15kv High Quality Oxide Zinc Surge Arrester for Substation
15kv High Quality Oxide Zinc Surge Arrester for Substation image
Get Latest Price Request a quote
Basic Info.
Product Description
Surge Arrester Series
General
1. Ratings:0.22~500KV (porcelain),0.22~220KV(composite)
2. Application:for protection of power transmission & distribution system from over-voltage.
3. Features:
1)Silicone polymer housing composite metal oxide surge arrester and porcelain housing metal Oxide surge arresters are available.
2)Easy installation and maintenance.
3)Good sealing capability to ensure reliable operation.
4)Protection and reliability of the surge arrester have been greatly enhanced.
Working Condition
1. Ambient air temperature:-40ºC ~+40ºC ;
2. Altitude:<=2000m;
3. Frequency: 48Hz~62Hz;
4. Power frequency voltage applied between terminals of surge arrester must not exceed continuous operating voltage of surge arrerter;
5. Earthquake intensity is less than 8 degree;
6. Max. Wind speed is 35m/s.
Main Techical Parameter
1. Metal oxide Polymer Housing (Gapless) type Surge Arrester for A.C System(5kA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-5W-6 | 6 | 5.1 | 18 | 320 | 150 | 65 | |
YH-5W-9 | 9 | 7.65 | 27 | 430 | 150 | 65 | |
YH-5W-12 | 12 | 10.2 | 36 | 430 | 150 | 65 | |
YH-5W-15 | 15 | 12.75 | 45 | 530 | 150 | 65 | |
YH-5W-18 | 18 |
15.3 |
54 | 530 | 150 | 65 | |
YH-5W-21 | 21 | 16.8 | 63 | 640 | 150 | 65 | |
YH-5W-24 | 24 | 19.2 | 72 | 640 | 150 | 65 | |
YH-5W-27 | 27 | 21.6 | 81 | 740 | 150 | 65 | |
YH-5W-30 | 30 | 24 | 90 | 890 | 150 | 65 | |
YH-5W-33 | 33 | 26.4 | 99 | 890 | 150 | 65 | |
YH-5W-36 | 36 | 28.8 | 108 | 1115 | 150 | 65 |
2. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (10KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-10W-6 | 6 | 5.1 | 18 | 1 | 320 | 250 | 100 |
YH-10W-9 | 9 | 7.65 | 27 | 1 | 430 | 250 | 100 |
YH-10W-12 | 12 | 10.2 | 36 | 1 | 430 | 250 | 100 |
YH-10W-15 | 15 | 12.75 | 45 | 1 | 530 | 250 | 100 |
YH-10W-18 | 18 | 15.3 | 54 | 1 | 530 | 250 | 100 |
YH-10W-21 | 21 | 16.8 | 63 | 1 | 640 | 250 | 100 |
YH-10W-24 | 24 | 19.2 | 72 | 1 | 740 | 250 | 100 |
YH-10W-27 | 27 | 21.6 | 81 | 1 | 740 | 250 | 100 |
YH-10W-30 | 30 | 24 | 90 | 1 | 890 | 250 | 100 |
YH-10W-33 | 33 | 26.4 | 99 | 1 | 890 | 250 | 100 |
YH-10W-36 | 36 | 28.8 | 108 | 1 | 1115 | 250 | 100 |
YH-10W-42 | 42 | 33.6 | 126 | 2 | 1260 | 400 | 100 |
YH-10W-48 | 48 | 39 | 139 | 2 | 1260 | 400 | 100 |
YH-10W-54 | 54 | 42 | 160 | 2 | 1260 | 400 | 100 |
YH-10W-60 | 60 | 48 | 178 | 2 | 1465 | 400 | 100 |
YH-10W-66 | 66 | 52.8 | 196 | 2 | 1465 | 400 | 100 |
YH-10W-72 | 72 | 57 | 214 | 2 | 2255 | 400 | 100 |
YH-10W-84 | 84 | 67.2 | 244 | 2 | 2255 | 400 | 100 |
YH-10W-90 | 90 | 72.5 | 249 | 2 | 2255 | 400 | 100 |
YH-10W-96 | 96 | 75 | 265 | 3 | 3555 | 800 | 100 |
YH-10W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
YH-10W-120 | 120 | 96 | 300 | 3 | 4153 | 800 | 100 |
YH-10W-150 | 150 | 120 | 416 | 3 | 5040 | 800 | 100 |
YH-10W-200 | 200 | 156 | 520 | 3 | 7110 | 800 | 100 |
3. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (20KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-20W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
YH-20W-120 | 120 | 96 | 300 | 3 | 4153 | 800 | 100 |
YH-20W-150 | 150 | 120 | 416 | 3 | 5040 | 800 | 100 |
YH-20W-200 | 200 | 156 | 520 | 3 | 7110 | 800 | 100 |
4. Metal Oxide Porcelain Housing (Gapless) type Surge Arrester for A.C. System (5KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y5W-6 | 6 | 5.1 | 18 | 280 | 150 | 65 | |
Y5W-9 | 9 | 7.65 | 27 | 320 | 150 | 65 | |
Y5W-12 | 12 | 10.2 | 36 | 320 | 150 | 65 | |
Y5W-15 | 15 | 12.75 | 45 | 450 | 150 | 65 | |
Y5W-18 | 18 |
15.3 |
54 | 450 | 150 | 65 | |
