Sz-50000/69/6.3 50mva 66kv Double-Winding Power Transformers with on-Load Tap Changer Distribution Transformer
Sz-50000/69/6.3 50mva 66kv Double-Winding Power Transformers with on-Load Tap Changer Distribution Transformer image
Get Latest Price Request a quote
Basic Info.
Product Description
Technical paramters:
| Rated Capacity(MVA): | 50 |
| Voltage ratio HV(KV): | 69 |
| Voltage ratio LV(KV): | 6.3 |
| Voltage ratio HV Tapping Range(kv): | ± 8 x 1.25% |
| Connection symbol: | YND11 |
| No-load Loss(KW): | 47.6 |
| No-load Current(%): | 0.4 |
| Full-load Loss(KW): | 184.5 |
| Impedance(%): | 9 |
| Reference Temperature | ° C | 75 | |||
| No-Load Losses at Principal Tapping: | W | 9.0 kW | |||
| Looses of Cooling Fan System | W | / | |||
| Insulation Levels (LI/AC): | LI325AC140/LI125AC55 | ||||
| No Load Current: | @ Un | % In | 0.56 | ||
| @ 1.05 Un | % In | 0.68 | |||
| Sound Level: | dB | < 67 | |||
| Short Circuit Impedance at Principal Tapping: | P/S | % Un | 8~10% | ||
| P/T | % Un | ||||
| S/T | % Un | ||||
| Reference Temperature | ° C | 75 | |||
| Top Oil Temperature Rise: | °C | 51K | |||
| Average Winding Temperature Rise: | °C | 64K | |||
| Insulation Resistance (Reference Temperature = 20°C): | |||||
| HV/LV / | Mohms | ≥1000 | |||
| HV/GR – LV/GR – | Mohms | ≥1000 | |||
Order Instructions
When you choose our company product, please offer following data:
Transformer model:
Rated capacity: kVA
Phase:Three-phase
Single-phase
Frequency:50HZ
60HZ
Rated voltage ( H.V. / L.V. ):
Tapping range: ± × %
Insulation level: LI AC / LI AC kv
Veotor group: Dyn11
Yyno
Other
Short-circuit Impedance: %
Cooling method:ONAN
ONAF
Tapping method:OLTC
OCTC
Other
Other requirement:
Notes:
We also can design special products according to customer’s particular requirements.
The final dimension is subject to outline drawing.
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Sz-50000/69/6.3 50mva 66kv Double-Winding Power Transformers with on-Load Tap Changer Distribution Transformer manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular cnville Products
Transformers 220kv Power Transmission Power Transformer Custom Made Free Design
S11-31500/35 31.5mva S11 Series 35kv Power Transformer with on Load Tap Changer
Transformer Custom Made Free Design 1600kVA 35kv Power Transformer with on Load Tap Changer
50t Electric Arc Furnace (eaf) Manufacture for Calcium Carbide & Steel Melting
Customized Power Amplifier Toroidal Transformer Toroidal for Amplifier
Conductive Arm for Electric Arc Furnace
Popular Electric Transformer Products
S11-20000/35 20mva S11 Series 35kv Power Transformer with on Load Tap Changer
8mva S11 Series 35kv Power Transformer with on Load Tap Changer
Sz9-31500/35 31.5mva Sz9 Series 35kv Power Transformer with on Load Tap Changer
S9-25000/35 25mva S9 Series 35kv Power Transformer with on Load Tap Changer
High Voltage Power Transformer/Distribution Transformer 30kVA~150mva
S9-6300/35 6.3mva S9 Series 35kv Power Transformer with on Load Tap Changer
Popular Sz-50000/69/6.3 50mva 66kv Double-Winding Power Transformers with on-Load Tap Changer Distribution Transformer Products
Popular Transformer Products
S9-Ms-2000/10 2mva S9-Ms Series 6kv/10kv Petrochemail Power Transformer
Toroidal Distribution Current Transformer Residual Zero Sequence Current Transformer
Manufacture 2500kVA 33kv Distribution Transformers
environmental Friendly Oil Immersed Power Transformer Manufacturer for Subway/Railway/Power Plant
Low Noise Traction Oil-Immersed Transformer Power Grid with TUV
Tags: cnville, Electric Transformer, Sz-50000/69/6.3 50mva 66kv Double-Winding Power Transformers with on-Load Tap Changer Distribution Transformer, Transformer