Low Voltage XLPE Insulated PVC Sheathed Sta Aluminum Power Cable
Low Voltage XLPE Insulated PVC Sheathed Sta Aluminum Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Tel: 0086 532 85611663 Phone 0086 15192706553
__________________________________________________________________________________________
Product Description
Low Voltage Cable
1. Application
The cable is used in electric transmission and distribution system operating at AC rated voltage up to and including 1.8/3 KV
2. Operating Characteristic
1) The rated voltage U0/U of cable is 0.6/1KV.
2) The long time allowable working temperature of conductor is 70 °C FOR cable with PVC insulation, 90 °C for cable with XLPE insulation.
3) The cable laying temperature is not less than 0°C, and the allowable bending radius of a cable is not less 20 times than cable overall diameter for single core unarmored cable, 15 times of that for single core armored, 12 times of that for 3 cores armored cable.
2. Construction
3. Cores and Nominal Cross Section Area:
| Rated voltage 0.6/1kV Single core Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 0.7 | 5.6 | 45 | 35 | ||||||
| 2.5 | 0.7 | 0.7 | 6.0 | 56 | 41 | ||||||
| 4 | 0.7 | 0.7 | 6.5 | 74 | 49 | ||||||
| 6 | 0.7 | 0.7 | 7.0 | 95 | 59 | ||||||
| 10 | 0.7 | 0.7 | 8.2 | 139 | 79 | ||||||
| 16 | 0.7 | 0.7 | 9.1 | 197 | 102 | ||||||
| 25 | 0.9 | 0.9 | 10.6 | 293 | 143 | 0.9 | 0.2 | 1.8 | 14.0 | 451 | 301 |
| 35 | 0.9 | 0.9 | 11.6 | 386 | 178 | 0.9 | 0.2 | 1.8 | 15.0 | 558 | 349 |
| 50 | 1.0 | 1.0 | 13.0 | 507 | 225 | 0.9 | 0.2 | 1.8 | 16.4 | 698 | 416 |
| 70 | 1.1 | 1.1 | 14.9 | 708 | 300 | 0.9 | 0.2 | 1.8 | 18.3 | 926 | 519 |
| 95 | 1.1 | 1.1 | 16.8 | 959 | 394 | 0.9 | 0.2 | 1.8 | 20.0 | 1194 | 628 |
| 120 | 1.2 | 1.2 | 18.5 | 1193 | 479 | 0.9 | 0.2 | 1.8 | 21.7 | 1450 | 737 |
| 150 | 1.4 | 1.4 | 20.6 | 1470 | 590 | 0.9 | 0.2 | 1.8 | 23.6 | 1745 | 865 |
| 185 | 1.6 | 1.6 | 22.8 | 1831 | 730 | 0.9 | 0.2 | 1.8 | 25.6 | 2122 | 1021 |
| 240 | 1.7 | 1.7 | 25.7 | 2380 | 933 | 0.9 | 0.2 | 1.9 | 28.5 | 2706 | 1259 |
| 300 | 1.8 | 1.8 | 28.3 | 2960 | 1144 | 0.9 | 0.2 | 1.9 | 30.9 | 3304 | 1488 |
| 400 | 2.0 | 2.0 | 31.3 | 3755 | 1433 | 1.2 | 0.5 | 2.1 | 35.9 | 4494 | 2173 |
| Rated voltage 0.6/1kV Two cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.2 | 114 | 96 | 0.9 | 0.2 | 1.8 | 12.8 | 232 | 214 |
