Low Voltage Cable
1. Application
The cable is used in electric transmission and distribution system operating at AC rated voltage up to and including 1.8/3 KV
2. Operating Characteristic
1) The rated voltage U0/U of cable is 0.6/1KV.
2) The long time allowable working temperature of conductor is 70 °C FOR cable with PVC insulation, 90 °C for cable with XLPE insulation.
3) The cable laying temperature is not less than 0°C, and the allowable bending radius of a cable is not less 20 times than cable overall diameter for single core unarmored cable, 15 times of that for single core armored, 12 times of that for 3 cores armored cable.
2. Construction
3. Cores and Nominal Cross Section Area:
| Rated voltage 0.6/1kV Single core Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 0.7 | 5.6 | 45 | 35 | ||||||
| 2.5 | 0.7 | 0.7 | 6.0 | 56 | 41 | ||||||
| 4 | 0.7 | 0.7 | 6.5 | 74 | 49 | ||||||
| 6 | 0.7 | 0.7 | 7.0 | 95 | 59 | ||||||
| 10 | 0.7 | 0.7 | 8.2 | 139 | 79 | ||||||
| 16 | 0.7 | 0.7 | 9.1 | 197 | 102 | ||||||
| 25 | 0.9 | 0.9 | 10.6 | 293 | 143 | 0.9 | 0.2 | 1.8 | 14.0 | 451 | 301 |
| 35 | 0.9 | 0.9 | 11.6 | 386 | 178 | 0.9 | 0.2 | 1.8 | 15.0 | 558 | 349 |
| 50 | 1.0 | 1.0 | 13.0 | 507 | 225 | 0.9 | 0.2 | 1.8 | 16.4 | 698 | 416 |
| 70 | 1.1 | 1.1 | 14.9 | 708 | 300 | 0.9 | 0.2 | 1.8 | 18.3 | 926 | 519 |
| 95 | 1.1 | 1.1 | 16.8 | 959 | 394 | 0.9 | 0.2 | 1.8 | 20.0 | 1194 | 628 |
| 120 | 1.2 | 1.2 | 18.5 | 1193 | 479 | 0.9 | 0.2 | 1.8 | 21.7 | 1450 | 737 |
| 150 | 1.4 | 1.4 | 20.6 | 1470 | 590 | 0.9 | 0.2 | 1.8 | 23.6 | 1745 | 865 |
| 185 | 1.6 | 1.6 | 22.8 | 1831 | 730 | 0.9 | 0.2 | 1.8 | 25.6 | 2122 | 1021 |
| 240 | 1.7 | 1.7 | 25.7 | 2380 | 933 | 0.9 | 0.2 | 1.9 | 28.5 | 2706 | 1259 |
| 300 | 1.8 | 1.8 | 28.3 | 2960 | 1144 | 0.9 | 0.2 | 1.9 | 30.9 | 3304 | 1488 |
| 400 | 2.0 | 2.0 | 31.3 | 3755 | 1433 | 1.2 | 0.5 | 2.1 | 35.9 | 4494 | 2173 |
| Rated voltage 0.6/1kV Two cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.2 | 114 | 96 | 0.9 | 0.2 | 1.8 | 12.8 | 232 | 214 |
| 2.5 | 0.7 | 1.8 | 11.0 | 141 | 111 | 0.9 | 0.2 | 1.8 | 13.6 | 269 | 238 |
| 4 | 0.7 | 1.8 | 12.0 | 181 | 132 | 0.9 | 0.2 | 1.8 | 14.6 | 320 | 271 |
| 6 | 0.7 | 1.8 | 13.0 | 228 | 156 | 0.9 | 0.2 | 1.8 | 15.6 | 379 | 306 |
| 10 | 0.7 | 1.8 | 15.4 | 331 | 211 | 0.9 | 0.2 | 1.8 | 18.0 | 509 | 389 |
