16-1250mm2 ACSR /AAC/AAAC Conductor 795mcm ACSR Conductor
16-1250mm2 ACSR /AAC/AAAC Conductor 795mcm ACSR Conductor image
Get Latest Price Request a quote
Quick Details
Product Details
Applications:
Conductor(AAC, AAAC and ACSR) have been widely used in power transmission lines with various voltage levels,because they have such good characteristics as simple structure,convenient installation and maintenance,low cost large transmission capacity.And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
Material Standard:
1) The hard aluminum conductor used for AAC and ACSR conforms to the standard GB/T 17048-1997(equivalent to IEC 60889:1987).
2) The zinc coated steel wire used for ACSR conforms to IEC 60888:1987.
3) Production can be arranged according to customers requirements for material standard,etc.
Construction of All Aluminum Conductor and Aluminum Conductor Steel Reinforced
Standards:
ASTM-B232 Standard specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
BS215-2 aluminum conductors steel-reinforced -For overhead power transmission
DIN48204 Steel reinforced aluminum stranded conductors
IEC209 Aluminum stranded conductor steel reinforced
Customized type available.
ACSR bare conductor meets/exceeds the following ASTM specifications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced
(ACSR)
B-341 Aluminum-Coated Steel Core Wire for Aluminum Conductors, Steel
Reinforced (ACSR/AZ)
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced
(ACSR/AZ)
B-500 Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum
Conductors, Steel Reinforced (ACSR)
Technical characteristics
Standard GB/T 1179-2008
Area |
/ Pieces/Diameter |
Diameter | Max. resistance At 20ºC |
Calculation Force |
Weight |
mm2 | mm | mm | Ω/km | KN | kg/km |
10 | 7/1.35 | 4.05 | 2.8633 | 1.95 | 27.4 |
16 | 7/1.71 | 5.12 | 1.7896 | 3.04 | 43.8 |
25 | 7/2.13 | 6.40 | 1.1453 | 4.50 | 68.4 |
40 | 7/2.70 | 8.09 | 0.7158 | 6.80 | 109.4 |
63 | 7/3.39 | 10.2 | 0.4545 | 10.39 | 172.3 |
100 | 19/2.59 | 12.9 | 0.2877 | 17.00 | 274.8 |
125 | 19/2.89 | 14.5 | 0.2302 | 21.25 | 343.6 |
160 | 19/3.27 | 16.4 | 0.1798 | 26.40 | 439.8 |
200 | 19/3.66 | 18.3 | 0.1439 | 32.00 | 549.7 |
250 | 19/4.09 | 20.5 | 0.1151 | 40.00 | 687.1 |
315 | 37/3.29 | 23.0 | 0.0916 | 51.97 | 867.9 |
400 | 37/3.71 | 26.0 | 0.0721 | 64.00 | 1102.0 |
450 | 37/3.94 | 27.5 | 0.0641 | 72.00 | 1239.8 |
500 | 37/4.15 | 29.0 | 0.0577 | 80.00 | 1377.6 |
560 | 37/4.39 | 30.7 | 0.0515 | 89.60 | 1542.9 |
630 | 61/3.63 | 32.6 | 0.0458 | 100.80 | 1738.3 |
710 | 61/3.85 | 34.6 | 0.0407 | 113.60 | 1959.1 |
800 | 61/4.09 | 36.8 | 0.0361 | 128.00 | 2207.4 |
900 | 61/4.33 | 39.0 | 0.0321 | 144.00 | 2483.3 |
1000 | 61/4.57 | 41.1 | 0.0289 | 160.00 | 2759.2 |
1120 | 91/3.96 | 43.5 | 0.0258 | 179.20 | 3093.5 |
1250 | 91/4.18 | 46.0 | 0.0231 | 200.00 | 3452.6 |
1400 | 91/4.43 | 48.7 | 0.0207 | 224.00 | 3866.9 |
1500 | 91/4.58 | 50.4 | 0.0193 | 240.00 | 4143.1 |
AAC Standard: ASTM B231
