Yjv 110kv-132kv XLPE Insulated 4core 95mm Power Cable
Yjv 110kv-132kv XLPE Insulated 4core 95mm Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
1. Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 15 times of the diameter of cable
For multi-core cable: Not less than 12 times of the diameter of cable
When the armored single core cable used for Alternative Current(AC) system, the armoring material should be non-magnetic.
2. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or direct in ground, able to bear external mechanical force, but unable to bear large pulling force.
3. Manufacturing Standards
IEC 60502-1 & Chinese national standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
4.Note:
If you want to know more details about 6mm armoured cable or this kind of products, please visit our website(homepage) because we have no ways to show so much information on this platform. Thank you.
5. Main technical data :
5.1 Main technical data of 0.6/1KV, Single core, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
| 1x10mm2 | RM | 1.0 | 0.2 | 1.8 | 12.9 | 3.08 |
| 1x16mm2 | RM | 1.0 | 0.2 | 1.8 | 13.9 | 1.91 |
| 1x25mm2 | RM | 1.2 | 0.2 | 1.8 | 14.3 | 1.20 |
| 1x35mm2 | RM | 1.2 | 0.2 | 1.8 | 15.5 | 0.868 |
| 1x50mm2 | RM | 1.4 | 0.2 | 1.8 | 17.2 | 0.641 |
| 1x70mm2 | RM | 1.4 | 0.2 | 1.8 | 19.0 | 0.443 |
| 1x95mm2 | RM | 1.6 | 0.2 | 1.8 | 21.3 | 0.320 |
| 1x120mm2 | RM | 1.6 | 0.2 | 1.8 | 22.9 | 0.253 |
| 1x150mm2 | RM | 1.8 | 0.2 | 1.8 | 24.9 | 0.206 |
| 1x185mm2 | RM | 2.0 | 0.2 | 1.8 | 27.1 | 0.164 |
| 1x240mm2 | RM | 2.2 | 0.2 | 1.8 | 30.2 | 0.125 |
| 1x300mm2 | RM | 2.4 | 0.5 | 2.0 | 35.2 | 0.100 |
| 1x400mm2 | RM | 2.6 | 0.5 | 2.1 | 38.8 | 0.0778 |
| 1x500mm2 | RM | 2.8 | 0.5 | 2.2 | 43.0 | 0.0605 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
5.2 Main technical data of 0.6/1KV, two cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
| 2×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 12.9 | 18.1 |
| 2×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.7 | 12.1 |
| 2x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 15.5 | 7.41 |
| 2x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.5 | 4.61 |
| 2x10mm2 | RM | 1.0 | 0.2 | 1.8 | 19.1 | 3.08 |
| 2x16mm2 | RM | 1.0 | 0.2 | 1.8 | 21.2 | 1.91 |
| 2x25mm2 | SM | 1.2 | 0.2 | 1.8 | 18.6 | 1.20 |
| 2x35mm2 | SM | 1.2 | 0.2 | 1.8 | 20.1 | 0.868 |
| 2x50mm2 | SM | 1.4 | 0.2 | 1.8 | 22.4 | 0.641 |
| 2x70mm2 | SM | 1.4 | 0.5 | 2.0 | 26.9 | 0.443 |
| 2x95mm2 | SM | 1.6 | 0.5 | 2.1 | 30.3 | 0.320 |
| 2x120mm2 | SM | 1.6 | 0.5 | 2.2 | 32.6 | 0.253 |
| 2x150mm2 | SM | 1.8 | 0.5 | 2.3 | 35.5 | 0.206 |
| 2x185mm2 | SM | 2.0 | 0.5 | 2.5 | 39.1 | 0.164 |
| 2x240mm2 | SM | 2.2 | 0.5 | 2.7 | 43.6 | 0.125 |
| 2x300mm2 | SM | 2.4 | 0.5 | 2.8 | 47.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
5.3 Main technical data of 0.6/1KV, three cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
| 3×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.4 | 18.1 |
| 3×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.3 | 12.1 |
| 3x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.1 | 7.41 |
| 3x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 4.61 |
| 3x10mm2 | RM | 1.0 | 0.2 | 1.8 | 20.0 | 3.08 |
| 3x16mm2 | RM | 1.0 | 0.2 | 1.8 | 22.3 | 1.91 |
| 3x25mm2 | SM | 1.2 | 0.2 | 1.8 | 21.3 | 1.20 |
| 3x35mm2 | SM | 1.2 | 0.2 | 1.8 | 23.2 | 0.868 |
| 3x50mm2 | SM | 1.4 | 0.2 | 1.9 | 26.2 | 0.641 |
| 3x70mm2 | SM | 1.4 | 0.5 | 2.0 | 31.1 | 0.443 |
| 3x95mm2 | SM | 1.6 | 0.5 | 2.2 | 35.4 | 0.320 |
| 3x120mm2 | SM | 1.6 | 0.5 | 2.3 | 38.2 | 0.253 |
| 3x150mm2 | SM | 1.8 | 0.5 | 2.4 | 41.7 | 0.206 |
| 3x185mm2 | SM | 2.0 | 0.5 | 2.6 | 46.0 | 0.164 |
| 3x240mm2 | SM | 2.2 | 0.5 | 2.8 | 51.4 | 0.125 |
| 3x300mm2 | SM | 2.4 | 0.5 | 3.0 | 56.5 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
5.4 Main technical data of 0.6/1KV, 3+1 cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation(mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath (mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
|||
| Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
| 3×2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 14.9 | 12.1 | 18.1 |
| 3×4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 16.7 | 7.41 | 12.1 |
| 3×6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 18.2 | 4.61 | 7.41 |
| 3×10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 20.8 | 3.08 | 4.61 |
| 3×16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 23.5 | 1.91 | 3.08 |
| 3×25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 24.2 | 1.20 | 1.91 |
