52-3 Porcelain Insulator
52-3 Porcelain Insulator image
Get Latest Price Request a quote
Quick Details
Product Details
CSA CANADIAN STANDARDS ASSOCIATION
G164-4 – Hot dip galvanizing of Irregular Shaped Articles
CAN/CSA – Quality Assurance Program Categories 2299.3
ANSI – AMERICAN NATIONAL STANDARDS INSTITUTE
C29.1 – American Standard Test Method For Electrical Power Insulators
C29.7 – American Standard For Wet-processed Porcelain Insulators (High Voltage Line Post Type) Electrical Power Insulators
987-1985 – IEEE Guide For Application of Composite Insulators
D750 – Recommended Practice for Operating Light and Weather Exposure Apparatus (Carbon Arc Type) For Artificial Weather Testing Of Rubber Compounds.
D1499 – Recommended Practice For Exposure of Plastics.
D2240 – Rubber Properties, Durometer Hardness
D2565 – Recommended Practice For Operating Xenon-Arc Light And Water Exposure Apparatus Plastics.
The weathershed of the Post Insulators shall be manufactured from either Hydrated Alumina Ethylene Propylene Copolymer (EPM) as the primary constituent or Silicone Elastomers. The weathershead shall be injection moulded and brought to final cure state in one continuous process to prevent internal undercure or surface overcure. Additionally, the weathershead shall provide hydrophobic surface, even after exposure to tropical marine environment, ultra violent rays and moisture.
Core
The rod or the core is manufactured from Fibreglass, having 70-75 by weight of auxiliary aligned glass fibre bonded by an organic resin. The rod is either be cast or pultruded.
The end fittings are have the following properties:
i. are compressed onto the Fibreglass rod member
ii. are not move relative to the central Fibreglass rod at applied loads equal to two times the rated Routine Test Load or maximum designed cantilever loads
iii. are attracted to the rod after completion of all external heat processes used to cure or bond component parts.
The insulator are provided load limiting bases that will deform under longitudinal loading of more than 100% of the rated design cantilever load.
Performance Characteristics
The Polymeric Insulators are meet the under listed performance characteristics.
| ITEM |
11kV |
33KV |
| Dry Flashover Withstand |
90kV |
180kV |
| Wet flashover withstand |
70kV |
165kV |
| Positive Impulse Critical flashover |
145kV |
300kV |
| Maximum Radio Interference Voltage |
Below 1micro volt |
Below 1 micro volt |
| Design Tension Strength |
100kN |
100kN |
| Residual Strength after Power Arc |
80kN |
80kN |
| Mechanical Proof Test Load |
45kN |
45kN |
| Maximum Sustained Load |
34kN |
34kN |
| Design Torque Rating |
83 Nm |
83 Nm |
The insulator are suitable for accepting both aluminium and copper conductors having cross-sectional areas ranging from 35mm2 to 265mm2. The insulators are designed for mounting on the angle and channel crossarms specified in Specification E14
All exposed ferrous part shall be treated against corrosion. Treatment by hot dip galvanizing is preferable.
We are China 52-3 Porcelain Insulator manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Composite Insulator Products
High Voltage Suspension Composite Phase-to-Phase Insulator Spacer 120kn Insulator
33kv Composite Polymer Station Post Insulator
Suspension Glass Insulator U70b, U120b, U160b
Hot Sale! ! ! ! P-11-Y/P-15-Y/P-22-Y/P-33-Y Pin Type Porcelain Insulator
Fzsw-110kv, 132kv, 220kv Composite Line Post Insulator Used in Distribution 10kn
Popular jgtrade1 Products
Nitrile Gloves, Safety Cuffnitrile Fully Coatedblue 7-11
Terminal Connectors for Horizontal Tubular Bus-Bar Type Mgp
Popular Polymer Insulator Products
TR202 polymer station post insulator
50kv AC and DC High Voltage Withstand Voltage Test Instrument
C10-550 Ceramic Porcelain Station Post Insulator
110kv Hv Polymeric Composite Suspension Tension Strain Insulator
Popular Silicone Rubber Insulator Products
3.5kv DC Withstand Voltage Test Instrument
33kv 70kn Eye and Hook Ended Tension Strain Long Rod Insulator
24kv composite station post insulator
Tags: Composite Insulator, jgtrade1, Polymer Insulator, Silicone Rubber Insulator