Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard
Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard image
Get Latest Price Request a quote
Basic Info.
Product Description
NFC33-226 is a medium voltage power cable with a rated voltage of 12kV to 20kV. The cables are available in single core or 3×1 construction and are suitable for buried, direct burial in soil or free air laying. The cable can be supplied with sheath colors according to the installation code: red for underground connections, gray for aerial, surface/underground and technical applications.
Specifically, product features and parameters of NFC33-226 cables may include:
1.Suitable for medium voltage power system from 12kV to 20kV;
2.Single core or 3×1 (clover) structure available;
3.It can be laid underground, directly buried in soil or in free air;
4.Sheath color can be selected according to installation specifications;
5.Aluminum material as a conductor;
6.XLPE and PE materials as insulation and sheath materials.
Features
- It can be applied to medium-voltage power systems from 12kV to 20kV, providing an efficient and reliable power transmission solution;
- Single core or 3×1 structure can be provided according to application requirements, which can meet the needs of different circuit connection methods;
- It can be laid underground, directly buried in soil or in free air, suitable for different application scenarios;
- Different colors of sheaths can be selected according to installation specifications, which helps to distinguish different types of cables and realize management and maintenance;
- Aluminum material is used as the conductor, which is not only light in weight and low in cost, but also has good electrical conductivity, thermal conductivity and corrosion resistance;
- XLPE and PE materials are used as insulation and sheath materials, which have good performances such as voltage resistance, heat resistance, and welding resistance.
Application
NFC33-226 cables are suitable for medium voltage power systems, with rated voltages between 12kV and 20kV. It can be used as a distribution line to transmit power, lighting and control signals, and can be applied in different scenarios, such as directly buried in the ground, laid in free air or buried in the soil.
More specifically, the application areas of NFC33-226 may include
1.Municipal engineering
Applied in the power distribution network of urban public facilities, streets and other areas
2.Industrial and mining enterprises:
Used in the construction and transformation of power distribution trunk lines in factories, mines and other places;
3.Residential quarters
Used as power distribution lines in residential quarters and villas.
Construction
Medium-voltage power cables have shielding and sheathing, and non-magnetic armoring can be used under necessary conditions. Refer to the figure below for the structure of conventional cables.
Performance
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 3.4 | 23.1 | 53.4 | 2603 | 0.387 | 230 | 235 |
| 3×1×70 | 3.4 | 24.9 | 57.5 | 3316 | 0.268 | 285 | 295 |
| 3×1×95 | 3.4 | 26.6 | 61.2 | 4153 | 0.193 | 340 | 360 |
| 3×1×120 | 3.4 | 28.3 | 64.9 | 4953 | 0.153 | 385 | 420 |
| 3×1×150 | 3.4 | 29.9 | 67.9 | 5815 | 0.124 | 430 | 475 |
| 3×1×185 | 3.4 | 31.5 | 72.0 | 6947 | 0.0991 | 485 | 550 |
| 3×1×240 | 3.4 | 34.0 | 77.6 | 8704 | 0.0754 | 560 | 650 |
NFC 33-226 Medium voltage cables (non-aerial) 6/10kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 3.4 | 23.1 | 53.4 | 1739 | 0.641 | 180 | 185 |
| 3×1×70 | 3.4 | 24.9 | 57.5 | 2070 | 0.443 | 220 | 230 |
| 3×1×95 | 3.4 | 26.6 | 61.2 | 2420 | 0.320 | 260 | 280 |
| 3×1×120 | 3.4 | 28.3 | 64.9 | 2769 | 0.253 | 300 | 325 |
| 3×1×150 | 3.4 | 29.9 | 67.9 | 3115 | 0.206 | 335 | 370 |
| 3×1×185 | 3.4 | 31.5 | 72.0 | 3574 | 0.164 | 380 | 425 |
| 3×1×240 | 3.4 | 34.0 | 77.6 | 4267 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 6/10kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 4.5 | 25.5 | 58.6 | 2892 | 0.387 | 230 | 245 |
| 3×1×70 | 4.5 | 27.3 | 62.7 | 3626 | 0.268 | 280 | 305 |
