10kv Duplex Cable XLPE Insulated ABC Service Drop Cable
10kv Duplex Cable XLPE Insulated ABC Service Drop Cable image
Get Latest Price Request a quote
Quick Details
Product Details
(1)Production capacity:500,000km/month
(2)MOQ:1km
(3)Delivery:5~15 official days.
(4)Standards:IEC,ASTM,DIN,BS; or according to customers’ requirements.
Product Desription
(1) PHASE CONDUCTORS :
Phase conductors made of aluminium wires are circular stranded, rounded and compacted with smooth circular surface.Our products are avaible 16 mm2 as solid, 25 to 70 mm2 7 wired; from 95 mm2 to onwards as 19 wired confirming TS 11654.
(2) MESSENGER (NEUTRAL) CONDUCTOR :
Bare, round, stranded and compacted aluminium alloy (294 N/mm2).
(3) INSULATION :
Phase conductors of Aerial Bundled Cables are insulated by black coloured PE or XLPE which are weather resistant.
(4) CORE IDENTIFICATION :
Phase conductors two, three and four longitudinal ridges, street lighting conductor without ridges.
(5) USAGE AREA & ADVANTAGES OF ABC SYSTEMS
The usage of Aerial Bundled Cables in low voltage networks provides important saving in installation costs, while it ensures the same reliability and safety, replaces bare conductors in overhead distribution lines and increased very rapidly all around the world.
Your best choice → Huatong Cable Inc.
(1),More than 30 years experience.
(2) ,100,000m² factory,200 staffs,annual output 100,000 metic tons.
(3),Sound Quality Control
–Material inspection;
–manufacturing inspection;
— Finished products inspection;
— Inspection before delivery.
–Third party inspection.
— Inspection of storage at port of departure.
(4),ISO Certificated.
(5) ,Plenty of material and lobor gurantee the delivery prompt and price competitive.
(6),24/7 service.
ABC technical parameters
1. Duplex Service Drop-Aluminum Conductor
Construction:
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Standards: ASTM B-230, B-231, B-232 and B-399 & ICEA S-76-474
| Code Name |
Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft(lbs) |
Rating(Amps) | ||||||
| Size AWG |
Strand | Insulation thickness (mls) |
Size AWG |
*Strand | Breaking strength (lbs) |
XLP | POLY | XLP | POLY | |
| AAC | ||||||||||
| Pekingese | 6 | solid | 45 | 6 | 7/w | 563 | 63.5 | 61.7 | 70 | 70 |
| Collie | 6 | 7/w | 45 | 6 | 7/w | 563 | 66.8 | 63.1 | 70 | 70 |
| Dachshund | 4 | solid | 45 | 4 | 7/w | 881 | 95.5 | 93.4 | 90 | 90 |
| Spaniel | 4 | 7/w | 45 | 4 | 7/w | 881 | 100.5 | 95.4 | 90 | 90 |
| Doberman | 2 | 7/w | 45 | 2 | 7/w | 1,350 | 152.7 | 145.7 | 120 | 120 |
| Malemute | 1/0 | 19/w | 60 | 1/0 | 7/w | 1,990 | 242.6 | 234.2 | 160 | 160 |
