76/132kv Fully Prefabricated Type Insulating Joint Medium Voltage Cable Joint
76/132kv Fully Prefabricated Type Insulating Joint Medium Voltage Cable Joint image
Get Latest Price Request a quote
- Overview
- Company Profile
- FAQ
Basic Info.
Packaging & Delivery
Product Description
66-220kV High Voltage Cable Accessories
Our company provides the voltage level of 48/66kV, 64/110kV, 127/220kV and other series of cable accessories are all in accordance with IEC 60502, IEC 60840, IEC 62067, IEC 60859, IEC 62271-209, GB/T 11017, GB/T 18890, GB/T 12706, GB 311, GB 772, DL508, DL509, JB/T8144 and other standards, and have passed the stringent factory test, type test, pre-qualification test.
One piece pre-molded straight joint/sectionalizing joint
Scope of application
For cross linked polyethylene insulated power cables 240-3000mm2.
Suitable for large-scale chemical industry, iron and steel, power substations, coastal areas.
Features
The main body is a monolithic prefabricated structure, i.e. insulation, shielding and stress cone in one piece.
The stress cone is made of imported liquid silicone rubber injection molding, with a long and stable holding force and electric field uniformity.
Compact structure, small size, light weight, easy to install.
The shell is protected by an insulated, magnetically isolated metal protection box with good mechanical properties and good sealing.
Structure & Size
1,glass fiber
2,copper shell
3,stress cone
4,insulation of cable
5,epoxy insulating insulation
6,connecting pipe
7,shielding tiles
8,prefabricated body
9,coaxial cable
10,cable
| Size / mm | 38/66kV | 50/66kV | 64/110kV | 76/132kV | 127/220kV |
| L | 1300 | 1300 | 1500 | 1500 | 1800 |
| A | 1900 | 1900 | 2100 | 2100 | 2400 |
Test Specification
All test classifications and codes:
| No.# | Test Name | Code |
| 1 | Routine test | R |
| 2 | Sample test | S |
| 3 | Type test | T |
| 4 | Pre-qualification test | P |
| 5 | Additional test | A |
The following routine tests are performed on stress cones, epoxy bushings of GIS terminals and prefabricated intermediate joints of each product at 66kV and above.
| Item | Voltage | ||||
| 38/66kV | 50/66kV | 64/110kV | 76/132kV | 127/220kV | |
| Partial discharge | 54kV, no detectable local discharge over background | 72kV, no detectable local discharge over background | 96kV, no detectable local discharge over background | 114kV, no detectable local discharge over background | 190kV, no detectable local discharge over background |
| The power frequency withstand voltage | 90kV/30min | 125kV/30min | 160kV/30min | 190kV/30min | 318kV/30min |
| Sealing | Seal fittings, porcelain bushings, composite bushings for 0.25±0.01MPa/1h, no leakage | ||||
| The epoxy casing was subjected to 0.6~0.7MPa/1h with no leakage. | |||||
| Appearance | The products are free of damage, cracks, and other defects that may affect the quality and appearance of the products. | ||||
66-220kV Main Test Parameters
| Item | Standard | Test Category | Product Category | ||||||
| 48/66kV | 64/110kV | 127/220kV | Porcelain Sleeve Terminal | Composite Sleeve Terminal | GIS terminal | Straight / Insulated Joint | flexible terminal | ||
| Sealing Fittings, Porcelain, Composite Sleeves | 0.25±0.01MPa/1h, no leakage | R | yes | yes | yes | – | – | ||
| Epoxy Sleeve | 0.6~0.7MPa/1h, no leakage | ||||||||
| Partial discharge of prefabricated parts | 72kV | 96kV | 190kV | R | yes | yes | yes | yes | yes |
| Detects no more than background discharge | |||||||||
| Frequency withstand voltage of prefabricated parts | 120kV | 160kV | 318kV | R | yes | yes | yes | yes | yes |
| 30min,no flashover, no breakdown | |||||||||
