11kv XLPE Insulated Unarmoured Power Cable
11kv XLPE Insulated Unarmoured Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Application:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.
Prpperty:
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.
Specification:
Standard:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km |
25 | 6.0 | 2.5 | 0.12 | 1.5 | 17.6 | 0.34 | 0.49 | 1.2000 | 0.7270 |
35 | 7.0 | 2.5 | 0.12 | 1.5 | 18.5 | 0.39 | 0.60 | 0.8680 | 0.5240 |
50 | 8.3 | 2.5 | 0.12 | 1.6 | 20.0 | 0.46 | 0.74 | 0.6410 | 0.3870 |
70 | 9.7 | 2.5 | 0.12 | 1.6 | 21.5 | 0.55 | 0.96 | 0.4430 | 0.2680 |
95 | 11.3 | 2.5 | 0.12 | 1.7 | 23.3 | 0.66 | 1.23 | 0.3200 | 0.1930 |
120 | 13 | 2.5 | 0.12 | 1.7 | 24.8 | 0.77 | 1.48 | 0.2530 | 0.1530 |
150 | 14.6 | 2.5 | 0.12 | 1.8 | 26.4 | 0.87 | 1.77 | 0.2060 | 0.1240 |
185 | 15.9 | 2.5 | 0.12 | 1.8 | 28.1 | 1.01 | 2.13 | 0.1640 | 0.0991 |
240 | 18.3 | 2.6 | 0.12 | 1.9 | 30.9 | 1.23 | 2.71 | 0.1250 | 0.0754 |
300 | 20.4 | 2.8 | 0.12 | 2.0 | 33.6 | 1.48 | 3.32 | 0.1000 | 0.0601 |
400 | 23.2 | 3.0 | 0.12 | 2.1 | 37.0 | 1.81 | 4.16 | 0.0778 | 0.0470 |
500 | 26.4 | 3.2 | 0.12 | 2.2 | 41.1 | 2.24 | 5.27 | 0.0605 | 0.0366 |
630 | 30.1 | 3.2 | 0.12 | 2.3 | 45.0 | 2.73 | 6.62 | 0.0469 | 0.0283 |
2)6/10(12)kV,6.35/11(12)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | |||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | |
25 | 6.0 | 3.4 | 0.12 | 1.5 | 19.4 | 0.40 | 0.55 | 1.2000 | 0.7270 | |
35 | 6.9 | 3.4 | 0.12 | 1.6 | 20.5 | 0.45 | 0.66 | 0.8680 | 0.5240 | |
50 | 8.2 | 3.4 | 0.12 | 1.6 | 21.8 | 0.52 | 0.80 | 0.6410 | 0.3870 | |
70 | 9.7 | 3.4 | 0.12 | 1.7 | 23.5 | 0.62 | 1.03 | 0.4430 | 0.2680 | |
95 | 11.3 | 3.4 | 0.12 | 1.7 | 25.1 | 0.73 | 1.30 | 0.3200 | 0.1930 | |
120 | 12.8 | 3.4 | 0.12 | 1.8 | 26.8 | 0.85 | 1.56 | 0.2530 | 0.1530 | |
150 | 14.2 | 3.4 | 0.12 | 1.8 | 28.2 | 0.95 | 1.85 | 0.2060 | 0.1240 | |
185 | 15.9 | 3.4 | 0.12 | 1.9 | 30.1 | 1.10 | 2.22 | 0.1640 | 0.0991 | |
240 | 18.3 | 3.4 | 0.12 | 2.0 | 32.7 | 1.33 | 2.80 | 0.1250 | 0.0754 | |
300 | 20.4 | 3.4 | 0.12 | 2.0 | 34.8 | 1.54 | 3.39 | 0.1000 | 0.0601 | |
400 | 23.2 | 3.4 | 0.12 | 2.2 | 38.0 | 1.87 | 4.22 | 0.0778 | 0.0470 | |
500 | 26.4 | 3.4 | 0.12 | 2.2 | 41.5 | 2.26 | 5.29 | 0.0605 | 0.0366 | |