| ACSR NEUTRAL-MESSENGER | ||||||||||
| Setter | 6 | solid | 45 | 6 | 6/1 | 1.190 | 75.0 | 73.2 | 70 | 70 |
| Shepherd | 6 | 7/w | 45 | 6 | 6/1 | 1.190 | 78.3 | 74.6 | 70 | 70 |
| Eskimo | 4 | solid | 45 | 4 | 6/1 | 1.860 | 113.7 | 111.6 | 90 | 90 |
| Terrier | 4 | 7/w | 45 | 4 | 6/1 | 1.860 | 118.7 | 113.6 | 90 | 90 |
| Chow | 2 | 7/w | 45 | 2 | 6/1 | 2.850 | 181.7 | 174.7 | 120 | 120 |
| Bull | 1/0 | 19/w | 60 | 1/0 | 6/1 | 4.380 | 288.7 | 280.3 | 160 | 160 |
| 6201 ALLOY NEUTRAL-MESSENGER | ||||||||||
| Chihuahua | 6 | solid | 45 | 6 | 7/w | 1,110 | 67.6 | 65.8 | 70 | 70 |
| Vizsla | 6 | 7/w | 45 | 6 | 7/w | 1,110 | 70.9 | 67.2 | 70 | 70 |
| Harrier | 4 | solid | 45 | 4 | 7/w | 1,760 | 102.0 | 99.9 | 90 | 90 |
| Whippet | 4 | 7/w | 45 | 4 | 7/w | 1,760 | 107.0 | 101.9 | 90 | 90 |
| Schnauzer | 2 | 7/w | 45 | 2 | 7/w | 2,800 | 163.3 | 156.2 | 120 | 120 |
| Heeler | 1/0 | 19/w | 60 | 1/0 | 7/w | 4,460 | 259.2 | 250.8 | 160 | 160 |
2. Triplex Service Drop-Aluminum Conductor
Construction:
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Standards: ASTM B-230, B-231, B-232 and B-339 & ICEA S-76-474
| Code Name |
Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft(lbs) |
Ampacity (Amps) | |||||||
| Size AWG |
Stranding | Insulation thickness (mls) |
Size AWG |
Stranding | Breaking strength (lbs) |
XLP | POLY | XLP | POLY | ||
| 6201 ALLOY NEUTRAL-MESSENGER | |||||||||||
| Minex | 6 | solid | 45 | 6 | 7 | 1,110 | 106.6 | 102.9 | 85 | 70 | |
| Hippa | 6 | 7/w | 45 | 6 | 7 | 1,110 | 113.2 | 105.7 | 85 | 70 | |
| Prawn | 4 | solid | 45 | 4 | 7 | 1,760 | 158.4 | 154.1 | 115 | 90 | |
| Barnacles | 4 | 7/w | 45 | 4 | 7 | 1,760 | 168.3 | 158.2 | 115 | 90 | |
| Shrimp | 2 | 7/w | 45 | 2 | 7 | 2,800 | 253.7 | 239.7 | 150 | 120 | |
| Gammarus | 1/0 | 7/w | 60 | 1/0 | 7 | 4,460 | 411.7 | 386.0 | 205 | 160 | |
| Leda | 1/0 | 19/w | 60 | 1/0 | 7 | 4,460 | 402.7 | 386.0 | 205 | 160 | |
| Dungenese | 2/0 | 7/w | 60 | 2/0 | 7 | 5,390 | 506.8 | 476.3 | 235 | 185 | |
| Cyclops | 2/0 | 19/w | 60 | 2/0 | 7 | 5,390 | 495.3 | 476.3 | 235 | 185 | |
| Flustra | 3/0 | 19/w | 60 | 3/0 | 7 | 6,790 | 611.4 | 589.1 | 275 | 215 | |
| Lepas | 4/0 | 19/w | 60 | 4/0 | 7 | 8,560 | 757.1 | 730.5 | 315 | 245 | |
| 6201 ALLOY REDUCED NEUTRAL-MESSENGER | |||||||||||
| Artemia | 4 | solid | 45 | 6 | 7 | 1,110 | 141.4 | 137.1 | 115 | 90 | |
| Crab | 4 | 7/w | 45 | 6 | 7 | 1,110 | 151.3 | 141.2 | 115 | 90 | |
| Solaster | 2 | 7/w | 45 | 4 | 7 | 1,760 | 226.6 | 212.6 | 150 | 120 | |
| Sandcrab | 1/0 | 7/w | 60 | 2 | 7 | 2,800 | 368.8 | 343.1 | 205 | 160 | |