Y5W-21 | 21 | 16.8 | 63 | 450 | 150 | 65 | |
Y5W-24 | 24 | 19.2 | 72 | 510 | 150 | 65 | |
Y5W-27 | 27 | 21.6 | 81 | 510 | 150 | 65 | |
Y5W-30 | 30 | 24 | 90 | 890 | 150 | 65 | |
Y5W-33 | 33 | 26.4 | 99 | 890 | 150 | 65 | |
Y5W-36 | 36 | 28.8 | 108 | 890 | 150 | 65 |
5. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (10KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y10W-6 | 6 | 5.1 | 18 | 1 | 280 | 250 | 100 |
Y10W-9 | 9 | 7.65 | 27 | 1 | 320 | 250 | 100 |
Y10W-12 | 12 | 10.2 | 36 | 1 | 320 | 250 | 100 |
Y10W-15 | 15 | 12.75 | 45 | 1 | 450 | 250 | 100 |
Y10W-18 | 18 | 15.3 | 54 | 1 | 450 | 250 | 100 |
Y10W-21 | 21 | 16.8 | 63 | 1 | 450 | 250 | 100 |
Y10W-24 | 24 | 19.2 | 72 | 1 | 510 | 250 | 100 |
Y10W-27 | 27 | 21.6 | 81 | 1 | 510 | 250 | 100 |
Y10W-30 | 30 | 24 | 90 | 1 | 890 | 250 | 100 |
Y10W-33 | 33 | 26.4 | 99 | 1 | 890 | 250 | 100 |
Y10W-36 | 36 | 28.8 | 108 | 1 | 890 | 250 | 100 |
Y10W-42 | 42 | 33.6 | 126 | 2 | 1256 | 400 | 100 |
Y10W-48 | 48 | 39 | 139 | 2 | 1256 | 400 | 100 |
Y10W-54 | 54 | 42 | 160 | 2 | 1256 | 400 | 100 |
Y10W-60 | 60 | 48 | 178 | 2 | 1440 | 400 | 100 |
Y10W-66 | 66 | 52.8 | 196 | 2 | 1440 | 400 | 100 |
Y10W-72 | 72 | 57 | 214 | 2 | 1440 | 400 | 100 |
Y10W-84 | 84 | 67.2 | 244 | 2 | 2200 | 400 | 100 |
Y10W-90 | 90 | 72.5 | 249 | 2 | 2200 | 400 | 100 |
Y10W-96 | 96 | 75 | 265 | 3 | 3350 | 800 | 100 |
Y10W-108 | 108 | 84 | 281 | 3 | 3350 | 800 | 100 |
Y10W-120 | 120 | 96 | 300 | 3 | 3948 | 800 | 100 |
Y10W-150 | 150 | 120 | 416 | 3 | 4400 | 800 | 100 |
Y10W-200 | 200 | 156 | 520 | 3 | 6700 | 800 | 100 |
6. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (20KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y20W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
Y20W-120 | 120 | 96 | 300 | 3 | 4106 | 800 | 100 |
Y20W-150 | 150 | 120 | 416 | 3 | 4400 | 800 | 100 |
Y20W-200 | 200 | 156 | 520 | 3 | 6700 | 800 | 100 |
Y20W-444 | 444 | 324 | 1106 | 4 | 17052 | 2000 | 100 |
Note: For details, please refer to the catalogue.
Participate in the exhibition pictures
testing report
We are China 15kv High Quality Oxide Zinc Surge Arrester for Substation manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular High Quality Oxide Zinc Surge Arrester Products
6kv High Quality Oxide Zinc Surge Arrester for Substation
33kv High Quality Oxide Zinc Surge Arrester for Substation
18kv High Quality Oxide Zinc Surge Arrester for Substation
9kv High Quality Oxide Zinc Surge Arrester for Substation
21kv High Quality Oxide Zinc Surge Arrester for Substation
36kv High Quality Oxide Zinc Surge Arrester for Substation
Popular Oxide Zinc Surge Arrester for Substation Products
9kv High Quality Oxide Zinc Surge Arrester for Substation
36kv High Quality Oxide Zinc Surge Arrester for Substation
33kv High Quality Oxide Zinc Surge Arrester for Substation
24kv High Quality Oxide Zinc Surge Arrester for Substation
21kv High Quality Oxide Zinc Surge Arrester for Substation
30kv High Quality Oxide Zinc Surge Arrester for Substation
Popular people Products
Cgh Suspension Clamp (Aluminium Alloy)
12kv Polymer Line Horizontal Post Insulator for Distribution Line
Malleable Iron Die Casting Galvanized Cross Arm
12kv High Voltage Lightning Arrester for Distribution Line
30kv Outdoor Expulsion Drop-out Type Loadbreak Fuse Cutout
Heat/Cold Shrinkable Cable Accessories Finger Cot
Popular Surge Arrester Products
33kv Composite Zinc Metal-Oxide Arrester Lightning Arrester
Lightning Arrester Lightning Protector Arresters
Yh42W-33, Sharp Head 33kv 10ka Surge Arrester
60kv High Voltage Surge Arrester for Distribution Line
Tags: High Quality Oxide Zinc Surge Arrester, Oxide Zinc Surge Arrester for Substation, people, Surge Arrester