| 16 | 0.7 | 1.8 | 17.2 | 458 | 268 | 0.9 | 0.2 | 1.8 | 19.8 | 657 | 467 |
| 25 | 0.9 | 1.8 | 20.2 | 672 | 371 | 0.9 | 0.2 | 1.8 | 22.8 | 905 | 604 |
| 35 | 0.9 | 1.8 | 22.2 | 873 | 455 | 0.9 | 0.2 | 1.8 | 24.8 | 1130 | 712 |
| 50 | 1.0 | 1.8 | 25.0 | 1140 | 574 | 0.9 | 0.2 | 1.8 | 27.6 | 1428 | 863 |
| 70 | 1.1 | 1.9 | 29.0 | 1592 | 775 | 1.2 | 0.2 | 2.0 | 33.6 | 2262 | 1445 |
| 95 | 1.1 | 2.0 | 32.6 | 2134 | 1000 | 1.2 | 0.2 | 2.2 | 37.4 | 2899 | 1765 |
| 120 | 1.2 | 2.1 | 36.2 | 2660 | 1229 | 1.2 | 0.5 | 2.3 | 41.0 | 3504 | 2074 |
| 150 | 1.4 | 2.3 | 40.4 | 3287 | 1522 | 1.2 | 0.5 | 2.4 | 45.0 | 4202 | 2437 |
| 185 | 1.6 | 2.4 | 44.6 | 4073 | 1864 | 1.2 | 0.5 | 2.5 | 49.2 | 5079 | 2870 |
| 240 | 1.7 | 2.6 | 50.4 | 5287 | 2384 | 1.4 | 0.5 | 2.8 | 55.6 | 6457 | 3554 |
| 300 | 1.8 | 2.8 | 55.6 | 6567 | 2925 | 1.4 | 0.5 | 2.9 | 60.6 | 7822 | 4180 |
| 400 | 2.0 | 2.9 | 61.4 | 8279 | 3622 | 1.4 | 0.5 | 3.1 | 66.6 | 9692 | 5034 |
| Rated voltage 0.6/1kV Three cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.7 | 135 | 107 | 0.9 | 0.2 | 1.8 | 13.3 | 259 | 231 |
| 2.5 | 0.7 | 1.8 | 11.5 | 171 | 125 | 0.9 | 0.2 | 1.8 | 14.1 | 304 | 259 |
| 4 | 0.7 | 1.8 | 12.6 | 225 | 152 | 0.9 | 0.2 | 1.8 | 15.2 | 370 | 297 |
| 6 | 0.7 | 1.8 | 13.7 | 291 | 182 | 0.9 | 0.2 | 1.8 | 16.3 | 449 | 341 |
| 10 | 0.7 | 1.8 | 16.3 | 429 | 250 | 0.9 | 0.2 | 1.8 | 18.9 | 618 | 438 |
| 16 | 0.7 | 1.8 | 18.2 | 609 | 324 | 0.9 | 0.2 | 1.8 | 20.8 | 820 | 534 |
| 25 | 0.9 | 1.8 | 21.4 | 907 | 455 | 0.9 | 0.2 | 1.8 | 24.0 | 1154 | 703 |
| 35 | 0.9 | 1.8 | 23.6 | 1194 | 567 | 0.9 | 0.2 | 1.8 | 26.2 | 1466 | 840 |
| 50 | 1.0 | 1.8 | 26.6 | 1570 | 722 | 0.9 | 0.2 | 1.9 | 29.4 | 1891 | 1042 |
| 70 | 1.1 | 1.9 | 30.9 | 2208 | 983 | 1.2 | 0.2 | 2.1 | 35.7 | 2936 | 1711 |
| 95 | 1.1 | 2.1 | 35.0 | 2995 | 1294 | 1.2 | 0.5 | 2.2 | 39.6 | 3794 | 2093 |
| 120 | 1.2 | 2.2 | 38.8 | 3741 | 1595 | 1.2 | 0.5 | 2.4 | 43.6 | 4642 | 2496 |
| 150 | 1.4 | 2.3 | 43.1 | 4601 | 1953 | 1.2 | 0.5 | 2.5 | 47.9 | 5598 | 2950 |
| 185 | 1.6 | 2.5 | 47.8 | 5738 | 2425 | 1.4 | 0.5 | 2.7 | 53.0 | 6851 | 3538 |
| 240 | 1.7 | 2.7 | 54.0 | 7462 | 3107 | 1.4 | 0.5 | 2.9 | 59.2 | 8711 | 4356 |
| 300 | 1.8 | 2.9 | 59.6 | 9283 | 3820 | 1.4 | 0.5 | 3.1 | 64.8 | 10655 | 5192 |
| 400 | 2.0 | 3.1 | 66.0 | 11771 | 4786 | 1.4 | 0.5 | 3.3 | 71.2 | 13284 | 6299 |