630 | 30.1 | 3.4 | 0.12 | 2.4 | 45.6 | 2.78 | 6.67 | 0.0469 | 0.0283 |
3)8.7/10(15)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | |||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | |
25 | 6.0 | 4.5 | 0.12 | 1.6 | 21.8 | 0.48 | 0.63 | 1.2000 | 0.7270 | |
35 | 6.9 | 4.5 | 0.12 | 1.7 | 22.9 | 0.54 | 0.75 | 0.8680 | 0.5240 | |
50 | 8.2 | 4.5 | 0.12 | 1.7 | 24.2 | 0.61 | 0.89 | 0.6410 | 0.3870 | |
70 | 9.7 | 4.5 | 0.12 | 1.8 | 25.9 | 0.72 | 1.13 | 0.4430 | 0.2680 | |
95 | 11.3 | 4.5 | 0.12 | 1.8 | 27.5 | 0.84 | 1.40 | 0.3200 | 0.1930 | |
120 | 12.8 | 4.5 | 0.12 | 1.9 | 29.2 | 0.96 | 1.67 | 0.2530 | 0.1530 | |
150 | 14.2 | 4.5 | 0.12 | 1.9 | 30.6 | 1.06 | 1.96 | 0.2060 | 0.1240 | |
185 | 15.9 | 4.5 | 0.12 | 2.0 | 32.5 | 1.22 | 2.34 | 0.1640 | 0.0991 | |
240 | 18.3 | 4.5 | 0.12 | 2.1 | 35.1 | 1.46 | 2.93 | 0.1250 | 0.0754 | |
300 | 20.4 | 4.5 | 0.12 | 2.1 | 37.2 | 1.68 | 3.52 | 0.1000 | 0.0601 | |
400 | 23.2 | 4.5 | 0.12 | 2.2 | 40.2 | 2.00 | 4.35 | 0.0778 | 0.0470 | |
500 | 26.4 | 4.5 | 0.12 | 2.3 | 43.9 | 2.43 | 5.45 | 0.0605 | 0.0366 | |
630 | 30.1 | 4.5 | 0.12 | 2.4 | 47.8 | 2.93 | 6.83 | 0.0469 | 0.0283 |
4)12/20(24)kV, 12.7/22(24)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km |
25 | |||||||||
35 | 6.9 | 5.5 | 0.12 | 1.7 | 24.9 | 0.62 | 0.83 | 0.8680 | 0.5240 |
50 | 8.2 | 5.5 | 0.12 | 1.8 | 26.4 | 0.70 | 0.98 | 0.6410 | 0.3870 |
70 | 9.7 | 5.5 | 0.12 | 1.8 | 27.9 | 0.80 | 1.21 | 0.4430 | 0.2680 |
95 | 11.3 | 5.5 | 0.12 | 1.9 | 29.7 | 0.94 | 1.50 | 0.3200 | 0.1930 |
120 | 12.8 | 5.5 | 0.12 | 1.9 | 31.2 | 1.05 | 1.77 | 0.2530 | 0.1530 |
150 | 14.2 | 5.5 | 0.12 | 2.0 | 32.8 | 1.17 | 2.07 | 0.2060 | 0.1240 |
185 | 15.9 | 5.5 | 0.12 | 2.0 | 34.5 | 1.33 | 2.45 | 0.1640 | 0.0991 |
240 | 18.3 | 5.5 | 0.12 | 2.1 | 37.1 | 1.57 | 3.04 | 0.1250 | 0.0754 |
300 | 20.4 | 5.5 | 0.12 | 2.2 | 39.4 | 1.81 | 3.66 | 0.1000 | 0.0601 |
400 | 23.2 | 5.5 | 0.12 | 2.3 | 42.4 | 2.14 | 4.49 | 0.0778 | 0.0470 |
500 | 26.4 | 5.5 | 0.12 | 2.4 | 46.1 | 2.58 | 5.61 | 0.0605 | 0.0366 |
630 | 30.1 | 5.5 | 0.12 | 2.4 | 49.8 | 3.10 | 6.99 | 0.0469 | 0.0283 |
5)18/30(36)kV,19/33(36)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | |||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | |
25 | ||||||||||
35 | ||||||||||