| Partial discharge at room temperature | 72kV | 96kV | 190kV | T | yes | yes | yes | yes | yes |
| Detects no more than background discharge | |||||||||
| Thermal cycling voltage test | 96kV | 128kV | 254kV | T | yes | yes | yes | yes | yes |
| 20 cycles, no flashover, no breakdown | |||||||||
| Partial discharge test at high temperature | 72kV | 96kV | 190kV | T | yes | yes | yes | yes | yes |
| Detects no more than background discharge | |||||||||
| Lightning impact test and subsequent frequency withstand voltage test | 450kV | 550kV | 1050kV | T | yes | yes | yes | yes | yes |
| 10 times for each positive and negative polarity | |||||||||
| 120kV | 160kV | 318kV | |||||||
| 15min, no flashover, no breakdown | |||||||||
| Directly buried joint outer protective layer immersion voltage test | Two ends impact among the 60/75kV,an end of hit 30/37.5kV | Two ends impact among the 60/95kV,an end of hit 30/47.5kV | T | – | – | – | yes | – | |
| Sealing test after assembly of accessories | 0.25±0.01MPa/1h, no leakage | T | yes | yes | yes | yes | yes | ||
| Outdoor terminal rain frequency voltage test | 140kV | 185kV | 460kV | T | yes | yes | – | – | yes |
| 1min, no flashover, no breakdown | |||||||||
| Pillar insulator voltage test | 20kV/1min, no flashover, no breakdown | T | yes | yes | – | – | – | ||
| Radio interference test for outdoor terminals | 61kV | 81kV | 140kV | A | yes | yes | – | – | yes |
| 1MHz radio interference, voltage ≤ 450μV | 1MHz radio interference, voltage ≤ 500μV | ||||||||
| Accessory specimen test | Visual inspection of accessory systems containing cables with no signs of deterioration that could affect the normal operation of the system | T | yes | yes | yes | yes | yes | ||
| DC voltage test | / | No breakdown between conductor and metal shield in connector, 20kV/1min. | T | – | – | – | yes | – | |
| Performance test of crimped connectors for conductor connecting rods | The total area after crimping is not more than 1.2 times the resistance of an equal length of conductor of the same cross-section. | T | yes | yes | yes | yes | yes | ||
/* March 5, 2024 10:24:42 */
!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China 76/132kv Fully Prefabricated Type Insulating Joint Medium Voltage Cable Joint manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 76/132kv Fully Prefabricated Type Insulating Joint Medium Voltage Cable Joint Products
Popular Cable Accessory Products
64/110kv Fully Prefabricated Type Insulating Joint
76/132kv Fully Prefabricated Type Straight Through Joint
220kv Fully Prefabricated Type Straight Through Joint
Heat Shrink/Insulated Shrinkable Sleeve Tube Fast Shrinkage
Electrical Cable Sleeve Heat Shrink Tube
64/110kv Fully Prefabricated Type Insulating Joint
Popular High Voltage Products
M50-7sheds Ceramic Porcelain Long Rods Insulator
11kv Pin Type Polymeric Insulator
Rated Voltages up to and Including 35kv XLPE Insulated Power Cables
Long Rod Suspension Composite Insulator
Hv Cable Underground 66kv 110kv 132kv 220kv XLPE Cable
11kv Pin Insulator Porcelain Electrical Hot Sale Pin Type Ceramic Insulator
Popular jiuweielectric Products
Heat Shrinkable V0 Class Flame Retartant Cable Sleeve
3 Cores Heat Shrinkable Cable Breakout Anti-Tracking
35kv 3core Cold Shrink Outdoor Terminal Accessory Power Cable Joint Termination Kits
Electrical Insulation Materials 1kv Heat Shrink Tubing
3 Core 1kv-35kv Heat Shrinkable Cable Insulation Straight Joint Kits
Hot Sale Cold Shrink Straight Joint Kit Cold Shrink Cable Accessories Termination Kit
Tags: 76/132kv Fully Prefabricated Type Insulating Joint Medium Voltage Cable Joint, Cable Accessory, High Voltage, jiuweielectric