| Echinus | 1/0 | 19/w | 60 | 2 | 7 | 2,800 | 358.8 | 343.1 | 205 | 160 | |
| Crayfish | 2/0 | 7/w | 60 | 1 | 7 | 3,530 | 452.6 | 422.5 | 235 | 185 | |
| Sipho | 2/0 | 19/w | 60 | 1 | 7 | 3,530 | 441.0 | 422.5 | 235 | 185 | |
| Fulgar | 3/0 | 19/w | 60 | 1/0 | 7 | 4,460 | 543.4 | 521.1 | 275 | 215 | |
| Arca | 4/0 | 19/w | 60 | 2/0 | 7 | 5,390 | 671.2 | 644.6 | 315 | 245 | |
| Code Name |
Phase Conductors | Bare Neutral | Weight Per 1000 ft.(lbs) |
Ampacity (Amps) | |||||||
| Size AWG or MCM |
Stranding | Insulation thickness (mls) |
Size (AWG) |
*Stranding | Rated strength (lbs) |
XLP | Poly | XLP | Poly | ||
| AAC NEUTRAL-MESSENGER | |||||||||||
| Haiotis | 6 | solid | 45 | 6 | 7 | 563 | 102.5 | 98.8 | 85 | 70 | |
| Patella | 6 | 7/w | 45 | 6 | 7 | 563 | 109.1 | 101.6 | 85 | 70 | |
| Fusus | 4 | solid | 45 | 4 | 7 | 881 | 151.9 | 147.6 | 115 | 90 | |
| Oyster | 4 | 7/w | 45 | 4 | 7 | 881 | 161.8 | 151.7 | 115 | 90 | |
| Clam | 2 | 7/w | 45 | 2 | 7 | 1,350 | 243.2 | 229.2 | 150 | 120 | |
| Murex | 1/0 | 7/w | 60 | 1/0 | 7 | 1,990 | 395.1 | 369.4 | 205 | 160 | |
| Purpura | 1/0 | 19/w | 60 | 1/0 | 7 | 1,990 | 386.1 | 369.4 | 205 | 160 | |
| Nassa | 2/0 | 7/w | 60 | 2/0 | 7 | 2,510 | 485.8 | 455.3 | 235 | 185 | |
| Melita | 3/0 | 19/w | 60 | 3/0 | 19 | 3,310 | 585.2 | 562.9 | 275 | 215 | |
| Portunus | 4/0 | 19/w | 60 | 4/0 | 19 | 4,020 | 723.9 | 697.3 | 315 | 245 | |
| Nannynose | 336.4 | 19/w | 80 | 336.4 | 19 | 6,146 | 1160.4 | 1118.0 | 420 | 325 | |
| WITH FULL SIZE ACSR MESSENGER | |||||||||||
| Paludina | 6 | solid | 45 | 6 | 6/1 | 1,190 | 114 | 113 | 85 | 70 | |
| Voluta | 6 | 7/w | 45 | 6 | 6/1 | 1,190 | 120 | 113 | 85 | 70 | |
| Whelk | 4 | solid | 45 | 4 | 6/1 | 1,860 | 169 | 165 | 115 | 90 | |
| Periwinkle | 4 | 7/w | 45 | 4 | 6/1 | 1,860 | 176 | 172 | 115 | 90 | |
| Conch | 2 | 7/w | 45 | 2 | 6/1 | 2,850 | 267 | 261 | 150 | 120 | |
| Neritina | 1/0 | 7/w | 60 | 1/0 | 6/1 | 4,380 | 530 | 419 | 205 | 160 | |
| Cenia | 1/0 | 19/w | 60 | 1/0 | 6/1 | 4,380 | 426 | 416 | 205 | 160 | |
| Runcina | 2/0 | 7/w | 60 | 2/0 | 6/1 | 5,310 | 530 | 519 | 235 | 185 | |
| Triton | 2/0 | 19/w | 60 | 2/0 | 6/1 | 5,310 | 526 | 514 | 235 | 185 | |
| Cherrystone | 3/0 | 7/w | 60 | 3/0 | 6/1 | 6,620 | 656 | 643 | 250 | 200 | |
| Mursia | 3/0 | 19/w | 60 | 3/0 | 6/1 | 6,620 | 650 | 638 | 250 | 200 | |
| Razor | 4/0 | 7/w | 60 | 4/0 | 6/1 | 8,350 | 814 | 799 | 315 | 245 | |
| Zuzara | 4/0 | 19/w | 60 | 4/0 | 6/1 | 8,350 | 805 | 792 | 315 | 245 | |
| Limpet | 336.4 | 19/w | 80 | 336.4 | 18/1 | 8,680 | 1209 | 1167 | 420 | 325 | |
| Code Name |