50 | 8.2 | 8.0 | 0.12 | 2.0 | 31.8 | 0.95 | 1.23 | 0.6410 | 0.3870 | |
70 | 9.7 | 8.0 | 0.12 | 2.0 | 33.3 | 1.07 | 1.47 | 0.4430 | 0.2680 | |
95 | 11.3 | 8.0 | 0.12 | 2.1 | 35.1 | 1.21 | 1.78 | 0.3200 | 0.1930 | |
120 | 12.8 | 8.0 | 0.12 | 2.1 | 36.6 | 1.34 | 2.05 | 0.2530 | 0.1530 | |
150 | 14.2 | 8.0 | 0.12 | 2.2 | 38.2 | 1.47 | 2.37 | 0.2060 | 0.1240 | |
185 | 15.9 | 8.0 | 0.12 | 2.2 | 39.9 | 1.64 | 2.76 | 0.1640 | 0.0991 | |
240 | 18.3 | 8.0 | 0.12 | 2.3 | 42.5 | 1.90 | 3.37 | 0.1250 | 0.0754 | |
300 | 20.4 | 8.0 | 0.12 | 2.4 | 44.8 | 2.16 | 4.01 | 0.1000 | 0.0601 | |
400 | 23.2 | 8.0 | 0.12 | 2.4 | 47.6 | 2.52 | 4.87 | 0.0778 | 0.0470 | |
500 | 26.4 | 8.0 | 0.12 | 2.5 | 51.3 | 2.98 | 6.01 | 0.0605 | 0.0366 | |
630 | 30.1 | 8.0 | 0.12 | 2.6 | 55.2 | 3.54 | 7.43 | 0.0469 | 0.0283 |
6)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | ||
25 | 6.0 | 2.5 | 0.1 | 2.0 | 34.6 | 1.13 | 1.58 | 1.2000 | 0.7270 | ||
35 | 6.9 | 2.5 | 0.1 | 2.1 | 36.8 | 1.29 | 1.92 | 0.8680 | 0.5240 | ||
50 | 8.2 | 2.5 | 0.1 | 2.2 | 39.8 | 1.51 | 2.36 | 0.6410 | 0.3870 | ||
70 | 9.7 | 2.5 | 0.1 | 2.3 | 43.2 | 1.81 | 3.04 | 0.4430 | 0.2680 | ||
95 | 11.3 | 2.5 | 0.1 | 2.4 | 46.9 | 2.17 | 3.87 | 0.3200 | 0.1930 | ||
120 | 12.8 | 2.5 | 0.1 | 2.4 | 50.1 | 2.53 | 4.69 | 0.2530 | 0.1530 | ||
150 | 14.2 | 2.5 | 0.1 | 2.5 | 53.3 | 2.90 | 5.60 | 0.2060 | 0.1240 | ||
185 | 15.9 | 2.5 | 0.1 | 2.6 | 57.2 | 3.40 | 6.77 | 0.1640 | 0.0991 | ||
240 | 18.3 | 2.6 | 0.1 | 2.8 | 63.2 | 4.12 | 8.55 | 0.1250 | 0.0754 | ||
300 | 20.4 | 2.8 | 0.1 | 3.0 | 69.0 | 4.89 | 10.46 | 0.1000 | 0.0601 | ||
400 | 23.2 | 3.0 | 0.1 | 3.4 | 76.7 | 6.10 | 13.18 | 0.0778 | 0.0470 | ||
500 | 26.4 | 3.2 | 0.1 | 3.6 | 85.7 | 8.10 | 16.55 | 0.0605 | 0.0366 |
7)6/10(12)kV,6.35/11(12)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | |||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | |
25 | 6.0 | 3.4 | 0.1 | 2.1 | 38.7 | 1.30 | 1.75 | 1.2000 | 0.7270 | |
35 | 6.9 | 3.4 | 0.1 | 2.2 | 40.9 | 1.47 | 2.22 | 0.8680 | 0.5240 | |
50 | 8.2 | 3.4 | 0.1 | 2.3 | 43.9 | 1.70 | 2.50 | 0.6410 | 0.3870 | |
70 | 9.7 | 3.4 | 0.1 | 2.4 | 47.3 | 2.02 | 3.25 | 0.4430 | 0.2680 | |
95 | 11.3 | 3.4 | 0.1 | 2.5 | 51.0 | 2.42 | 4.12 | 0.3200 | 0.1930 | |
120 | 12.8 | 3.4 | 0.1 | 2.6 | 54.4 | 2.79 | 4.95 | 0.2530 | 0.1530 | |