| Rated voltage 0.6/1kV Four cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 11.4 | 160 | 123 | 0.9 | 0.2 | 1.8 | 14.0 | 292 | 255 |
| 2.5 | 0.7 | 1.8 | 12.4 | 207 | 147 | 0.9 | 0.2 | 1.8 | 15.0 | 351 | 290 |
| 4 | 0.7 | 1.8 | 13.6 | 277 | 179 | 0.9 | 0.2 | 1.8 | 16.2 | 434 | 337 |
| 6 | 0.7 | 1.8 | 14.8 | 362 | 217 | 0.9 | 0.2 | 1.8 | 17.4 | 533 | 389 |
| 10 | 0.7 | 1.8 | 17.7 | 542 | 302 | 0.9 | 0.2 | 1.8 | 20.3 | 746 | 507 |
| 16 | 0.7 | 1.8 | 19.8 | 777 | 396 | 0.9 | 0.2 | 1.8 | 22.4 | 1005 | 625 |
| 25 | 0.9 | 1.8 | 23.5 | 1169 | 566 | 0.9 | 0.2 | 1.8 | 26.1 | 1440 | 838 |
| 35 | 0.9 | 1.8 | 25.9 | 1546 | 710 | 0.9 | 0.2 | 1.9 | 28.7 | 1858 | 1022 |
| 50 | 1.0 | 1.9 | 29.5 | 2054 | 923 | 1.2 | 0.2 | 2.1 | 34.3 | 2751 | 1620 |
| 70 | 1.1 | 2.1 | 34.4 | 2909 | 1275 | 1.2 | 0.2 | 2.2 | 39.0 | 3695 | 2061 |
| 95 | 1.1 | 2.2 | 38.8 | 3930 | 1661 | 1.2 | 0.5 | 2.4 | 43.6 | 4831 | 2563 |
| 120 | 1.2 | 2.3 | 43.1 | 4913 | 2051 | 1.2 | 0.5 | 2.5 | 47.9 | 5909 | 3048 |
| 150 | 1.4 | 2.5 | 48.0 | 6067 | 2537 | 1.4 | 0.5 | 2.7 | 53.2 | 7184 | 3654 |
| 185 | 1.6 | 2.7 | 53.3 | 7566 | 3148 | 1.4 | 0.5 | 2.8 | 58.3 | 8772 | 4355 |
| 240 | 1.7 | 2.9 | 60.2 | 9839 | 4033 | 1.4 | 0.5 | 3.1 | 65.4 | 11225 | 5419 |
| 300 | 1.8 | 3.1 | 66.4 | 12242 | 4957 | 1.4 | 0.5 | 3.3 | 71.6 | 13764 | 6479 |
| 400 | 2.0 | 3.3 | 73.5 | 15526 | 6212 | 1.4 | 0.5 | 3.5 | 78.7 | 17205 | 7891 |
| Rated voltage 0.6/1kV Five cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 12.2 | 186 | 140 | 0.9 | 0.2 | 1.8 | 14.8 | 328 | 281 |
| 2.5 | 0.7 | 1.8 | 13.3 | 244 | 168 | 0.9 | 0.2 | 1.8 | 15.9 | 398 | 322 |
| 4 | 0.7 | 1.8 | 14.6 | 329 | 207 | 0.9 | 0.2 | 1.8 | 17.2 | 498 | 376 |
| 6 | 0.7 | 1.8 | 16.0 | 434 | 254 | 0.9 | 0.2 | 1.8 | 18.6 | 619 | 439 |
| 10 | 0.7 | 1.8 | 19.2 | 655 | 356 | 0.9 | 0.2 | 1.8 | 21.8 | 877 | 578 |
| 16 | 0.7 | 1.8 | 21.7 | 948 | 472 | 0.9 | 0.2 | 1.8 | 24.3 | 1199 | 723 |
| 25 | 0.9 | 1.8 | 25.7 | 1432 | 679 | 0.9 | 0.2 | 1.9 | 28.5 | 1742 | 989 |
| 35 | 0.9 | 1.9 | 28.6 | 1914 | 869 | 0.9 | 0.2 | 2.0 | 31.4 | 2257 | 1213 |
| 50 | 1.0 | 2.0 | 32.6 | 2546 | 1131 | 1.2 | 0.2 | 2.2 | 37.4 | 3310 | 1896 |
| 70 | 1.1 | 2.2 | 38.1 | 3607 | 1565 | 1.2 | 0.5 | 2.3 | 42.7 | 4473 | 2431 |
| 95 | 1.1 | 2.3 | 42.9 | 4876 | 2040 | 1.2 | 0.5 | 2.5 | 47.7 | 5868 | 3032 |
| 120 | 1.2 | 2.5 | 47.9 | 6120 | 2543 | 1.4 | 0.5 | 2.7 | 53.1 | 7235 | 3658 |