| 2.5 | 0.7 | 1.8 | 11.0 | 141 | 111 | 0.9 | 0.2 | 1.8 | 13.6 | 269 | 238 |
| 4 | 0.7 | 1.8 | 12.0 | 181 | 132 | 0.9 | 0.2 | 1.8 | 14.6 | 320 | 271 |
| 6 | 0.7 | 1.8 | 13.0 | 228 | 156 | 0.9 | 0.2 | 1.8 | 15.6 | 379 | 306 |
| 10 | 0.7 | 1.8 | 15.4 | 331 | 211 | 0.9 | 0.2 | 1.8 | 18.0 | 509 | 389 |
| 16 | 0.7 | 1.8 | 17.2 | 458 | 268 | 0.9 | 0.2 | 1.8 | 19.8 | 657 | 467 |
| 25 | 0.9 | 1.8 | 20.2 | 672 | 371 | 0.9 | 0.2 | 1.8 | 22.8 | 905 | 604 |
| 35 | 0.9 | 1.8 | 22.2 | 873 | 455 | 0.9 | 0.2 | 1.8 | 24.8 | 1130 | 712 |
| 50 | 1.0 | 1.8 | 25.0 | 1140 | 574 | 0.9 | 0.2 | 1.8 | 27.6 | 1428 | 863 |
| 70 | 1.1 | 1.9 | 29.0 | 1592 | 775 | 1.2 | 0.2 | 2.0 | 33.6 | 2262 | 1445 |
| 95 | 1.1 | 2.0 | 32.6 | 2134 | 1000 | 1.2 | 0.2 | 2.2 | 37.4 | 2899 | 1765 |
| 120 | 1.2 | 2.1 | 36.2 | 2660 | 1229 | 1.2 | 0.5 | 2.3 | 41.0 | 3504 | 2074 |
| 150 | 1.4 | 2.3 | 40.4 | 3287 | 1522 | 1.2 | 0.5 | 2.4 | 45.0 | 4202 | 2437 |
| 185 | 1.6 | 2.4 | 44.6 | 4073 | 1864 | 1.2 | 0.5 | 2.5 | 49.2 | 5079 | 2870 |
| 240 | 1.7 | 2.6 | 50.4 | 5287 | 2384 | 1.4 | 0.5 | 2.8 | 55.6 | 6457 | 3554 |
| 300 | 1.8 | 2.8 | 55.6 | 6567 | 2925 | 1.4 | 0.5 | 2.9 | 60.6 | 7822 | 4180 |
| 400 | 2.0 | 2.9 | 61.4 | 8279 | 3622 | 1.4 | 0.5 | 3.1 | 66.6 | 9692 | 5034 |
| Rated voltage 0.6/1kV Three cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.7 | 135 | 107 | 0.9 | 0.2 | 1.8 | 13.3 | 259 | 231 |
| 2.5 | 0.7 | 1.8 | 11.5 | 171 | 125 | 0.9 | 0.2 | 1.8 | 14.1 | 304 | 259 |
| 4 | 0.7 | 1.8 | 12.6 | 225 | 152 | 0.9 | 0.2 | 1.8 | 15.2 | 370 | 297 |
| 6 | 0.7 | 1.8 | 13.7 | 291 | 182 | 0.9 | 0.2 | 1.8 | 16.3 | 449 | 341 |
| 10 | 0.7 | 1.8 | 16.3 | 429 | 250 | 0.9 | 0.2 | 1.8 | 18.9 | 618 | 438 |
| 16 | 0.7 | 1.8 | 18.2 | 609 | 324 | 0.9 | 0.2 | 1.8 | 20.8 | 820 | 534 |
| 25 | 0.9 | 1.8 | 21.4 | 907 | 455 | 0.9 | 0.2 | 1.8 | 24.0 | 1154 | 703 |
| 35 | 0.9 | 1.8 | 23.6 | 1194 | 567 | 0.9 | 0.2 | 1.8 | 26.2 | 1466 | 840 |
| 50 | 1.0 | 1.8 | 26.6 | 1570 | 722 | 0.9 | 0.2 | 1.9 | 29.4 | 1891 | 1042 |
| 70 | 1.1 | 1.9 | 30.9 | 2208 | 983 | 1.2 | 0.2 | 2.1 | 35.7 | 2936 | 1711 |
| 95 | 1.1 | 2.1 | 35.0 | 2995 | 1294 | 1.2 | 0.5 | 2.2 | 39.6 | 3794 | 2093 |
| 120 | 1.2 | 2.2 | 38.8 | 3741 | 1595 | 1.2 | 0.5 | 2.4 | 43.6 | 4642 | 2496 |
| 150 | 1.4 | 2.3 | 43.1 | 4601 | 1953 | 1.2 | 0.5 | 2.5 | 47.9 | 5598 | 2950 |
| 185 | 1.6 | 2.5 | 47.8 | 5738 | 2425 | 1.4 | 0.5 | 2.7 | 53.0 | 6851 | 3538 |
