Tcfs-12 12kv Indoor Small and Compact Electric Equipment Switch Cubicle
Tcfs-12 12kv Indoor Small and Compact Electric Equipment Switch Cubicle image
Get Latest Price Request a quote
Basic Info.
Product Description
Summary:
TCFS-12 Compact Stationary Solid Insulated Switchgear (hereinafter referred to as “switchgear”) is a new generation of extensible, modularized and free-maintenance metal enclosed switchgear, which is widely used in 3-12kVand 50Hz electric system. Its switches are including:
TLS load switch
TLS-T load switch+ fuse-combination unit
TVC breaker
TLG isolated earthing switch
Environmental Conditions:
2.1 Ambient air temperature
a) Upper +40ºC;
b) Lower -25ºC.
2.2 Ambient temperature
a) Daily average relative humidity:≤95%;
b) Monthly average relative humidity:≤90%;
c) Daily average saturated vapor pressure:≤2.2kPa,
d) Monthly average saturated vapor pressure:≤1.8kPa.
2.3 Altitude
No more than1500m.
2.4 Operation place
No flammable, explosive hazard, chemical corrosion and severe vibration.
Picture:
Specification:
| No. | Parameters name | Unit | Parameters | ||||||
| Circuit breaker | Load switch | ||||||||
| 1 | Rated voltage | kV | 12 | ||||||
| 2 | Rated current of main busbar | A | 630 | 1250 | |||||
| 3 | Rated frequency | Hz | 50 | ||||||
| 4 | Rated short time withstand current | Main circuit | kA | 25 | 31.5 | ||||
| Ground circuit | 21.7 | 27.4 | |||||||
| 5 | Rated short-time peak current | Main circuit | 63 | 80 | |||||
| Ground circuit | 54.5 | 68.5 | |||||||
| 6 | Rated short circuit withstand time | Main circuit | s | 4 | |||||
| Ground circuit | 2 | ||||||||
| 7 | Rated short circuit closing current (peak) | kA | 63 | 80 | |||||
| 8 | Rated short circuit breaking current | 25 | 31.5 | ||||||
| 9 | Rated short circuit breaking times | Times | 30 | ||||||
| 10 | Rated operation sequence | O-0.3s-CO-180s-CO | |||||||
| 11 | Mechanical life | Circuit breaker (load switch) | Times | 10000 | |||||
| Three-position switch | 5000 | ||||||||
| 12 | Rated insulation level | 1min power frequency withstand voltage (effective value) | Phase, to ground | kV | 42 | ||||
| Fracture | 48 | ||||||||
| Lightning impulse withstand voltage (peak) | Phase, to ground | 75 | |||||||
| Fracture | 85 | ||||||||
| Power frequency withstand voltage of secondary circuit | V | 2000 | |||||||
| 13 | Contact opening distance | mm | 9±1 | ||||||
| 14 | Overtravel | 3±0.5 | |||||||
| 15 | Interphase center distance | 210±1 | |||||||
| 16 | Closing contact bounce time | ms | ≤2 | ||||||
| 17 | Three phase asynchronous of opening | ≤2 | |||||||
| 18 | Opening time | highest | 17~55 | ||||||
| rated | |||||||||
| When the operating voltage is | Minimum | ||||||||
| 19 | Closing time | ms | 30~70 | ||||||
| 20 | Average opening speed (first 6mm average) | m/s | 1.0~1.8 | ||||||
| 21 | Average closing speed (after 6mm average) | 0.8~1.4 | |||||||
| 22 | Main conductive circuit’s resistance | μΩ | ≤100 | ||||||
| 23 | Contact pressure | N | 3200±150 | ||||||
| 24 | Opening contact’s rebound amplitude | mm | ≤2 | ||||||
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Tcfs-12 12kv Indoor Small and Compact Electric Equipment Switch Cubicle manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Electric Equipment Products
Aluminium Alloy Fd Type Damper for Powertransmission Line
Vic Cable Clamp Hot Line Clamp
Electric Power Accessories Fd Vibration Damper for ACSR Cable
33 Kv Pin Porcelain Insulators with Spindle
70kn 11kv Hot DIP Galvanized Forged Steel Long Socket Eye
Popular liyond Products
Sf6 Vcb Panel for 12kv Vacuum Breaker
1000mm Width Switchgear Withdrawable Element Electrical Chasis Truck Without Interlock Function
Vs1-12 Vacuum Circuit Breaker 2023
Kyn28 24kv Power Distribution Cabinet Removable Metal-Clad Switchgear Panel
Popular Switch Cubicle Products
Vgk550 Width550 with Vacuum Circuit Breaker MID-Set Switch Cubicle