| 150 | 1.4 | 2.7 | 53.4 | 7556 | 3143 | 1.4 | 0.5 | 2.8 | 58.4 | 8765 | 4352 |
| 185 | 1.6 | 2.9 | 59.2 | 9419 | 3897 | 1.4 | 0.5 | 3.0 | 64.2 | 10752 | 5230 |
| 240 | 1.7 | 3.1 | 66.9 | 12249 | 4992 | 1.4 | 0.5 | 3.3 | 72.1 | 13783 | 6525 |
| 300 | 1.8 | 3.4 | 74.0 | 15273 | 6168 | 1.4 | 0.5 | 3.5 | 79.0 | 16925 | 7820 |
| 400 | 2.0 | 3.6 | 82.0 | 19369 | 7726 | 1.4 | 0.5 | 3.8 | 88.4 | 22080 | 10437 |
| Rated voltage 0.6/1kV 3+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 12.4 | 198 | 143 | 0.9 | 0.2 | 1.8 | 15.0 | 342 | 287 |
| 4/2.5 | 0.7/0.7 | 1.8 | 13.6 | 262 | 174 | 0.9 | 0.2 | 1.8 | 16.2 | 420 | 332 |
| 6/4 | 0.7/0.7 | 1.8 | 14.8 | 343 | 211 | 0.9 | 0.2 | 1.8 | 17.4 | 515 | 382 |
| 10/6 | 0.7/0.7 | 1.8 | 17.7 | 506 | 290 | 0.9 | 0.2 | 1.8 | 20.3 | 710 | 495 |
| 16/10 | 0.7/0.7 | 1.8 | 19.8 | 724 | 378 | 0.9 | 0.2 | 1.8 | 22.4 | 953 | 607 |
| 25/16 | 0.9/0.7 | 1.8 | 23.5 | 1083 | 536 | 0.9 | 0.2 | 1.8 | 26.1 | 1354 | 807 |
| 35/16 | 0.9/0.7 | 1.8 | 25.3 | 1371 | 649 | 0.9 | 0.2 | 1.9 | 28.1 | 1676 | 954 |
| 50/25 | 1.0/0.9 | 1.9 | 28.8 | 1852 | 853 | 0.9 | 0.2 | 2.0 | 31.6 | 2198 | 1199 |
| 70/35 | 1.1/0.9 | 2.0 | 33.5 | 2593 | 1158 | 1.2 | 0.2 | 2.2 | 38.3 | 3378 | 1944 |
| 95/50 | 1.1/1.0 | 2.2 | 37.9 | 3506 | 1522 | 1.2 | 0.5 | 2.3 | 42.5 | 4367 | 2383 |
| 120/70 | 1.2/1.1 | 2.3 | 42.1 | 4452 | 1897 | 1.2 | 0.5 | 2.5 | 46.9 | 5425 | 2871 |
| 150/70 | 1.4/1.1 | 2.5 | 46.9 | 5361 | 2305 | 1.4 | 0.5 | 2.6 | 51.9 | 6430 | 3373 |
| 185/95 | 1.6/1.1 | 2.6 | 51.8 | 6732 | 2851 | 1.4 | 0.5 | 2.8 | 57.0 | 7933 | 4053 |
| 240/120 | 1.7/1.2 | 2.9 | 58.8 | 8740 | 3670 | 1.4 | 0.5 | 3.0 | 63.8 | 10065 | 4995 |
| 300/150 | 1.8/1.4 | 3.1 | 64.8 | 10850 | 4504 | 1.4 | 0.5 | 3.2 | 69.8 | 12304 | 5958 |
| 400/185 | 2.0/1.6 | 3.3 | 71.8 | 13718 | 5628 | 1.4 | 0.5 | 3.5 | 77.0 | 15359 | 7269 |
| Rated voltage 0.6/1kV 3+2 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 225 | 161 | 0.9 | 0.2 | 1.8 | 15.9 | 379 | 315 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 300 | 197 | 0.9 | 0.2 | 1.8 | 17.2 | 469 | 366 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 398 | 241 | 0.9 | 0.2 | 1.8 | 18.6 | 583 | 426 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 584 | 332 | 0.9 | 0.2 | 1.8 | 21.8 | 806 | 554 |
