Quick Details
Product Details
Aluminium Conductors. Polythylene or Crosslinked Polyethylene Insulation.
ABC Cables Applications:
Used to supply 3 phase power, usually from a pole-mounted transformer, to the user’s service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.
ABC Cables Construction:
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR.One conductor is manufactured with an extruded ridge for phase identification.
ABC Cables Standards:
1.B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2.B-231 Aluminum conductors, Concentric-Lay-Stranded.
3.B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
4.B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
5.B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
6.Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
ABC Cables Using Properties
1.Rated Voltage:0.6/1kV
2.Cable installation temperature not less than -20°C
3.Max. temperature of cable at short circuit(The max. duration does not exceed 5 minutes)
For XLPE insulation is 250°C.
For HDPE insulation is 150 °C.
4.The Max. bending radius of cable shall not be less than 20Dmm(D overall diameter of cable)
Type of ABC Cable
1.Duplex Service Drop:To supply 120 volt aerial service for temporary service at construction sites,outdoor or street lighting . For service at 600 volts or lower at a conductor temperature of 75 maximum.
2.Triplex Service Drop: To supply power from the ulility`s lines to the consumer`s weatherhead. For service at 600 volts or less(phase to phase ) at a conductor temperature of 75 maximum for PE insulation or 90 maximum for XLPE insulation .
3.Quadruplex Service Drop: Used to supply 3 phase power , usually from a pole-mounted transformer to the use`s servic head where connection to the service entance cable is made . To be used at voltages of 600 volts or less phase to phase and at conductor temperature not to exceed 75 for PE insulated conductors or 90 for XLPE insulated conductors.
ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for type USE
Federal Specification JC-30B NEC
Code Name | Phase Conductor | Neutral | Single Phase Conductor(in) | Outside diameter(in) | Weight Per 1000ft (lbls) | Ampacity | |||||
Size AWG | Strand | Insulation Thickness (mls) | Size AWG | Strand | Insulation Thickness (mls) | Direct Burial | In Duct | ||||
Tulsa | 4 | 7/w | 60 | 4 | 7/w | 60 | .345 | .833 | 258 | 119 | 85 |
Dyke | 2 | 7/w | 60 | 4 | 7/w | 60 | .403 | .938 | 346 | 153 | 115 |
Wittenberg | 2 | 7/w | 60 | 2 | 7/w | 60 | .403 | .973 | 375 | 153 | 115 |
Notre Dame | 1/0 | 19/w | 80 | 2 | 7/w | 60 | .522 | 1.188 | 541 | 198 | 150 |
Purdue | 1/0 | 19/w | 80 | 1/0 | 19/w | 80 | .522 | 1.260 | 596 | 198 | 150 |
Syracuse | 2/0 | 19/w | 80 | 1/0 | 19/w | 80 | .566 | 1.316 | 664 | 225 | 170 |
Lafayette | 2/0 | 19/w | 80 | 2/0 | 19/w | 80 | .566 | 1.367 | 720 | 225 | 170 |
Swarthmore | 3/0 | 19/w | 80 | 1/0 | 19/w | 80 | .616 | 1.430 | 805 | 250 | 195 |
Davidson | 3/0 | 19/w | 80 | 3/0 | 19/w | 80 | .616 | 1.487 | 874 | 250 | 195 |
Wake Forest | 4/0 | 19/w | 80 | 2/0 | 19/w | 80 | .672 | 1.560 | 979 | 290 | 225 |
Earlham | 4/0 | 19/w | 80 | 4/0 | 19/w | 80 | .672 | 1.623 | 1066 | 290 | 225 |
Slippery Rock | 350 | 37/w | 95 | 4/0 | 19/w | 80 | .851 | 1.945 | 1544 | 385 | 305 |
Wofford | 500 | 37/w | 95 | 350 | 37/w | 95 | .851 | 2.348 | 2174 | 467 | 420 |
Windham | 750 | 61/w | 110 | 500 | 37/w | 95 | .979 | 2.850 | 2542 | 615 | 492 |
We are China ABC Cable XLPE Insulation HDPE Sheath/Jacket Sac Single Aluminium Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular ABC Cable Products
AAC AAAC ACSR Conductor PVC/XLPE Insulated ABC Cable
0.6/1kv Aluminum Conductor XLPE Insulated ABC Cable
0.6/1kv ABC Aluminum Conductor Aerial Bundled HDPE Power Cable.
Low Voltage 600V Triplex Service Cable 2X4AWG+4AWG
0.6/1kv Aluminum Wire XLPE Insulation ABC Wire Cable
Quadruplex 0.6/1kv XLPE Insulated Al Conductor Aerial Bundle Overhead ABC Cable
Popular HDPE Sheath/Jacket Products
10kv/33kv/35kv XLPE Insulated HDPE Sheath/Jacket Aerial Isolated Cable
Popular huatongcable Products
Copper Conductor Double XLPE Sheathed PV Cable Low Voltage 6mm
Factory Price Duplex Service Drop Cable ABC Cable 6 AWG Retriever
0.6/1kv XLPE Insulated PVC Sheathed Power Cable for Hot Sale Factory Price
UL/TUV/RoHS H01z2z2K UV Resistant -40 Degree 4mm 6mm PV Wire PV/Solar Cable
IEC 60227 Copper Conductor PVC Insulation Electric Wire BV 0.75mm2
Service Drop Cable Aerial Bundled Cable Twisted Aluminum ABC Cable
Popular Sac Products
33kV SAC Aluminum Spaced Aerial Cable TIS 2341-2555
ABC Cable Manufacturer 33kv Sac Aluminum Spaced Aerial Cable Tis 2341-2555
22kV SAC Aluminum Spaced Aerial Cable TIS 2341-2555
Aluminum conductor Aerial, size 185 sq.mm, 22kV SAC Space Aerial Cables TIS 293
Aluminum conductor Aerial, size 50 sq.mm, 33kV SAC Space Aerial Cables TIS 293
Aluminum conductor Aerial, size 185 sq.mm, 33kV SAC Space Aerial Cables TIS 293
Tags: ABC Cable, HDPE Sheath/Jacket, huatongcable, Sac