AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 image
Get Latest Price Request a quote
Quick Details
Product Details
AAAC (All Aluminum Alloy Conductor) referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR;
Having lower breaking loads than the latter, their use becomes particularly favourable when ice and win loadings are low.
We can supply this conductor according to different recognized standards, such as BS EN50182, IEC61089, ASTM B399DIN 48, customer special specification also can be satisfied.
2. Applications:
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics. Aluminum-alloy gives 6201-T81 gives AAAC higher resistance to corrosion than ACSR.
3. Standards&Specifications:
All Aluminium Alloy Conductor-AAAC (DIN 48201 Standard Sizes)
| Nominal Area | Conductor Construction | Calculated Area | Overall Diameter | Weight | DC Resistance at 20 |
| mm2 | No./mm | mm2 | mm | kg/km | Ω/km |
| 16 | 7/1.70 | 15.9 | 5.1 | 43.5 | 2.091 |
| 25 | 7/2.10 | 24.2 | 6.3 | 66.4 | 1.370 |
| 35 | 7/2.50 | 34.4 | 7.5 | 94.1 | 0.9669 |
| 50 | 7/3.00 | 49.5 | 9.0 | 135 | 0.6714 |
| 50 | 19/1.80 | 48.3 | 9.0 | 133 | 0.6905 |
| 70 | 19/2.10 | 65.8 | 10.5 | 181 | 0.5073 |
| 95 | 19/2.50 | 93.3 | 12.5 | 257 | 0.358 |
| 120 | 19/2.80 | 117 | 14 | 322 | 0.2854 |
| 150 | 37/2.25 | 147 | 15.7 | 406 | 0.2274 |
| 185 | 37/2.50 | 182 | 17.5 | 501 | 0.1842 |
| 240 | 61/2.25 | 243 | 20.2 | 671 | 0.1383 |
| 300 | 61/2.50 | 299 | 22.5 | 828 | 0.1120 |
| 400 | 61/2.89 | 400 | 26.0 | 1,106 | 0.0838 |
| 500 | 61/3.23 | 500 | 29.1 | 1382 | 0.06709 |
| 625 | 91/2.96 | 626 | 32.6 | 1,735 | 0.05367 |
| 800 | 91/3.35 | 802 | 36.9 | 2,222 | 0.0419 |
| 1000 | 91/3.74 | 1,000 | 41.1 | 2,770 | 0.03362 |
| ALUMINIUM ALLOY CONDUCTOR ASTM B399 | |||||||||
| Code Name | Area | Size&Stranding of ACSR with equal diameter | No. and diameter | Overall diameter | Weight | Nominal breaking load | MAX .DC resistance at 20ºC | ||
| Nominal | Actual | AWG or MCM | Al/St | ||||||
| MCM | mm2 | mm | mm | kg/km | kN | ohm/km | |||
| AKRON | 30.58 | 15.48 | 6 | 6/1 | 7/1.68 | 5.04 | 42.7 | 4.92 | 0.3966 |
| ALTON | 48.69 | 24.71 | 4 | 6/1 | 7/2.12 | 6.35 | 68 | 7.84 | 0.3811 |
| AMES | 77.47 | 39.22 | 2 | 6/1 | 7/2.67 | 8.02 | 108 | 12.45 | 0.3671 |
| AZUSA | 123.3 | 62.38 | 1/0 | 6/1 | 7/3.37 | 10.11 | 172 | 18.97 | 0.3524 |
| ANAHEIM | 155.4 | 78.65 | 2/0 | 6/1 | 7/3.78 | 11.35 | 217 | 23.93 | 0.3448 |
| AMHERST | 195.7 | 99.22 | 3/0 | 6/1 | 7/4.25 | 12.75 | 273 | 30.18 | 0.3375 |
| ALLIANCE | 246.9 | 125.1 | 4/0 | 6/1 | 7/4.77 | 14.31 | 345 | 38.05 | 0.3306 |
| BUTTE | 312.8 | 158.6 | 266.8 | 26/7 | 19/3.26 | 16.3 | 437 | 48.76 | 0.3196 |
| CANTON | 394.5 | 199.9 | 366.4 | 26/7 | 19/3.66 | 18.3 | 551 | 58.91 | 0.3124 |
| CAIRO | 465.4 | 235.8 | 397.5 | 26/7 | 19/3.98 | 19.88 | 650 | 69.48 | 0.3071 |