| 240 | 1.7 | 2.7 | 54.0 | 7462 | 3107 | 1.4 | 0.5 | 2.9 | 59.2 | 8711 | 4356 |
| 300 | 1.8 | 2.9 | 59.6 | 9283 | 3820 | 1.4 | 0.5 | 3.1 | 64.8 | 10655 | 5192 |
| 400 | 2.0 | 3.1 | 66.0 | 11771 | 4786 | 1.4 | 0.5 | 3.3 | 71.2 | 13284 | 6299 |
| Rated voltage 0.6/1kV Four cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 11.4 | 160 | 123 | 0.9 | 0.2 | 1.8 | 14.0 | 292 | 255 |
| 2.5 | 0.7 | 1.8 | 12.4 | 207 | 147 | 0.9 | 0.2 | 1.8 | 15.0 | 351 | 290 |
| 4 | 0.7 | 1.8 | 13.6 | 277 | 179 | 0.9 | 0.2 | 1.8 | 16.2 | 434 | 337 |
| 6 | 0.7 | 1.8 | 14.8 | 362 | 217 | 0.9 | 0.2 | 1.8 | 17.4 | 533 | 389 |
| 10 | 0.7 | 1.8 | 17.7 | 542 | 302 | 0.9 | 0.2 | 1.8 | 20.3 | 746 | 507 |
| 16 | 0.7 | 1.8 | 19.8 | 777 | 396 | 0.9 | 0.2 | 1.8 | 22.4 | 1005 | 625 |
| 25 | 0.9 | 1.8 | 23.5 | 1169 | 566 | 0.9 | 0.2 | 1.8 | 26.1 | 1440 | 838 |
| 35 | 0.9 | 1.8 | 25.9 | 1546 | 710 | 0.9 | 0.2 | 1.9 | 28.7 | 1858 | 1022 |
| 50 | 1.0 | 1.9 | 29.5 | 2054 | 923 | 1.2 | 0.2 | 2.1 | 34.3 | 2751 | 1620 |
| 70 | 1.1 | 2.1 | 34.4 | 2909 | 1275 | 1.2 | 0.2 | 2.2 | 39.0 | 3695 | 2061 |
| 95 | 1.1 | 2.2 | 38.8 | 3930 | 1661 | 1.2 | 0.5 | 2.4 | 43.6 | 4831 | 2563 |
| 120 | 1.2 | 2.3 | 43.1 | 4913 | 2051 | 1.2 | 0.5 | 2.5 | 47.9 | 5909 | 3048 |
| 150 | 1.4 | 2.5 | 48.0 | 6067 | 2537 | 1.4 | 0.5 | 2.7 | 53.2 | 7184 | 3654 |
| 185 | 1.6 | 2.7 | 53.3 | 7566 | 3148 | 1.4 | 0.5 | 2.8 | 58.3 | 8772 | 4355 |
| 240 | 1.7 | 2.9 | 60.2 | 9839 | 4033 | 1.4 | 0.5 | 3.1 | 65.4 | 11225 | 5419 |
| 300 | 1.8 | 3.1 | 66.4 | 12242 | 4957 | 1.4 | 0.5 | 3.3 | 71.6 | 13764 | 6479 |
| 400 | 2.0 | 3.3 | 73.5 | 15526 | 6212 | 1.4 | 0.5 | 3.5 | 78.7 | 17205 | 7891 |
| Rated voltage 0.6/1kV Five cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 12.2 | 186 | 140 | 0.9 | 0.2 | 1.8 | 14.8 | 328 | 281 |
| 2.5 | 0.7 | 1.8 | 13.3 | 244 | 168 | 0.9 | 0.2 | 1.8 | 15.9 | 398 | 322 |
| 4 | 0.7 | 1.8 | 14.6 | 329 | 207 | 0.9 | 0.2 | 1.8 | 17.2 | 498 | 376 |
| 6 | 0.7 | 1.8 | 16.0 | 434 | 254 | 0.9 | 0.2 | 1.8 | 18.6 | 619 | 439 |
| 10 | 0.7 | 1.8 | 19.2 | 655 | 356 | 0.9 | 0.2 | 1.8 | 21.8 | 877 | 578 |
| 16 | 0.7 | 1.8 | 21.7 | 948 | 472 | 0.9 | 0.2 | 1.8 | 24.3 | 1199 | 723 |
| 25 | 0.9 | 1.8 | 25.7 | 1432 | 679 | 0.9 | 0.2 | 1.9 | 28.5 | 1742 | 989 |
| 35 | 0.9 | 1.9 | 28.6 | 1914 | 869 | 0.9 | 0.2 | 2.0 | 31.4 | 2257 | 1213 |
| 50 | 1.0 | 2.0 | 32.6 | 2546 | 1131 | 1.2 | 0.2 | 2.2 | 37.4 | 3310 | 1896 |