| 3×35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 25.9 | 0.868 | 1.91 |
| 3×50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.0 | 30.5 | 0.641 | 1.20 |
| 3×70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.9 | 0.443 | 0.868 |
| 3×95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.3 | 38.5 | 0.320 | 0.641 |
| 3×120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 41.8 | 0.253 | 0.443 |
| 3×150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.5 | 45.0 | 0.206 | 0.443 |
| 3×185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.7 | 49.9 | 0.164 | 0.320 |
| 3×240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 2.9 | 55.5 | 0.125 | 0.253 |
| 3×300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.1 | 61.0 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
5.5 Main technical data of 0.6/1KV, four cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables
CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
| 4×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.2 | 18.1 |
| 4×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.1 | 12.1 |
| 4x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 7.41 |
| 4x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 4.61 |
| 4x10mm2 | RM | 1.0 | 0.2 | 1.8 | 21.6 | 3.08 |
| 4x16mm2 | RM | 1.0 | 0.2 | 1.8 | 24.1 | 1.91 |
| 4x25mm2 | SM | 1.2 | 0.2 | 1.8 | 23.8 | 1.20 |
| 4x35mm2 | SM | 1.2 | 0.2 | 1.8 | 25.9 | 0.868 |
| 4x50mm2 | SM | 1.4 | 0.5 | 2.0 | 31.4 | 0.641 |
| 4x70mm2 | SM | 1.4 | 0.5 | 2.1 | 35.0 | 0.443 |
| 4x95mm2 | SM | 1.6 | 0.5 | 2.3 | 39.9 | 0.320 |
| 4x120mm2 | SM | 1.6 | 0.5 | 2.4 | 43.1 | 0.253 |
| 4x150mm2 | SM | 1.8 | 0.5 | 2.6 | 47.3 | 0.206 |
| 4x185mm2 | SM | 2.0 | 0.5 | 2.8 | 52.3 | 0.164 |
| 4x240mm2 | SM | 2.2 | 0.5 | 3.0 | 58.4 | 0.125 |
| 4x300mm2 | SM | 2.4 | 0.5 | 3.2 | 64.3 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
5.6 Main technical data of 0.6/1KV, five cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables , CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
| 5×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.0 | 18.1 |
| 5×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 16.1 | 12.1 |
| 5x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 7.41 |
| 5x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 19.8 | 4.61 |
| 5x10mm2 | RM | 1.0 | 0.2 | 1.8 | 23.3 | 3.08 |
| 5x16mm2 | RM | 1.0 | 0.2 | 1.8 | 26.2 | 1.91 |
| 5x25mm2 | SM | 1.2 | 0.2 | 1.8 | 26.1 | 1.20 |
| 5x35mm2 | SM | 1.2 | 0.5 | 2.0 | 30.7 | 0.868 |
| 5x50mm2 | SM | 1.4 | 0.5 | 2.1 | 34.6 | 0.641 |
| 5x70mm2 | SM | 1.4 | 0.5 | 2.3 | 38.9 | 0.443 |
| 5x95mm2 | SM | 1.6 | 0.5 | 2.5 | 44.4 | 0.320 |
| 5x120mm2 | SM | 1.6 | 0.5 | 2.6 | 47.9 | 0.253 |
| 5x150mm2 | SM | 1.8 | 0.5 | 2.8 | 52.6 | 0.206 |
| 5x185mm2 | SM | 2.0 | 0.5 | 2.9 | 57.9 | 0.164 |
| 5x240mm2 | SM | 2.2 | 0.5 | 3.2 | 65.0 | 0.125 |
| 5x300mm2 | SM | 2.4 | 0.5 | 3.4 | 71.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
5.7 Main technical data of 0.6/1KV, 4+1 cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation(mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath (mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
|||
| Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
| 4×2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 15.9 | 12.1 | 18.1 |
| 4×4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 18.0 | 7.41 | 12.1 |
| 4×6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 19.6 | 4.61 | 7.41 |
| 4×10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 22.6 | 3.08 | 4.61 |
| 4×16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 25.6 | 1.91 | 3.08 |
| 4×25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 26.6 | 1.20 | 1.91 |
| 4×35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.9 | 28.7 | 0.868 | 1.91 |
| 4×50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.8 | 0.641 | 1.20 |
| 4×70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.3 | 37.8 | 0.443 | 0.868 |
| 4×95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 42.8 | 0.320 | 0.641 |
| 4×120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.6 | 46.6 | 0.253 | 0.443 |
| 4×150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.7 | 50.4 | 0.206 | 0.443 |
| 4×185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.9 | 55.9 | 0.164 | 0.320 |
| 4×240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 3.1 | 62.2 | 0.125 | 0.253 |
| 4×300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.3 | 68.4 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Why Choose us?