| DARIEN | 559.5 | 283.5 | 477 | 26/7 | 19/4.36 | 21.79 | 781 | 83.52 | 0.3014 |
| ELGIN | 652.4 | 330.6 | 556.5 | 26/7 | 19/4.71 | 23.54 | 911 | 97.42 | 0.2966 |
| FLINT | 740.8 | 375.3 | 636 | 26/7 | 37/3.59 | 25.16 | 1035 | 108.21 | 0.2917 |
| GREELY | 927.2 | 469.8 | 795 | 26/7 | 37/4.02 | 28.14 | 1295 | 135.47 | 0.2846 |
| Area | Stranding and wire diameter | Approx. overall diameter | Weight | Nominal Breaking Load | MAX .DC resistance at 20ºC | |
| Nominal | Actual | |||||
| AWGorMCM | (mm2) | (mm) | (mm) | (kg/km) | (kN) | (ohm/km) |
| 6 | 13.30 | 7/1.554 | 4.67 | 37 | 4.22 | 2.5199 |
| 4 | 21.15 | 1/1.961 | 5.89 | 58 | 6.71 | 1.5824 |
| 2 | 33.63 | 7/2.474 | 7.42 | 93 | 10.68 | 0.9942 |
| 1/0 | 53.48 | 7/3.119 | 9.36 | 148 | 16.97 | 0.6256 |
| 2/0 | 67.42 | 7/3.503 | 10.51 | 186 | 20.52 | 0.4959 |
| 3/0 | 85.03 | 7/3.932 | 11.8 | 234 | 25.86 | 0.3936 |
| 4/0 | 107.23 | 7/4.417 | 13.26 | 296 | 32.63 | 0.3119 |
| 250 | 126.66 | 19/2.913 | 14.57 | 349 | 38.93 | 0.2642 |
| 300 | 152.1 | 19/3.193 | 15.97 | 419 | 46.77 | 0.2199 |
| 350 | 177.35 | 19/3.447 | 17.24 | 489 | 52.25 | 0.1887 |
| 400 | 202.71 | 19/3.686 | 18.43 | 559 | 59.74 | 0.1650 |
| 450 | 228 | 19/3.909 | 19.55 | 629 | 67.19 | 0.1467 |
| 500 | 253.35 | 19/4.120 | 20.60 | 698 | 74.64 | 0.1321 |
| 550 | 278.60 | 37/3.096 | 21.67 | 768 | 83.80 | 0.1202 |
| 600 | 303.80 | 37/3.233 | 22.63 | 838 | 91.38 | 0.1102 |
| 650 | 329.25 | 37/3.366 | 23.56 | 908 | 97.94 | 0.1016 |
| 700 | 354.55 | 37/3.493 | 24.45 | 978 | 102.20 | 0.0944 |
| 750 | 380.20 | 37/3.617 | 25.32 | 1049 | 109.60 | 0.0880 |
| 800 | 405.15 | 37/3.734 | 26.14 | 1117 | 116.80 | 0.0826 |
| 900 | 456.16 | 37/3.962 | 27.73 | 1258 | 131.50 | 0.0733 |
| 1000 | 506.71 | 37/4.176 | 29.23 | 1399 | 146.10 | 0.0660 |
| 1100 | 557 | 61/3.41 | 30.69 | 1537 | 162.16 | 0.0589 |
| 1200 | 608 | 61/3.56 | 32.04 | 1677 | 176.75 | 0.0541 |
| 1300 | 659 | 61/3.71 | 33.39 | 1816 | 191.95 | 0.0498 |
| 1400 | 709 | 61/3.85 | 34.65 | 1955 | 206.72 | 0.0463 |
| 1500 | 760 | 61/3.98 | 35.82 | 2095 | 220.90 | 0.0441 |
| 1600 | 811 | 61/4.12 | 37.08 | 2236 | 235.57 | 0.0405 |
| 1700 | 861 | 61/4.24 | 38.16 | 2374 | 250.72 | 0.0382 |
| 1800 | 912 | 61/4.36 | 39.28 | 2514 | 265.11 | 0.03693 |
| 1900 | 963 | 91/3.67 | 40.37 | 2655 | 277.10 | 0.03411 |
| 2000 | 1013 | 91/3.76 | 41.4 | 2793 | 292.41 | 0.03243 |
| ALUMINIUM ALLOY CONDUCTOR BSEN50183 | |||||||
| Code Name | Calculated Area | No. Of Wires | Diameter | Weight | Rated Strength | MAX .DC resistance at 20ºC | |
| Wire | Cond. | ||||||
| mm2 | mm | mm | kg/km | Kn | ohm/km | ||
| Box | 18.8 | 7 | 1.85 | 5.55 | 51.4 | 5.55 | 1.748 |
| Acacia | 23.8 | 7 | 2.08 | 6.24 | 64.9 | 7.02 | 1.3828 |
| Almond | 30.1 | 7 | 2.34 | 7.02 | 82.2 | 8.88 | 1.0926 |
| Cedar | 35.5 | 7 | 2.54 | 7.62 | 96.8 | 10.46 | 0.9273 |