| 70 | 1.1 | 2.2 | 38.1 | 3607 | 1565 | 1.2 | 0.5 | 2.3 | 42.7 | 4473 | 2431 |
| 95 | 1.1 | 2.3 | 42.9 | 4876 | 2040 | 1.2 | 0.5 | 2.5 | 47.7 | 5868 | 3032 |
| 120 | 1.2 | 2.5 | 47.9 | 6120 | 2543 | 1.4 | 0.5 | 2.7 | 53.1 | 7235 | 3658 |
| 150 | 1.4 | 2.7 | 53.4 | 7556 | 3143 | 1.4 | 0.5 | 2.8 | 58.4 | 8765 | 4352 |
| 185 | 1.6 | 2.9 | 59.2 | 9419 | 3897 | 1.4 | 0.5 | 3.0 | 64.2 | 10752 | 5230 |
| 240 | 1.7 | 3.1 | 66.9 | 12249 | 4992 | 1.4 | 0.5 | 3.3 | 72.1 | 13783 | 6525 |
| 300 | 1.8 | 3.4 | 74.0 | 15273 | 6168 | 1.4 | 0.5 | 3.5 | 79.0 | 16925 | 7820 |
| 400 | 2.0 | 3.6 | 82.0 | 19369 | 7726 | 1.4 | 0.5 | 3.8 | 88.4 | 22080 | 10437 |
| Rated voltage 0.6/1kV 3+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 12.4 | 198 | 143 | 0.9 | 0.2 | 1.8 | 15.0 | 342 | 287 |
| 4/2.5 | 0.7/0.7 | 1.8 | 13.6 | 262 | 174 | 0.9 | 0.2 | 1.8 | 16.2 | 420 | 332 |
| 6/4 | 0.7/0.7 | 1.8 | 14.8 | 343 | 211 | 0.9 | 0.2 | 1.8 | 17.4 | 515 | 382 |
| 10/6 | 0.7/0.7 | 1.8 | 17.7 | 506 | 290 | 0.9 | 0.2 | 1.8 | 20.3 | 710 | 495 |
| 16/10 | 0.7/0.7 | 1.8 | 19.8 | 724 | 378 | 0.9 | 0.2 | 1.8 | 22.4 | 953 | 607 |
| 25/16 | 0.9/0.7 | 1.8 | 23.5 | 1083 | 536 | 0.9 | 0.2 | 1.8 | 26.1 | 1354 | 807 |
| 35/16 | 0.9/0.7 | 1.8 | 25.3 | 1371 | 649 | 0.9 | 0.2 | 1.9 | 28.1 | 1676 | 954 |
| 50/25 | 1.0/0.9 | 1.9 | 28.8 | 1852 | 853 | 0.9 | 0.2 | 2.0 | 31.6 | 2198 | 1199 |
| 70/35 | 1.1/0.9 | 2.0 | 33.5 | 2593 | 1158 | 1.2 | 0.2 | 2.2 | 38.3 | 3378 | 1944 |
| 95/50 | 1.1/1.0 | 2.2 | 37.9 | 3506 | 1522 | 1.2 | 0.5 | 2.3 | 42.5 | 4367 | 2383 |
| 120/70 | 1.2/1.1 | 2.3 | 42.1 | 4452 | 1897 | 1.2 | 0.5 | 2.5 | 46.9 | 5425 | 2871 |
| 150/70 | 1.4/1.1 | 2.5 | 46.9 | 5361 | 2305 | 1.4 | 0.5 | 2.6 | 51.9 | 6430 | 3373 |
| 185/95 | 1.6/1.1 | 2.6 | 51.8 | 6732 | 2851 | 1.4 | 0.5 | 2.8 | 57.0 | 7933 | 4053 |
| 240/120 | 1.7/1.2 | 2.9 | 58.8 | 8740 | 3670 | 1.4 | 0.5 | 3.0 | 63.8 | 10065 | 4995 |
| 300/150 | 1.8/1.4 | 3.1 | 64.8 | 10850 | 4504 | 1.4 | 0.5 | 3.2 | 69.8 | 12304 | 5958 |
| 400/185 | 2.0/1.6 | 3.3 | 71.8 | 13718 | 5628 | 1.4 | 0.5 | 3.5 | 77.0 | 15359 | 7269 |
| Rated voltage 0.6/1kV 3+2 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 225 | 161 | 0.9 | 0.2 | 1.8 | 15.9 | 379 | 315 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 300 | 197 | 0.9 | 0.2 | 1.8 | 17.2 | 469 | 366 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 398 | 241 | 0.9 | 0.2 | 1.8 | 18.6 | 583 | 426 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 584 | 332 | 0.9 | 0.2 | 1.8 | 21.8 | 806 | 554 |