Code Name |
Total Area | / Stranding and wire diameter mm |
Linear Mass kg/km |
Overall Diameter mm |
Nominal Breaking Load daN |
Max. D.C. Resistance at 20ºC ≤Ω/k |
|
AWG or MCM | mm2 | ||||||
Peachbell | 6 | 13.29 | 7/1.554 | 37 | 4.67 | 249 | 2.1692 |
Rose | 4 | 21.16 | 7/1.961 | 58 | 5.89 | 396 | 1.3624 |
Iris | 2 | 33.61 | 7/2.474 | 93 | 7.42 | 597 | 0.8577 |
Pansy | 1 | 42.39 | 7/2.776 | 117 | 8.33 | 732 | 0.6801 |
Poppy | 1/0 | 53.48 | 7/3.119 | 147 | 9.36 | 873 | 0.5390 |
Aster | 2/0 | 67.42 | 7/3.503 | 186 | 10.51 | 1100 | 0.4276 |
Phlox | 3/0 | 85.03 | 7/3.932 | 234 | 11.80 | 1347 | 0.3390 |
Oxlip | 4/0 | 107.23 | 7/4.417 | 296 | 13.26 | 1698 | 0.2688 |
Valerian | 250 | 126.71 | 19/2.931 | 349 | 14.57 | 2062 | 0.2275 |
Sneezewort | 250 | 126.71 | 7/4.80 | 349 | 14.4 | 2007 | 0.2275 |
Laurel | 266.8 | 135.16 | 19/3.01 | 373 | 15.05 | 2200 | 0.2133 |
Daisy | 266.8 | 135.16 | 7/4.96 | 373 | 14.9 | 2141 | 0.2133 |
Peony | 300 | 152.0 | 19/3.193 | 419 | 15.97 | 2403 | 0.1896 |
Tulip | 336.4 | 170.45 | 19/3.381 | 470 | 16.91 | 2695 | 0.1691 |
Daffodil | 350 | 177.35 | 19/3.447 | 489 | 17.24 | 2804 | 0.1625 |
Canna | 397.5 | 201.42 | 19/3.673 | 555 | 18.36 | 3184 | 0.1431 |
Goldentuft | 450 | 228 | 19/3.909 | 629 | 19.55 | 3499 | 0.1264 |
Syringa | 477 | 241.68 | 37/2.882 | 666 | 20.19 | 3849 | 0.1193 |
Cosmos | 477 | 241.68 | 19/4.023 | 666 | 20.12 | 3708 | 0.1193 |
Hyacinth | 500 | 253.35 | 37/2.951 | 698 | 20.65 | 4035 | 0.1138 |
Zinnia | 500 | 253.35 | 19/4.12 | 698 | 20.6 | 3888 | 0.1138 |
Dahlia | 556.5 | 282 | 19/4.346 | 777 | 21.73 | 4327 | 0.1022 |
Mistletoe | 556.5 | 282 | 37/3.114 | 777 | 21.79 | 4362 | 0.1022 |
Meadowsweet | 600 | 304 | 37/3.233 | 838 | 22.63 | 4703 | 0.0948 |
Orchid | 636 | 322.25 | 37/3.33 | 888 | 23.31 | 4985 | 0.0894 |
Heuchera | 650 | 329.35 | 37/3.366 | 908 | 23.56 | 5095 | 0.0875 |
Flag | 700 | 354.71 | 61/2.72 | 978 | 24.48 | 5146 | 0.0813 |
AAC Standard: ASTM B231
Code Name |
Total Area | / Stranding and wire diameter mm |
Overall Diameter mm |
Linear Mass kg/mass |
Nominal Breaking Load daN |
Max. D.C. Resistance at 20ºC ≤Ω/km |
|
AWG or MCM | mm2 | ||||||
Verbena | 700 | 354.71 | 37/3.493 | 24.45 | 978 | 5487 | 0.0813 |
Nasturtium | 715.5 | 362.58 | 61/2.75 | 24.76 | 1000 | 5874 | 0.0795 |
Violet | 715.5 | 362.58 | 37/3.533 | 24.74 | 1000 | 5609 | 0.0795 |
Cattail | 750 | 380 | 61/2.817 | 25.35 | 1048 | 5985 | 0.0759 |
Petunia | 750 | 380 | 37/3.617 | 25.32 | 1048 | 5875 | 0.0759 |
Lilac | 795 | 402.84 | 61/2.90 | 26.11 | 1111 | 6345 | 0.0715 |
Arbutus | 795 | 402.84 | 37/3.724 | 26.06 | 1111 | 6232 | 0.0715 |
Snapdragon | 900 | 456.06 | 61/3.086 | 27.78 | 1257 | 6978 | 0.0632 |
Cockscomb | 900 | 456.06 | 37/3.962 | 27.73 | 1257 | 6848 | 0.0632 |
Goldenrod | 954 | 483.42 | 61/3.177 | 28.6 | 1333 | 7896 | 0.0596 |
Magnolia | 954 | 483.42 | 37/4.079 | 28.55 | 1333 | 7258 | 0.0596 |
Camellia | 1000 | 506.71 | 61/3.251 | 29.36 | 1397 | 7753 | 0.0569 |