150 | 14.2 | 3.4 | 0.1 | 2.7 | 57.6 | 3.17 | 5.87 | 0.2060 | 0.1240 | |
185 | 15.9 | 3.4 | 0.1 | 2.8 | 61.5 | 3.69 | 7.06 | 0.1640 | 0.0991 | |
240 | 18.3 | 3.4 | 0.1 | 2.9 | 66.9 | 4.38 | 8.82 | 0.1250 | 0.0754 | |
300 | 20.4 | 3.4 | 0.1 | 3.1 | 71.8 | 5.11 | 10.68 | 0.1000 | 0.0601 | |
400 | 23.2 | 3.4 | 0.1 | 3.3 | 78.3 | 6.24 | 13.32 | 0.0778 | 0.0470 | |
500 | 26.4 | 3.4 | 0.1 | 3.5 | 86.4 | 7.63 | 16.50 | 0.0605 | 0.0366 |
8)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | ||
25 | 6.0 | 4.5 | 0.1 | 2.3 | 43.9 | 1.57 | 2.02 | 0.9270 | 0.7270 | ||
35 | 6.9 | 4.5 | 0.1 | 2.4 | 46.0 | 1.75 | 2.38 | 0.6680 | 0.5240 | ||
50 | 8.2 | 4.5 | 0.1 | 2.4 | 48.8 | 2.00 | 2.85 | 0.4936 | 0.3870 | ||
70 | 9.7 | 4.5 | 0.1 | 2.5 | 52.3 | 2.34 | 3.57 | 0.3420 | 0.2680 | ||
95 | 11.3 | 4.5 | 0.1 | 2.6 | 55.9 | 2.75 | 4.45 | 0.2464 | 0.1930 | ||
120 | 12.8 | 4.5 | 0.1 | 2.7 | 59.4 | 3.16 | 5.32 | 0.1955 | 0.1530 | ||
150 | 14.2 | 4.5 | 0.1 | 2.8 | 62.6 | 3.57 | 6.27 | 0.1587 | 0.1240 | ||
185 | 15.9 | 4.5 | 0.1 | 2.9 | 66.4 | 4.07 | 7.45 | 0.1271 | 0.0991 | ||
240 | 18.3 | 4.5 | 0.1 | 3.1 | 72.0 | 4.82 | 9.25 | 0.0976 | 0.0754 | ||
300 | 20.4 | 4.5 | 0.1 | 3.3 | 77.0 | 5.71 | 11.28 | 0.0778 | 0.0601 | ||
400 | 23.2 | 4.5 | 0.1 | 3.4 | 83.2 | 6.78 | 13.86 | 0.0615 | 0.0470 | ||
500 | 26.4 | 4.5 | 0.1 | 3.5 | 91.1 | 8.20 | 17.32 | 0.0487 | 0.0366 |
9)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||||
mm2 | mm | mm | mm2 | mm | mm | kg/m | kg/m | Ω/km | Ω/km | ||
25 | – | ||||||||||
35 | 6.9 | 5.5 | 0.1 | 2.4 | 50.3 | 2.00 | 2.63 | 0.8680 | 0.6680 | ||
50 | 8.2 | 5.5 | 0.1 | 2.5 | 53.3 | 2.26 | 3.11 | 0.6410 | 0.4936 | ||
70 | 9.7 | 5.5 | 0.1 | 2.6 | 56.8 | 2.62 | 3.85 | 0.4430 | 0.3420 | ||
95 | 11.3 | 5.5 | 0.1 | 2.8 | 60.6 | 3.07 | 4.77 | 0.3200 | 0.2464 | ||
120 | 12.8 | 5.5 | 0.1 | 2.9 | 64.1 | 3.49 | 5.65 | 0.2530 | 0.1955 | ||
150 | 14.2 | 5.5 | 0.1 | 3.0 | 67.3 | 3.91 | 6.61 | 0.2060 | 0.1587 | ||
185 | 15.9 | 5.5 | 0.1 | 3.1 | 71.2 | 4.44 | 7.81 | 0.1640 | 0.1271 | ||
240 | 18.3 | 5.5 | 0.1 | 3.3 | 76.8 | 5.21 | 9.64 | 0.1250 | 0.0976 | ||
300 | 20.4 | 5.5 | 0.1 | 3.3 | 81.3 | 6.10 | 11.66 | 0.1000 | 0.0778 | ||
400 | 23.2 | 5.5 | 0.1 | 3.5 | 87.7 | 7.20 | 14.28 | 0.0778 | 0.0615 | ||