| 16/10 | 0.7/0.7 | 1.8 | 21.8 | 844 | 439 | 0.9 | 0.2 | 1.8 | 24.4 | 1096 | 691 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1262 | 620 | 0.9 | 0.2 | 1.9 | 28.5 | 1572 | 930 |
| 35/16 | 0.9/0.7 | 1.8 | 27.5 | 1557 | 740 | 0.9 | 0.2 | 1.9 | 30.3 | 1889 | 1072 |
| 50/25 | 1.0/0.9 | 2.0 | 31.6 | 2148 | 998 | 1.2 | 0.2 | 2.1 | 36.2 | 2873 | 1724 |
| 70/35 | 1.1/0.9 | 2.1 | 36.7 | 2993 | 1350 | 1.2 | 0.2 | 2.3 | 41.5 | 3849 | 2206 |
| 95/50 | 1.1/1.0 | 2.3 | 41.5 | 4037 | 1770 | 1.2 | 0.5 | 2.4 | 46.1 | 4976 | 2709 |
| 120/70 | 1.2/1.1 | 2.4 | 46.1 | 5186 | 2223 | 1.4 | 0.5 | 2.6 | 51.3 | 6262 | 3299 |
| 150/70 | 1.4/1.1 | 2.6 | 51.5 | 6133 | 2669 | 1.4 | 0.5 | 2.8 | 56.7 | 7328 | 3863 |
| 185/95 | 1.6/1.1 | 2.8 | 57.1 | 7789 | 3341 | 1.4 | 0.5 | 3.0 | 62.3 | 9106 | 4658 |
| 240/120 | 1.7/1.2 | 3.0 | 64.5 | 10040 | 4255 | 1.4 | 0.5 | 3.2 | 69.7 | 11521 | 5736 |
| 300/150 | 1.8/1.4 | 3.3 | 71.3 | 12479 | 5251 | 1.4 | 0.5 | 3.4 | 76.3 | 14074 | 6845 |
| 400/185 | 2.0/1.6 | 3.5 | 79.0 | 15742 | 6547 | 1.4 | 0.5 | 3.7 | 85.4 | 18358 | 9163 |
| Rated voltage 0.6/1kV 4+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 235 | 165 | 0.9 | 0.2 | 1.8 | 15.9 | 389 | 319 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 315 | 202 | 0.9 | 0.2 | 1.8 | 17.2 | 483 | 371 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 416 | 247 | 0.9 | 0.2 | 1.8 | 18.6 | 601 | 432 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 620 | 344 | 0.9 | 0.2 | 1.8 | 21.8 | 842 | 566 |
| 16/10 | 0.7/0.7 | 1.8 | 21.7 | 896 | 455 | 0.9 | 0.2 | 1.8 | 24.3 | 1146 | 706 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1347 | 650 | 0.9 | 0.2 | 1.9 | 28.5 | 1657 | 960 |
| 35/16 | 0.9/0.7 | 1.9 | 28.2 | 1742 | 811 | 0.9 | 0.2 | 1.9 | 30.8 | 2067 | 1136 |
| 50/25 | 1.0/0.9 | 2.0 | 32.1 | 2347 | 1065 | 1.2 | 0.2 | 2.1 | 36.7 | 3083 | 1802 |
| 70/35 | 1.1/0.9 | 2.2 | 37.5 | 3308 | 1466 | 1.2 | 0.5 | 2.3 | 42.1 | 4161 | 2318 |
| 95/50 | 1.1/1.0 | 2.3 | 42.2 | 4456 | 1905 | 1.2 | 0.5 | 2.5 | 47.0 | 5432 | 2881 |
| 120/70 | 1.2/1.1 | 2.5 | 47.1 | 5663 | 2394 | 1.4 | 0.5 | 2.6 | 52.1 | 6736 | 3466 |
| 150/70 | 1.4/1.1 | 2.7 | 52.6 | 6857 | 2918 | 1.4 | 0.5 | 2.8 | 57.6 | 8048 | 4109 |