Phase Conductors | Bare Neutral | Weight Per 1000 ft.(lbs) |
Ampacity (Amps) | |||||||
| Size AWG or MCM | Stranding | Insulation thickness (mls) |
Size (AWG) |
Stranding | Rated strength (lbs) |
XLP | Poly | XLP | Poly | ||
| WITH ACSR REDUCED SIZE MESSENGER | |||||||||||
| Scallop | 4 | Solid | 45 | 6 | 6/1 | 1,190 | 148 | 144 | 115 | 90 | |
| Strombus | 4 | 7/w | 45 | 6 | 6/1 | 1,190 | 158 | 148 | 115 | 90 | |
| Cockle | 2 | 7/ w | 45 | 4 | 6/1 | 1,860 | 233 | 227 | 150 | 120 | |
| Janthina | 1/0 | 7/ w | 60 | 2 | 6/1 | 2,850 | 376 | 365 | 205 | 160 | |
| Ranella | 1/0 | 19/ w | 60 | 2 | 6/1 | 2,850 | 372 | 362 | 205 | 160 | |
| Cavolinia | 2/0 | 7/ w | 60 | 1 | 6/1 | 3,550 | 462 | 451 | 235 | 185 | |
| Clio | 2/0 | 19/ w | 60 | 1 | 6/1 | 3,550 | 458 | 446 | 235 | 185 | |
| Sanddollar | 3/0 | 7/ w | 60 | 1/0 | 6/1 | 4,380 | 570 | 557 | 275 | 215 | |
| Aega | 3/0 | 19/ w | 60 | 1/0 | 6/1 | 4,380 | 565 | 552 | 275 | 215 | |
| Cuttlefish | 4/0 | 7/ w | 60 | 2/0 | 6/1 | 5,310 | 706 | 691 | 315 | 245 | |
| Cerapus | 4/0 | 19/ w | 60 | 2/0 | 6/1 | 5,310 | 699 | 684 | 315 | 245 | |
| Cowry | 336.4 | 19/ w | 80 | 4/0 | 6/1 | 8,350 | 1135 | 1093 | 420 | 325 | |
3. Quadruplex Service Drop-Aluminum Conductor
Construction:
Conductors are concentrically stranded, compressed 1350-H19 aluminum, insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR, One conductor is manufactured with an extruded ridge for phase identification.
Standards: ASTM B-230, B-231, B-232, B-339 & ICEA S-76 -474
| Code Name |
Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft(lbs) |
Rating(Amps) | ||||||
| Size AWG |
Strand | Insulation thickness (mls) |
Size AWG |
Strand | Breaking strength (lbs) |
XLP | POLY | XLP | POLY | |
| AAC NEUTRAL-MESSNGER | ||||||||||
| Clydesdale | 4 | Solid | 45 | 4 | 7 | 881 | 208 | 201.8 | 100 | 80 |
| Pinto | 4 | 7/w | 45 | 4 | 7 | 881 | 223 | 207.9 | 100 | 80 |
| Mustang | 2 | 7/w | 45 | 2 | 7 | 1,350 | 333 | 312.6 | 135 | 105 |
| Criollo | 1/0 | 19/w | 60 | 1/0 | 7 | 1,990 | 529 | 504.5 | 180 | 140 |
| Percheron | 2/0 | 19/w | 60 | 2/0 | 7 | 2,510 | 649 | 620.5 | 205 | 160 |
| Hanoverian | 3/0 | 19/w | 60 | 3/0 | 19 | 3,310 | 799 | 765.6 | 235 | 185 |
| Oldenburg | 4/0 | 19/w | 60 | 4/0 | 19 | 4,020 | 986 | 946.7 | 275 | 210 |
| Lippizaner | 336.4 | 19/w | 80 | 336.4 | 19 | 6,146 | 1,546 | 1,519.2 | 370 | 280 |
| ACSR NEUTRAL-MESSNGER | ||||||||||
| Morochuca | 6 | Solid | 45 | 6 | 6/1 | 1,190 | 152 | 147.4 | 75 | 60 |
| Chola | 6 | 7/w | 45 | 6 | 6/1 | 1,190 | 162 | 151.7 | 75 | 60 |
| Morgan | 4 | Solid | 45 | 4 | 6/1 | 1,860 | 226 | 220 | 100 | 80 |