500 | 26.4 | 5.5 | 0.1 | 3.8 | 96.0 | 9.15 | 17.80 | 0.0605 | 0.0487 |
10)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km |
25 | |||||||||
35 | |||||||||
50 | 8.2 | 8.0 | 0.1 | 2.9 | 64.9 | 3.02 | 3.87 | 0.6410 | 0.4936 |
70 | 9.7 | 8.0 | 0.1 | 3.0 | 68.4 | 3.42 | 4.65 | 0.4430 | 0.3420 |
95 | 11.3 | 8.0 | 0.1 | 3.1 | 72.0 | 3.89 | 5.59 | 0.3200 | 0.2464 |
120 | 12.8 | 8.0 | 0.1 | 3.3 | 75.7 | 4.39 | 6.54 | 0.2530 | 0.1955 |
150 | 14.2 | 8.0 | 0.1 | 3.3 | 78.7 | 4.85 | 7.55 | 0.2060 | 0.1587 |
185 | 15.9 | 8.0 | 0.1 | 3.4 | 82.6 | 5.42 | 8.79 | 0.1640 | 0.1271 |
240 | 18.3 | 8.0 | 0.1 | 3.5 | 88.0 | 6.22 | 10.66 | 0.1250 | 0.0976 |
300 | 20.4 | 8.0 | 0.1 | 3.7 | 92.9 | 7.20 | 12.77 | 0.1000 | 0.0778 |
400 | 23.2 | 8.0 | 0.1 | 3.9 | 99.3 | 8.38 | 15.46 | 0.0778 | 0.0615 |
500 | 26.4 | 8.0 | 0.1 | 4.2 | 107.6 | 10.15 | 18.85 | 0.0605 | 0.0487 |
We are China 11kv XLPE Insulated Unarmoured Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular jpcable99 Products
Rubber Insulated Welding Cable
BS215 Standard Aluminum Conductor Steel Reinforced ACSR Conductor
Good Quality Bare Conduct ACSR/Aw
11kv Mv Aluminium 3 Core Type Cable (Armoured) Steel Catenary
Popular PVC Cable Products
Yjv XLPE Insulated PVC Sheathed Steel Tape Armoured Armored Electric Power Cable
Copper Conductor PVC PE Insulated Power Electric Wirewiring Fire Retardant Flexible Electrical Wire
Aluminum Conductor XLPE Insulated Cable
Flexibile Electric Wire PVC Electric Wire
Popular XLPE Cable Products
CU/XLPE/CTS/PVC/AWA/PVC MV Underground Copper Power Cable 6.35/11kV IEC60502-2 1X120mm2
3*70+54.6mm Overhead XLPE Insulated ABC Cable
Copper Armored Power Cable Electrical Cable for Sale
XLPE Insulated Overhead ABC Cable (Service drop cable)
18/30kv, 36kv, 33kv S/C 800sqmm XLPE Power Cable
Popular XLPE Insulated Cable Products
Low Voltage Overhead Conductor XLPE Insulated Aerial Bundled Aluminum Cable
11kv, 33kv, 66kv Middle Voltage Cable, CE Certificate
Low Smoke Halogen Free XLPE Insulated PVC Sheathed Power Cable
Overhead ABC Cable Prices 16mm2 35mm2 50mm2 XLPE Insulated Aluminum ABC Cable
11kv, 33kv, 66kv Middle Voltage Cable, ASTM Standard
0.6/1kv XLPE Insulated PVC Steel Armored Copper Electrical Power Cable
Tags: jpcable99, PVC Cable, XLPE Cable, XLPE Insulated Cable