Product Description
66-220kV High Voltage Cable Accessories
Our company provides the voltage level of 48/66kV, 64/110kV, 127/220kV and other series of cable accessories are all in accordance with IEC 60502, IEC 60840, IEC 62067, IEC 60859, IEC 62271-209, GB/T 11017, GB/T 18890, GB/T 12706, GB 311, GB 772, DL508, DL509, JB/T8144 and other standards, and have passed the stringent factory test, type test, pre-qualification test.
Termination with porcelation insulator
Scope of application
For cross linked polyethylene insulated power cables 240-3000mm2.
Suitable for large-scale chemical industry, iron and steel, power substations, coastal areas.
Features
Adoption of high-strength inorganic electric porcelain, stable performance
The stress cone is made of imported liquid silicone rubber injection molding, with a long and stable holding force and electric field uniformity.
Porcelain sleeve for the size of the umbrella structure, the whole outside the formation of a cone, has a very good anti-fouling flash, Weather resistance, anti-leakage marks, anti-electro-etching and water-repellent ability.
The terminal adopts multiple sealing structure to prevent water seepage and oil leakage during operation. water seepage and oil leakage phenomenon.
Structure & Size
1,wire clip (optional)
2,equalizing cover
3,core insulation
4,insulating oil
5,porcelain set
6,stress cone
7,fixed plate
8,support insulator
9,tail pipe
10,cable
Size /mm | 48/66kV | 64/110kV | 80/138kV | 127/220kV |
H | 1270 | 1500 | 1750 | 2500 |
A | 1510 | 1935 | 2085 | 3100 |
B | 1925 | 2155 | 2400 | 3600 |
C | 450 | 450 | 450 | 650 |
D | 200 | 200 | 200 | 300 |
E | Φ22 | Φ22 | Φ22 | Φ32 |
creepage distance | ≥2248 | ≥3906 | ≥4495 | ≥7812 |
Test Specification
All test classifications and codes:
No.# | Test Name | Code |
1 | Routine test | R |
2 | Sample test | S |
3 | Type test | T |
4 | Pre-qualification test | P |
5 | Additional test | A |
The following routine tests are performed on stress cones, epoxy bushings of GIS terminals and prefabricated intermediate joints of each product at 66kV and above.
Item | Voltage | ||||
38/66kV | 50/66kV | 64/110kV | 76/132kV | 127/220kV | |
Partial discharge | 54kV, no detectable local discharge over background | 72kV, no detectable local discharge over background | 96kV, no detectable local discharge over background | 114kV, no detectable local discharge over background | 190kV, no detectable local discharge over background |
The power frequency withstand voltage | 90kV/30min | 125kV/30min | 160kV/30min | 190kV/30min | 318kV/30min |
Sealing | Seal fittings, porcelain bushings, composite bushings for 0.25±0.01MPa/1h, no leakage | ||||
The epoxy casing was subjected to 0.6~0.7MPa/1h with no leakage. | |||||
Appearance | The products are free of damage, cracks, and other defects that may affect the quality and appearance of the products. |
66-220kV Main Test Parameters
Item | Standard | Test Category | Product Category | ||||||
48/66kV | 64/110kV | 127/220kV | Porcelain Sleeve Terminal | Composite Sleeve Terminal | GIS terminal | Straight / Insulated Joint | flexible terminal | ||
Sealing Fittings, Porcelain, Composite Sleeves | 0.25±0.01MPa/1h, no leakage | R | yes | yes | yes | – | – | ||
Epoxy Sleeve | 0.6~0.7MPa/1h, no leakage | ||||||||
Partial discharge of prefabricated parts | 72kV | 96kV | 190kV | R | yes | yes | yes | yes | yes |
Detects no more than background discharge | |||||||||
Frequency withstand voltage of prefabricated parts | 120kV | 160kV | 318kV | R | yes | yes | yes | yes | yes |
30min,no flashover, no breakdown | |||||||||
Partial discharge at room temperature | 72kV | 96kV | 190kV | T | yes | yes | yes | yes | yes |
Detects no more than background discharge | |||||||||
Thermal cycling voltage test | 96kV | 128kV | 254kV | T | yes | yes | yes | yes | yes |
20 cycles, no flashover, no breakdown | |||||||||
Partial discharge test at high temperature | 72kV | 96kV | 190kV | T | yes | yes | yes | yes | yes |
Detects no more than background discharge | |||||||||
Lightning impact test and subsequent frequency withstand voltage test | 450kV | 550kV | 1050kV | T | yes | yes | yes | yes | yes |
10 times for each positive and negative polarity | |||||||||
120kV | 160kV | 318kV | |||||||
15min, no flashover, no breakdown | |||||||||
Directly buried joint outer protective layer immersion voltage test | Two ends impact among the 60/75kV,an end of hit 30/37.5kV | Two ends impact among the 60/95kV,an end of hit 30/47.5kV | T | – | – | – | yes | – | |
Sealing test after assembly of accessories | 0.25±0.01MPa/1h, no leakage | T | yes | yes | yes | yes | yes | ||
Outdoor terminal rain frequency voltage test | 140kV | 185kV | 460kV | T | yes | yes | – | – | yes |
1min, no flashover, no breakdown | |||||||||
Pillar insulator voltage test | 20kV/1min, no flashover, no breakdown | T | yes | yes | – | – | – | ||
Radio interference test for outdoor terminals | 61kV | 81kV | 140kV | A | yes | yes | – | – | yes |
1MHz radio interference, voltage ≤ 450μV | 1MHz radio interference, voltage ≤ 500μV | ||||||||
Accessory specimen test | Visual inspection of accessory systems containing cables with no signs of deterioration that could affect the normal operation of the system | T | yes | yes | yes | yes | yes | ||
DC voltage test | / | No breakdown between conductor and metal shield in connector, 20kV/1min. | T | – | – | – | yes | – | |
Performance test of crimped connectors for conductor connecting rods | The total area after crimping is not more than 1.2 times the resistance of an equal length of conductor of the same cross-section. | T | yes | yes | yes | yes | yes |
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China 132kv Porcelain Bushing Outdoor Termination manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 132kv Porcelain Bushing Outdoor Termination Products
Popular jiuweielectric Products
Factory Supply Vzg Non Slip Flame Retardant Heavy Wall Tube Adhrsive Film Tubing
Vcs High and Low Voltage Transformer Insulation Protection Shield
24kv 250A European Electric Cable Elbow Connector
Factory Wholesale Various Specs PVC Insulation Heat Shrink Tubing
Flame Retardant 35kv Red Color Heat Shrink Sleeves
Professional Manufacturer Heat Shrink Termination Kit High Voltage Heat Shrinkable Joint Kit
Popular Outdoor Termination Products
138kv Composite Bushing Outdoor Termination
66kv Porcelain Bushing Outdoor Termination
50/66kv Composite Bushing Outdoor Termination
132kv Composite Bushing Outdoor Termination
110kv Composite Bushing Outdoor Termination
220kv Porcelain Bushing Outdoor Termination
Popular Porcelain Bushing Products
24kv 630A-P2 EN 50180 medium voltage porcelain bushing
33kv Porcelain Bushing Insulator for Transformer
Transformer Bushings DIN 42530 Rated Voltage 1KV Rated Current 250-630A
1KV 2000A Bushing Insulator for transformer DIN42530
1.2kv 2500A spade type 8hole ANSI porcelain transformer bushing
52KV 3150A-P4 EN 50180 High voltage porcelain bushing
Tags: 132kv Porcelain Bushing Outdoor Termination, jiuweielectric, Outdoor Termination, Porcelain Bushing