| Hackney | 4 | 7/w | 45 | 4 | 6/1 | 1,860 | 241 | 226.1 | 100 | 80 |
| Palomino | 2 | 7/w | 45 | 2 | 6/1 | 2,850 | 362 | 342.6 | 135 | 105 |
| Costena | 1/0 | 19/w | 60 | 1/0 | 6/1 | 4,380 | 575 | 550.6 | 180 | 140 |
| Grullo | 2/0 | 19/w | 60 | 2/0 | 6/1 | 5,310 | 707 | 678.7 | 205 | 160 |
| Suffolk | 3/0 | 19/w | 60 | 3/0 | 6/1 | 6,620 | 872 | 838.9 | 235 | 185 |
| Appaloosa | 4/0 | 19/w | 60 | 4/0 | 6/1 | 8,350 | 1079 | 1039.2 | 275 | 210 |
| Bronco | 336.4 | 19/w | 80 | 336.4 | 18/1 | 8,580 | 1613 | 1568.2 | 370 | 280 |
| Gelding | 336.4 | 19/w | 80 | 4/0 | 6/1 | 8,350 | 1548 | 1494.3 | 370 | 280 |
| Code Name |
Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft(lbs) |
Rating(Amps) | ||||||
| Size AWG |
Strand | Insulation thickness (mls) |
Size AWG |
Strand | Breaking strength (lbs) |
XLP | POLY | XLP | POLY | |
| 6201 ALLOY NEUTRAL-MESSENGER | ||||||||||
| Bay | 6 | Solid | 45 | 6 | 7 | 1,110 | 145 | 140.0 | 75 | 60 |
| French Coach | 6 | 7/w | 45 | 6 | 7 | 1,110 | 155 | 144.3 | 75 | 60 |
| German Coach | 4 | Solid | 45 | 4 | 7 | 1,760 | 214 | 208.3 | 100 | 80 |
| Arabian | 4 | 7/w | 45 | 4 | 7 | 1,760 | 229 | 214.4 | 100 | 80 |
| Belgian | 2 | 7/w | 45 | 2 | 7 | 2,800 | 344 | 323.1 | 135 | 105 |
| Shetland | 1/0 | 19/w | 60 | 1/0 | 7 | 4,460 | 546 | 521.1 | 180 | 140 |
| Thoroughbred | 2/0 | 19/w | 60 | 2/0 | 7 | 5,390 | 670 | 641.5 | 205 | 160 |
| Trotter | 3/0 | 19/w | 60 | 3/0 | 7 | 6,790 | 825 | 791.8 | 235 | 185 |
| Walking | 4/0 | 19/w | 60 | 4/0 | 7 | 8,560 | 1019 | 979.7 | 275 | |
We are China 10kv Duplex Cable XLPE Insulated ABC Service Drop Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 10kv Duplex Cable Products
Popular 150mm Aerial Cable Products
150mm 0.6/1kv Al/XLPE Aerial Bundle Cable
150mm 0.6/1kv Al/XLPE Aerial Cable
Popular ABC Service Drop Cable Products
3 Cores Overhead Electrica Aluminum Cable ABC Service Drop Line
Overhead XLPE Covered Triplex Service Drop ABC Cable
Hot Seller ABC Overhead Duplex Drop Cable
High Quality 0.6/1kv ABC Service Drop Cable
3 Cores Overhead Electrica Aluminum ABC Cable
0.6/1kv Overhead Aluminium Conductor Aerial Bundled Cable Overhead Insulated Cable- (ABC cable)
Popular huatongcable Products
1kv/3kv Aluminium Core Power Cable IEC60502-1 61304 60754 Standard
Overhead Aacsr (Aluminum-Alloy Conductors Steel Reinforced) ASTM B711
Bare ACSR Conductor 400mm2 for Power Distribution
450/750V Aluminium/Copper Conductor Wire PVC Insulated Wire
6.35/11 Kv Cabo Xhiav 3 X 95 Power Cable
Tags: 10kv Duplex Cable, 150mm Aerial Cable, ABC Service Drop Cable, huatongcable