80A HRC Fuse
80A HRC Fuse image
Get Latest Price Request a quote
Quick Details
Product Details
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
| S/N | Description | Units | Schedule A | Schedule B | |
| 1 | Current ratings | A | 5 | ||
| 2 | Frequency | Hz | 50 | ||
| 3 | Rated Speed ratio | Type K as per IEC 60282 -2 |
|||
| 4 | Class of fuse link | Class B as per IEC 60282-2 |
|||
| 5 | Fuse element | Tin or Silver | |||
| 6 | Following Routine test results shall be provided on delivery of fuse links | Yes/No |
a) a static strength test; and | Yes | |
| b) a resistance test, with the fuse-link under strain. |
Yes |
||||
| 7 | The following tests shall be performed on one fuse-link per batch and test results provided on delivery of fuse links: |
Yes/No |
a)confirmation of the time/current characteristics; and |
Yes |
|
| b) a dynamic strength test. | Yes | ||||
| 8 | Drawing showing construction and dimensions as per figure 1 below to be provided with bid |
Yes/No | Yes | ||
| 9 | Previous type tests reports/certificate to be provided on bid. |
Yes/No |
Yes |
||
| 10 | Altitude above sea level | m | 1400 | ||
| 11 | Ambient operating | oC | -1 to 40 | ||
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 22 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 27 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 320 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2 |
| Performance Characteristic | |
| Applied standard | IEC60282-2 |
| Catalog number | |
| Nominal system voltage kV | 11 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 12 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 372 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | N/A |
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 33 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 38 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 8000/5000 |
| BIL 1.2×50 µs kV-peak | 150 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 165 |
| Dry withstand voltage kV-RMS | 70 |
| Wet withstand voltage kV-RMS | 60 |
| Creepage distance to group Min.mm | 650 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2.3 |
| DIMENSION(mm) | |||||
| RATED CURRENT (A) |
A | B | C | D | L MN |
| 1 to 25 | 12.5+0.2 | 19.0+0.2 | 6.5 | 2.0 | 533,600,787 |
| 30 to 40 | 12.5+0.2 | 19.0+0.2 | 8.0 | 3.0 | 533,600,787 |
| 50 to 100 | 19.0+0.3 | not applicable | 9.0 | 5.0 | 533,600,787 |
| 140 to 200 | 19.0+0.3 | not applicable | 13.0 | 7.0 | 533,600,787 |
We are China 80A HRC Fuse manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Fuse Link Products
1 0.5-Inch Gray Cow Hide Split Leather, Green Leather Reinforced Double Palm,
5 Threads Latex Glovespolyester Linerorange 7-11
Popular High Voltage Fuse Products
13G Nitrile Glovespolyesterblack 7-11
13G Latex Glovespolyester Linerblack 7-11
38kv High Voltage Fuse Cutout Arrester Combinations for Overhead
Fuse Links Mv Type J Slotted (400 AMPS)
Popular jgtrade1 Products
ACSR 556.4 Mcm Conductor Compression Clamp
Power Pole with a 170-280 Cap Hoop Wire Stent
High -Voltage Isolate Switch 12kv 200A
Polymer Fuse Cutout, Drop out Fuses 15 Kv 200A
High -Voltage Isolate Switch 40.5kv