| Deodar | 42.2 | 7 | 2.77 | 8.31 | 115.2 | 12.44 | 0.7797 |
| Fir | 47.8 | 7 | 2.95 | 8.85 | 130.6 | 14.11 | 0.6875 |
| Hazel | 59.9 | 7 | 3.3 | 9.9 | 163.4 | 17.66 | 0.5494 |
| Pine | 71.6 | 7 | 3.61 | 10.8 | 195.6 | 21.14 | 0.4591 |
| Holly | 84.1 | 7 | 3.91 | 11.7 | 229.5 | 24.79 | 0.3913 |
| Willow | 89.7 | 7 | 4.04 | 12.1 | 245 | 26.47 | 0.3665 |
| Oak | 118.9 | 7 | 4.65 | 14 | 324.5 | 35.07 | 0.2767 |
| Mulberry | 150.9 | 19 | 3.18 | 15.9 | 414.3 | 44.52 | 0.2192 |
| Ash | 180.7 | 19 | 3.48 | 17.4 | 496.1 | 53.31 | 0.183 |
| Elm | 211 | 19 | 3.76 | 18.8 | 579.2 | 62.24 | 0.1568 |
| Poplar | 239.4 | 37 | 2.87 | 20.1 | 659.4 | 70.61 | 0.1387 |
| Sycamore | 303.2 | 37 | 3.23 | 22.6 | 835.2 | 89.4 | 0.1095 |
| Upas | 362.1 | 37 | 3.53 | 24.7 | 997.5 | 106.82 | 0.0917 |
| Yew | 479 | 37 | 4.06 | 28.4 | 1319.6 | 141.31 | 0.0693 |
| Totara | 498.1 | 37 | 4.14 | 29 | 1372.1 | 146.93 | 0.0666 |
| Rubus | 586.9 | 61 | 3.5 | 31.5 | 1622 | 173.13 | 0.0567 |
| Sorbus | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
| Araucaria | 821.1 | 61 | 4.14 | 37.3 | 2269.4 | 242.24 | 0.0406 |
| Redwood | 996.2 | 61 | 4.56 | 41 | 2753.2 | 293.88 | 0.0334 |
| ALUMINIUM ALLOY CONDUCTOR BS 3242 | |||||||
| Code Name | Calculated Area | No. Of Wires | Diameter | Weight | Rated Strength | MAX .DC resistance at 20ºC | |
| Wire | Cond. | ||||||
| mm2 | mm | mm | kg/km | Kn | ohm/km | ||
| Box | 15 | 7/1.85 | 18.82 | 5.55 | 51 | 537 | 1.7495 |
| Acacia | 20 | 7/2.08 | 23.79 | 6.24 | 65 | 680 | 1.384 |
| Almond | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 861 | 1.0934 |
| Cedar | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 1014 | 0.9281 |
| – | 35 | 7/2.77 | 42.18 | 8.31 | 115 | 1205 | 0.7804 |
| Fir | 40 | 7/2.95 | 47.87 | 8.85 | 131 | 1367 | 0.688 |
| Hazel | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 1711 | 0.5498 |
| Pine | 60 | 7/3.61 | 71.65 | 10.83 | 196 | 2048 | 0.4594 |
| – | 70 | 7/3.91 | 84.05 | 11.73 | 230 | 2402 | 0.3917 |
| Willow | 75 | 7/4.04 | 89.73 | 12.12 | 245 | 2565 | 0.3669 |
| – | 80 | 7/4.19 | 96.52 | 12.57 | 264 | 2758 | 0.3441 |
| – | 90 | 7/4.44 | 108 | 13.32 | 298 | 3112 | 0.3023 |
| Oak | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 3398 | 0.2769 |
| – | 100 | 19/2.82 | 118.7 | 14.1 | 326 | 3393 | 0.2787 |
| Mulbery | 125 | 19/3.18 | 150.9 | 15.9 | 415 | 4312 | 0.2192 |
| Ash | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 5164 | 0.1831 |
| Elm | 175 | 19/3.76 | 211 | 18.8 | 580 | 6030 | 0.1568 |
| Poplar | 200 | 37/2.87 | 239.4 | 20.09 | 659 | 8841 | 0.1385 |
| – | 225 | 37/3.05 | 270.3 | 21.35 | 744 | 7724 | 0.1227 |
| Sycamore | 250 | 37/3.22 | 303.2 | 22.54 | 835 | 8664 | 0.1093 |
| Upas | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 10350 | 0.09156 |
| Walnut | 350 | 37/3.81 | 421.8 | 26.67 | 1162 | 12053 | 0.0786 |