| 185/95 | 1.6/1.1 | 2.8 | 58.1 | 8591 | 3606 | 1.4 | 0.5 | 3.0 | 63.3 | 9931 | 4946 |
| 240/120 | 1.7/1.2 | 3.1 | 65.8 | 11159 | 4638 | 1.4 | 0.5 | 3.3 | 71.0 | 12668 | 6146 |
| 300/150 | 1.8/1.4 | 3.3 | 72.6 | 13860 | 5693 | 1.4 | 0.5 | 3.5 | 77.8 | 15518 | 7351 |
| 400/185 | 2.0/1.6 | 3.6 | 80.6 | 17573 | 7154 | 1.4 | 0.5 | 3.8 | 87.0 | 20238 | 9819 |
4. Our Factory
5. Exhibition/ Customer Visit
6. Our Honor
7. Contact Details
Jessica Wang | Taifeng Cable Co., Ltd.
Add.: Heda Center, No.177 Tailiu Road, Shibei District, Qingdao, China
Factory Add.: No.1 Taifeng Road, Dacaozhuang Administrative Zone, Xingtai City, Hebei Province, China
Tel: 0086 532 85611663
Phone: 0086 15192706553
Website: taifengcable.en.
We are China Low Voltage XLPE Insulated PVC Sheathed Sta Aluminum Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Low Voltage Cable Products
Swa/Sta LV (Low Voltage) Power Cable
Copper Conductor XLPE Insulation PVC Sheath Aluminum Electrical Power Cable
0.6/1 kV 4X240 Cu XLPE PVC Double Steel Tape Armour Direct Burial Power Cable
Building Cable Size 2*0.5sqmm 300/500V 450/750V PVC/XLPE Insulated Electrical Cable Wire
Electric Cable Low Voltage (LV) PVC/XLPE Insulated Armoured
Popular PVC Sheathed Cable Products
Low Smoke Halogen Free Mica Tape XLPE Insulated Copper Cable
Railway Train Station XLPE Insulated PVC Sheathed Copper Electric Wire
Taifeng Cable Underground XLPE Insulated PVC Sheathed Swa Copper Electrical Wire
Copper XLPE Insulated LSZH Flame Retardant Armored Power Cable
Low Voltage XLPE Insulated PVC Sheathed Aluminum Conductor Electric Cable
Metallic Shielded XLPE Insulated PVC Sheath Power Cable
Popular taifengcable Products
1/2/3/4/5 Core PVC XLPE Insulated Armoured Electric Wire Power Cable
0.6/1kv XLPE Insulation PVC Sheath Power Cable 4c 95mm2 IEC60502
Copper Conductor PVC Insulated 1.5 2.5 6mm2 Home Use House Building Wire
Three Cores Copper Conductor Steel Armoured Sta/Swa XLPE Insulated PVC Cable
4mm2 Electrical DC PV Solar Cable Photovoltaic Wire PV Cables PV1-F
Popular XLPE Insulated Cable Products
Top Quality LV Cable 0.6/1kv Cu/XLPE/Swa/PVC Power Cable
NFC Standard ABC Cable AAAC Neutral Conductor
11kv 3c 185mm2 240mm2 300mm2 Al Conductor XLPE Insulated Power Cable
Overhead Aluminum Cabl XLPE Insulated Aluminum Conductor Aerial Bundle Cable
Tags: Low Voltage Cable, PVC Sheathed Cable, taifengcable, XLPE Insulated Cable