Hawkweed | 1000 | 506.71 | 37/4.176 | 29.23 | 1397 | 7608 | 0.0569 |
Larkspur | 1033.5 | 523.68 | 61/3.307 | 29.76 | 1444 | 8012 | 0.0550 |
Bluebell | 1033.5 | 523.68 | 37/4.244 | 29.72 | 1444 | 7863 | 0.0550 |
Marigold | 1113 | 563.93 | 61/3.432 | 30.89 | 1555 | 8628 | 0.0511 |
Hawthorn | 1192.5 | 604.26 | 61/3.551 | 31.05 | 1666 | 9245 | 0.0477 |
Narcissus | 1272 | 644.51 | 61/3.668 | 33.02 | 1777 | 9861 | 0.0477 |
Columbine | 1351.5 | 684.84 | 61/3.78 | 34.01 | 1888 | 10478 | 0.0421 |
Carnation | 1431 | 725.10 | 61/3.89 | 35.03 | 1999 | 10768 | 0.0398 |
Gladiolus | 1510.5 | 765.35 | 61/4.00 | 35.09 | 2110 | 11365 | 0.0376 |
Coreopsis | 1590 | 805.68 | 61/4.099 | 36.51 | 2221 | 11964 | 0.0358 |
Jessamine | 1750 | 886.71 | 61/4.302 | 38.72 | 2445 | 13168 | 0.0325 |
Cowslip | 2000 | 1013.42 | 91/3.76 | 41.40 | 2791 | 15300 | 0.0285 |
Lupine | 2500 | 1266.67 | 91/4.21 | 46.30 | 3524 | 18700 | 0.0230 |
Trillium | 3000 | 1520.13 | 127/3.90 | 50.75 | 4232 | 22500 | 0.0192 |
Bluebonnet | 3500 | 1773.50 | 127/4.21 | 54.80 | 4985 | 26200 | 0.0166 |
AAC Standard: BS215 Part 1
Nominal Alum Area mm2 |
Stranding and wire diameter mm |
Sectional Area mm2 |
Approx. Weight Kg/km |
Overall Diameter mm |
Max..D.C. Resistance At 20ºC ≤Ω/km |
Calculated breaking load da N |
Final Modulus Of Elasticity hbar |
Coefficient of Linear Expansion /ºC |
22 | 7/2.06 | 23.33 | 64 | 6.18 | 1.227 | 399 | 5900 | 23×10- |
25 | 3/3.35 | 26.40 | 73 | 7.2 | 1.081 | 411 | 5900 | 23×10- |
25 | 7/2.21 | 26.8 | 73 | 6.6 | 1.066 | 459 | 5900 | 23×10- |
30 | 3/3.66 | 31.6 | 86 | 7.9 | 0.9082 | 486 | 5900 | 23×10- |
35 | 7/2.59 | 37.0 | 101 | 7.8 | 0.7762 | 603 | 5900 | 23×10- |
40 | 7/2.79 | 42.8 | 117 | 8.4 | 0.6689 | 687 | 5900 | 23×10- |
50 | 7/3.10 | 52.83 | 145 | 9.30 | 0.5419 | 828 | 5900 | 23×10- |
60 | 7/3.40 | 63.55 | 174 | 10.20 | 0.4505 | 990 | 5900 | 23×10- |
70 | 7/3.66 | 73.7 | 202 | 11.0 | 0.3881 | 1134 | 5900 | 23×10- |
75 | 7/3.78 | 78.5 | 215 | 11.4 | 0.3644 | 1194 | 5900 | 23×10- |
80 | 7/3.91 | 84.1 | 230 | 11.7 | 0.3406 | 1278 | 5900 | 23×10- |
90 | 7/4.17 | 95.6 | 262 | 12.5 | 0.2994 | 1453 | 5900 | 23×10- |
100 | 7/4.39 | 106.0 | 290 | 13.17 | 0.2702 | 1600 | 5900 | 23×10- |
100 | 19/2.67 | 106.0 | 293 | 13.4 | 0.2704 | 1742 | 5600 | 23×10- |
125 | 7/4.90 | 132.0 | 361 | 14.7 | 0.2169 | 1944 | 5900 | 23×10- |
150 | 7/5.36 | 157.9 | 432 | 16.1 | 0.1818 | 2385 | 5900 | 23×10- |
150 | 19/3.25 | 157.9 | 434 | 16.25 | 0.1825 | 2570 | 5600 | 23×10- |
175 | 19/3.53 | 186 | 512 | 17.7 | 0.1547 | 2863 | 5600 | 23×10- |
200 | 19/3.78 | 213.2 | 587 | 18.9 | 0.1349 | 3240 | 5600 | 23×10- |
225 | 19/3.99 | 236.9 | 652 | 20.0 | 0.1211 | 3601 | 5600 | 23×10- |
250 | 19/4.22 | 265.7 | 731 | 21.10 | 0.1083 | 4040 | 5600 | 23×10- |
300 | 19/4.65 | 322.7 | 888 | 23.25 | 0.08916 | 4875 | 5600 | 23×10- |
350 | 37/5.00 | 373.2 | 1027 | 25.0 | 0.07711 | 5637 | 5600 | 23×10- |
350 | 19/3.58 | 373.3 | 1029 | 25.1 | 0.07741 | 5745 | 5600 | 23×10- |