| 16/10 | 0.7/0.7 | 1.8 | 21.8 | 844 | 439 | 0.9 | 0.2 | 1.8 | 24.4 | 1096 | 691 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1262 | 620 | 0.9 | 0.2 | 1.9 | 28.5 | 1572 | 930 |
| 35/16 | 0.9/0.7 | 1.8 | 27.5 | 1557 | 740 | 0.9 | 0.2 | 1.9 | 30.3 | 1889 | 1072 |
| 50/25 | 1.0/0.9 | 2.0 | 31.6 | 2148 | 998 | 1.2 | 0.2 | 2.1 | 36.2 | 2873 | 1724 |
| 70/35 | 1.1/0.9 | 2.1 | 36.7 | 2993 | 1350 | 1.2 | 0.2 | 2.3 | 41.5 | 3849 | 2206 |
| 95/50 | 1.1/1.0 | 2.3 | 41.5 | 4037 | 1770 | 1.2 | 0.5 | 2.4 | 46.1 | 4976 | 2709 |
| 120/70 | 1.2/1.1 | 2.4 | 46.1 | 5186 | 2223 | 1.4 | 0.5 | 2.6 | 51.3 | 6262 | 3299 |
| 150/70 | 1.4/1.1 | 2.6 | 51.5 | 6133 | 2669 | 1.4 | 0.5 | 2.8 | 56.7 | 7328 | 3863 |
| 185/95 | 1.6/1.1 | 2.8 | 57.1 | 7789 | 3341 | 1.4 | 0.5 | 3.0 | 62.3 | 9106 | 4658 |
| 240/120 | 1.7/1.2 | 3.0 | 64.5 | 10040 | 4255 | 1.4 | 0.5 | 3.2 | 69.7 | 11521 | 5736 |
| 300/150 | 1.8/1.4 | 3.3 | 71.3 | 12479 | 5251 | 1.4 | 0.5 | 3.4 | 76.3 | 14074 | 6845 |
| 400/185 | 2.0/1.6 | 3.5 | 79.0 | 15742 | 6547 | 1.4 | 0.5 | 3.7 | 85.4 | 18358 | 9163 |
| Rated voltage 0.6/1kV 4+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 235 | 165 | 0.9 | 0.2 | 1.8 | 15.9 | 389 | 319 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 315 | 202 | 0.9 | 0.2 | 1.8 | 17.2 | 483 | 371 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 416 | 247 | 0.9 | 0.2 | 1.8 | 18.6 | 601 | 432 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 620 | 344 | 0.9 | 0.2 | 1.8 | 21.8 | 842 | 566 |
| 16/10 | 0.7/0.7 | 1.8 | 21.7 | 896 | 455 | 0.9 | 0.2 | 1.8 | 24.3 | 1146 | 706 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1347 | 650 | 0.9 | 0.2 | 1.9 | 28.5 | 1657 | 960 |
| 35/16 | 0.9/0.7 | 1.9 | 28.2 | 1742 | 811 | 0.9 | 0.2 | 1.9 | 30.8 | 2067 | 1136 |
| 50/25 | 1.0/0.9 | 2.0 | 32.1 | 2347 | 1065 | 1.2 | 0.2 | 2.1 | 36.7 | 3083 | 1802 |
| 70/35 | 1.1/0.9 | 2.2 | 37.5 | 3308 | 1466 | 1.2 | 0.5 | 2.3 | 42.1 | 4161 | 2318 |
| 95/50 | 1.1/1.0 | 2.3 | 42.2 | 4456 | 1905 | 1.2 | 0.5 | 2.5 | 47.0 | 5432 | 2881 |
| 120/70 | 1.2/1.1 | 2.5 | 47.1 | 5663 | 2394 | 1.4 | 0.5 | 2.6 | 52.1 | 6736 | 3466 |
| 150/70 | 1.4/1.1 | 2.7 | 52.6 | 6857 | 2918 | 1.4 | 0.5 | 2.8 | 57.6 | 8048 | 4109 |
| 185/95 | 1.6/1.1 | 2.8 | 58.1 | 8591 | 3606 | 1.4 | 0.5 | 3.0 | 63.3 | 9931 | 4946 |
| 240/120 | 1.7/1.2 | 3.1 | 65.8 | 11159 | 4638 | 1.4 | 0.5 | 3.3 | 71.0 | 12668 | 6146 |
