Termination Kits
Cable Accessories Indoor 10kv Cold Shrink Straight Joint Kit
Easy Installation High Voltage 33kv Cold Shrink Indoor Terminal
Outdoor 10kv 3 Cores Cold Shrinkable Cable Straight Joint
Popular Indoor Termination Kit Products
20kv 3-Cores Cold Shrinkable Termination Kits
Cold Insulation Cable Accessories Cold Shrink Cable Joint Kit
Easy Installation High Voltage 33kv Cold Shrink Indoor Terminal
1kv 1~5 Cores Cold Shrinkable Straight Joint Kit
35kv Cable Accessories 3 Core Cold Shrinkable Cable Termination
35kv Single Core Cold Shrinkable Joint Cable Termination Kits
Popular jiuweielectric Products
3 Core 20kv Heat Shrinkable Accessories Outdoor Cable Termination Kit
Cable Connector Box Red Cable Joint Protection Box
Waterproof Electrical EPDM Cold Shrinking Tubing
High Standard 3: 1 4: 1 Heat Shrinkable Adhesive Dual Wall Tubing Insulation Sleeving
Telecommunication Cable Connector Sealing Silicone Rubber Cold Shrink Tube
132kv Porcelain Bushing Outdoor Termination
Tags: 10kv 3 Cores Cold Shrink Cable Connector Set Straight Joint Kit, Cold Shrink Joint Kit, Indoor Termination Kit, jiuweielectric