400 | 37/5.36 | 428.5 | 1179 | 26.8 | 0.06710 | 6473 | 5600 | 23×10- |
400 | 37/3.78 | 415.2 | 1145 | 26.46 | 0.06944 | 6310 | 5600 | 23×10- |
450 | 37/4.09 | 486.9 | 1342 | 28.6 | 0.05931 | 7401 | 5600 | 23×10- |
500 | 37/4.27 | 529.5 | 1460 | 29.9 | 0.05441 | 7998 | 5600 | 23×10- |
600 | 37/4.65 | 628.6 | 1733 | 32.6 | 0.04588 | 9495 | 5600 | 23×10- |
750 | 37/5.23 | 794.6 | 2191 | 36.6 | 0.03627 | 12010 | 5600 | 23×10- |
We can make according to your specifications, customized LOGO, with your company name on the cable.
Factory Address:
Yichuan Electricity Industry zone, Luoyang City, Henan Province, China
Test Machine
extruding machine, cable-former, drawbench and so on.
Package
Wooden drum or 100m/roll
Customer
American, Australia, India, South Africa, South America…
Our Principles
1. Quality first, customer first, safety first
2. Better service, faster delivery
3. Equal and mutual benefit
4. Honest and professional
Why choose us?
1. Swift and professional response
2. Patient and trusty
3. Severe quality control system
4. On-time delivery
Contact
Cathy Shi
Department sale manager
International Trade Department
Luoyang Dayuan Cable Co., Ltd
=================================
Tel: +86-379-69991587
Mobile: + 86-15136243085
=================================
We are China 16-1250mm2 ACSR /AAC/AAAC Conductor 795mcm ACSR Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAC Products
DIN 48201 95/15 All Aluminium Bare Conductor
IEC 61089 Standard Overhead Conductors AAC Aluminium Cable 25mm
Bare All Aluminiumn Conductor 50mm2 AAC Stranded Wire
High Quality All Aluminum Conductor/Cable AAC Manufacturer/Supplier
Duplex Triplex ABC Cable Service Drop Cable Aluminum Conductor Wire
AAC Bare Conductor for Project
Popular AAC Conductor Products
Overhead Transmission Line All Aluminum Stranded Conductor AAC Cable
Triplex Cable XLPE PE Insulated Aluminum Air Lighting Line with AAC AAAC ACSR Conductor
All Aluminium Conductor Overhead Bare Conductor AAC Transmission Lines
AAC Aluminum Stranded Conductor
Overhead Conductors AAC/ AAAC/ ACSR/ Acar/ Accc Bare Conductors
AAC Conductor, ACSR Conductor, AAAC Conductor
Popular AAC Power Cable Products
All Aluminum Conductor AAC to ASTM B231
Bare Aluminum Conductor AAC or Asc Conductor Wasp
High Quality All Aluminum Conductors AAC for Distribution Lines
Electric Power Distribution Peso De Cable ACSR 1 0 /ACSR Cable IEC 61089 Standard
Bare All Aluminum Conductor AAC Cable
High Quality AAC Conductor From Experienced Manufacturer
Popular dycable Products
AAAC All Aluminum Alloy Conductor Bare Cable ASTM B399 BS En 50182-2001
TUV Certificate High Quality Single Core PV1-F PV Solar Cables
Stranded Conductor 16mm2 All Aluminum Bare Conductor AAC
AAAC Conductor 25mm 35mm 50mm 70mm 95mm 120mm
ASTM Standard AWG Size Bare Aluminium Conductor AAC
Bare ACSR Conductor BS215 Standard for Africa Market
Tags: AAC, AAC Conductor, AAC Power Cable, dycable