For over 20 years, Zhengzhou Jinyuan Wire and Cable Co., Ltd., as a professional armoured cable, PVC cable, Aluminum cable manufacturer has been producing customized cable for a wide range of applications based on high quality, excellent service and competitive market prices. This is an elite team with experienced personnel and strong technical support. Our achievements benefit by having access to the largest market for cheap labor and abundant resources in China and our determination to exceed our clients’ expectations.
PRODUCTS & STANDARDS
We can produce more than 2,000 types of cables and wires, such as
Bare Conductor: AAC, AAAC, ACSR, ACSR/AW, ACAR, ACSS, ACSS/AW, Aluminum Clad Steel Wire/Strand, Bare Copper Conductors, Copper Clad Steel Wire/Strand, Copper Clad Aluminum(CCA), Galvanized Steel Wire/Strand, etc.
Overhead Insulated Cable: Covered Line Single Core Cable and Aerial Bundled Cable (ABC). ABC includes Duplex, Triplex, Quadruplex and more Cores Service Drop Cable.
PVC Insulated Wire up to 450/750V
PVC or XLPE Insulated Power Cable from 1kV to 36kV
Control Cable
Welding Cable
Rubber Cable
We can produce cables according to the standards of IEC, ASTM, EN (BS, DIN, NF, etc.), AS/NZ and meet customers’ special requirements.
ACHIEVEMENTS & COMMITMENT
Our cable has been exported to South-East Asia, South Asia, Middle-East, Europe, North and South America, Africa, Australia & New Zealand and so on. Zhengzhou Jinyuan Wire and Cable Co., Ltd.’s commitment is to be recognized as a zero-defect world class manufacturer in cable industry through continuous improvement of our quality, processes, and products, and by our determination to exceed our clients’ expectations.
Welcome to contact us for more information about the 6mm armoured cable or other size cables.
web 1: jytopcable.en.
We are China Yjv 110kv-132kv XLPE Insulated 4core 95mm Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 240mm2 Power Cable Products
OEM RoHS Compliant High Quality 240mm2 Power Cable
240mm 3 Core Armoured Cable XLPE Insulation 11kv Power Cable
33kv 240mm2 Single Core XLPE Power Cable
Underground XLPE 240mm2 120mm Power Cables
BS 5467 Swa PVC Basec Multi Core 0.6/1kv Cable
Popular 4 Core 95mm Power Cable Products
4 Core 95mm Power Cable for Underground Electric Cable
N2xry LV 0.6/1kv XLPE Power Cable 4 X95mm2 4 Core 95mm Power Cable
4 Core 95mm Power Cable Power Cable Wire
Top Quality 4 Core 95mm Power Cable Wire Electric
4 Core Copper Conductor PVC Insulated Steel Wire Armoured 95mm Power Cable
Popular 400mm Power Cable Products
0.6/1kv 400mm Aluminum Conductor XLPE Insulated Power Cable
400 Kv Cable/400 Sq mm Cable/400mm Power Cable
400mm2 Yjv Single Core Copper Conductor XLPE Insulated Power Cable
Aluminum Conductive Core PVC or PE Sheath 400mm Power Cable
3.8/6.6kv XLPE Insulated 400mm 240mm2 185mm2 240 Sq mm 50 Sq mm 50mm2 500mm2 Electric Power Cable
400 Sq mm Cable/400mm Power Cable/400 Kv Cable
Popular jytopcable Products
Thw Wire PVC Wire Building Wire Electric Wire
120mm2 Overhead Cable All Aluminum Conductor AAC AAAC ACSR
20kv Copper Conductor XLPE Insulated Steel Tape Armored Power Cable
Electrical Hard Drawn Copper Conductor Copper Bare Wire Ground Cable
CSA C49 Standard AAC Conductor
600/1000V Kabel Yky Yaky Cable Nayy Cable
Tags: 240mm2 Power Cable, 4 Core 95mm Power Cable, 400mm Power Cable, jytopcable