| 300/150 | 1.8/1.4 | 3.3 | 72.6 | 13860 | 5693 | 1.4 | 0.5 | 3.5 | 77.8 | 15518 | 7351 |
| 400/185 | 2.0/1.6 | 3.6 | 80.6 | 17573 | 7154 | 1.4 | 0.5 | 3.8 | 87.0 | 20238 | 9819 |
4. Our Factory
5. Our Honor
6. Contact Details
Jessica Wang | Taifeng Cable Co., Ltd.
Add.: Heda Center, No.177 Tailiu Road, Shibei District, Qingdao, China
Factory Add.: No.1 Taifeng Road, Dacaozhuang Administrative Zone, Xingtai City, Hebei Province, China
Tel: 0086 532 85611663
Phone: 0086 15192706553
Website: taifengcable.en.
We are China 5 Core XLPE Insulated PVC Sheathed Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Low Voltage Cable Products
Railway Train Station XLPE Insulated PVC Sheathed Copper Electric Wire
XLPE Cable / XLPE Insulated Power Cable
Aluminum Uganda Market Service Cable
Low Voltage XLPE Insulated PVC Sheathed Copper Conductor Power Cable (YJV, YJLV)
Factory Since 1988, PVC Insulated Stranded Power Cable Round Copper Flexible Electric Wire
XLPE Cable Low Voltage (LV) PVC/XLPE Insulated Armoured
Popular PVC Sheathed Cable Products
Low Voltage 4 Core XLPE Insutated PVC Sheathed Cable Cxv/Swa
300 - 500 PVC Insulated and PVC Sheathed Copper Conductors H05VV-U Cable
Cable 120 Sq mm LV 4/C Al PVC Swa PVC
Nyy 0.6/1kv PVC Insulated Power Cable to DIN/VDE Standard
0.6/1kv Aluminum Conductor PVC/XLPE Insulated 4 Core Power Cable 240 Sq mm
2.5sqmm LV 7/C Cu Copper PVC Insulated Swa Power Cable
Popular taifengcable Products
Sta/Swa Armoured XLPE Insulated PVC Sheathed Electrical Wire Power Cable
Low Voltage Power Cable 4X240+1X120mm2 XLPE Insulation Armoured Flame Retardant
ACSR 340/30 380/50 385/35 435/55 450/40 490/65
Copper/Aluminium Electric Power Cable Multi Cores Building Wire for House
XLPE Insulated PVC Sheathed Steel Tape Armoured Copper Electrical Cables
China Manufacturer XLPE Sheathed PVC Electrical Wire Cable
Popular XLPE Insulated Cable Products
0.6/1kv XLPE Insulated Overhead Electric Transmission Aerial Bundle Cable
Alu Erdleitung Starkstrom Kabel Nayy-J 5X70 RM Ground Wire Cable
Overhead ABC Cable Prices 16mm2 35mm2 50mm2 XLPE Insulated Aluminum ABC Cable
Low Voltage XLPE Insulated Electric Cable
Single Core Three Core Medium Voltage Cable PVC or PE Sheathed Middle Voltage Cable
Low Voltage Aluminum Core XLPE Insulated Power Cable 0.6/1kv
Tags: Low Voltage Cable, PVC Sheathed Cable, taifengcable, XLPE Insulated Cable