| 3×1×95 | 4.5 | 29.0 | 66.4 | 4481 | 0.193 | 335 | 375 |
| 3×1×120 | 4.5 | 30.7 | 70.1 | 5299 | 0.153 | 385 | 425 |
| 3×1×150 | 4.5 | 32.3 | 73.1 | 6176 | 0.124 | 430 | 485 |
| 3×1×185 | 4.5 | 33.9 | 77.2 | 7328 | 0.0991 | 490 | 560 |
| 3×1×240 | 4.5 | 36.4 | 82.8 | 9113 | 0.0754 | 560 | 660 |
NFC 33-226Medium voltage cables (non-aerial) 8.7/15kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 4.5 | 25.5 | 58.6 | 2028 | 0.641 | 180 | 190 |
| 3×1×70 | 4.5 | 27.3 | 62.7 | 2379 | 0.443 | 220 | 235 |
| 3×1×95 | 4.5 | 29.0 | 66.4 | 2748 | 0.320 | 260 | 290 |
| 3×1×120 | 4.5 | 30.7 | 70.1 | 3115 | 0.253 | 300 | 330 |
| 3×1×150 | 4.5 | 32.3 | 73.1 | 3476 | 0.206 | 335 | 375 |
| 3×1×185 | 4.5 | 33.9 | 77.2 | 3955 | 0.164 | 380 | 430 |
| 3×1×240 | 4.5 | 36.4 | 82.8 | 4676 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 8.7/15kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 5.5 | 28.0 | 63.4 | 3180 | 0.387 | 230 | 245 |
| 3×1×70 | 5.5 | 29.5 | 67.5 | 3932 | 0.268 | 280 | 305 |
| 3×1×95 | 5.5 | 31.2 | 71.2 | 4804 | 0.193 | 335 | 375 |
| 3×1×120 | 5.5 | 32.9 | 74.9 | 5639 | 0.153 | 385 | 425 |
| 3×1×150 | 5.5 | 34.5 | 77.9 | 6530 | 0.124 | 430 | 485 |
| 3×1×185 | 5.5 | 36.1 | 82.0 | 7701 | 0.0991 | 490 | 560 |
| 3×1×240 | 5.5 | 38.6 | 87.6 | 9511 | 0.0754 | 560 | 660 |
NFC 33-226 Medium voltage cables (non-aerial) 12/20kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 5.5 | 28.0 | 63.4 | 2316 | 0.641 | 180 | 190 |
| 3×1×70 | 5.5 | 29.5 | 67.5 | 2685 | 0.443 | 220 | 235 |
| 3×1×95 | 5.5 | 31.2 | 71.2 | 3071 | 0.320 | 260 | 290 |
| 3×1×120 | 5.5 | 32.9 | 74.9 | 3455 | 0.253 | 300 | 330 |
| 3×1×150 | 5.5 | 34.5 | 77.9 | 3830 | 0.206 | 335 | 375 |
| 3×1×185 | 5.5 | 36.1 | 82.0 | 4328 | 0.164 | 380 | 430 |
| 3×1×240 | 5.5 | 38.6 | 87.6 | 5074 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 12/20kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 8.0 | 33.1 | 75.2 | 3979 | 0.387 | 230 | 245 |
| 3×1×70 | 8.0 | 34.9 | 79.2 | 4777 | 0.268 | 280 | 305 |
| 3×1×95 | 8.0 | 36.8 | 83.4 | 5725 | 0.193 | 335 | 375 |
| 3×1×120 | 8.0 | 38.3 | 86.6 | 6565 | 0.153 | 385 | 425 |
| 3×1×150 | 8.0 | 39.9 | 89.6 | 7491 | 0.124 | 430 | 485 |
| 3×1×185 | 8.0 | 41.5 | 93.7 | 8707 | 0.0991 | 490 | 560 |
| 3×1×240 | 8.0 | 44.0 | 99.3 | 10579 | 0.0754 | 560 | 660 |
NFC 33-226 Medium voltage cables (non-aerial) 18/30kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 8.0 | 33.1 | 75.2 | 3115 | 0.641 | 180 | 190 |
| 3×1×70 | 8.0 | 34.9 | 79.2 | 3530 | 0.443 | 220 | 235 |
| 3×1×95 | 8.0 | 36.8 | 83.4 | 3992 | 0.320 | 260 | 290 |
| 3×1×120 | 8.0 | 38.3 | 86.6 | 4381 | 0.253 | 300 | 330 |
| 3×1×150 | 8.0 | 39.9 | 89.6 | 4790 | 0.206 | 335 | 375 |
| 3×1×185 | 8.0 | 41.5 | 93.7 | 5334 | 0.164 | 380 | 430 |
| 3×1×240 | 8.0 | 44.0 | 99.3 | 6143 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 18/30kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular chinajinshui Products
Electrical Wire Flat Cable 2 Core 3 Core 1.5 2.5 4sqmm Jacket PVC Wire and Cable
IEC 60502 Standard Aluminium XLPE ABC PVC Insulated Electric Cable
0.6/1kv Electric PVC Conductor PVC XLPE Insulated ABC Overhead Electrical Wire Cable
18/30kv Cu/XLPE/Swa Power Cable 3*150 3*240
PVC Material Standard EV Charging Cable
Aluminum Conductor Steel Reinforced ACSR 680/85 mm2 DIN 48204
Popular Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard Products
Popular Medium Voltage Cable Products
Medium Voltage Urd Cable UL1072 Standard 15kv 35kv XLPE Insulation Power Cable Mv105 Mv90
Medium Voltage Aerial Bundle Cable
8.7/15kv XLPE Insulated PVC Sheathed 3 Core Power Cable
11kv Copper XLPE Electrica Cable 3 X 240mm2 Power Cable Price
15kv Copper Wire XLPE Mv90 Cable
Single Core XLPE Insulated Copper Power Armoured Cable
Popular Overhead Cable Products
Triplex Cyclops, Lepas, Shrimp, Arca XLPE Insulated ABC Cable
10kv and 35kv Aerial Insulated Power Cable
4 Core Overhead Copper Wire ABC Aluminum Cable
Aluminum Conductor ABC Power XLPE Insulated PVC Douplex Triple Overhead Aerial Bundle Cable
Tags: chinajinshui, Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard, Medium Voltage Cable, Overhead Cable