| Yew | 400 | 37/4.06 | 479 | 28.42 | 1319 | 13685 | 0.06921 |
| Totara | 425 | 37/4.14 | 498.1 | 28.98 | 1372 | 14233 | 0.06656 |
| Rubus | 500 | 61/3.50 | 586.9 | 31.5 | 1620 | 16771 | 0.05662 |
| Araucaria | 700 | 61/4.14 | 821.1 | 37.26 | 2266 | 23450 | 0.04047 |
4.FAQ
(1).When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please
call us or tell us in your e-mail so that we will regard your inquiry priority.
(2).How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freight
charge should be paid.
(3).How long can I expect to get the sample?
After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7
days. The samples will be sent to you via express and arrive in 3~5 days. You can use your own express account orprepay us if you do not have an account.
(4).What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order.The best record we keep is
delivering 10 kilometers cable within a week. Generally speaking, we suggest that you start inquiry two months
before the date you would like to get the products at your country.
We are China AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAAC Conductor Products
Aluminum 1350-H19 Wires Concentrically Stranded AAC Conductors Manufactured to IEC61089
Overhead Application and Aluminum Conductor Material ACSR /AAC/AAAC Conductor Products
ASTM BS IEC Standard Aluminum Conductor Power Cable AAAC Conductor
Overhead All Aluminum Alloy Conductor Alliance AAAC Conductor
Bare Conductor AAAC Aluminum Alloy Stranded Conductor ASTM AWG
AAAC Manufacturer (All Aluminium Alloy Conductors) for Overhead Transmission Line
Popular Aluminum Alloy 6201-T81 Conductor Products
AAAC AS 1531 Aluminium Alloy 6201 Ruby
AAAC Conductor ASTM B399 Aluminium Alloy 6201-T81 25mm2
Overhead ACSR, AAC, AAAC, Acss/Tw, Accc, Aacsr, Acar, Opgw Bare Conductor
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 4/0AWG
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Elm
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Oak
Popular Aluminum Alloy Conductor AAAC Products
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Oak
AAAC AS 1531 Aluminium Alloy 6201 Sapphire
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 Cairo
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 Canton
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Cedar
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Hazel
Popular huatongcable Products
SAE1006cr SAE1008cr Low Carbon Steel Wire in Coils
PVC Insulated & Sheathed Electric Power Cable (VV)
L Mask 3ply Disposable Face Mask
Overhead Quadruplex Service Drop Station Aerial Bundled Cable for Transmission Line
Bare Aluminium Annealed Binding Wire Tie Wire Price
Overhead Triplex Service Drop Nasa Aerial Bundled Cable for Transmission Line
Tags: AAAC Conductor, Aluminum Alloy 6201-T81 Conductor, Aluminum Alloy Conductor AAAC, huatongcable