Low Voltage XLPE Insulated PVC Sheathed Steel Tape Armoured Aluminum Electrical Cable
Low Voltage XLPE Insulated PVC Sheathed Steel Tape Armoured Aluminum Electrical Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Low Voltage Cable
1. Application
The cable is used in electric transmission and distribution system operating at AC rated voltage up to and including 1.8/3 KV
2. Operating Characteristic
1) The rated voltage U0/U of cable is 0.6/1KV.
2) The long time allowable working temperature of conductor is 70 °C FOR cable with PVC insulation, 90 °C for cable with XLPE insulation.
3) The cable laying temperature is not less than 0°C, and the allowable bending radius of a cable is not less 20 times than cable overall diameter for single core unarmored cable, 15 times of that for single core armored, 12 times of that for 3 cores armored cable.
2. Construction
3. Cores and Nominal Cross Section Area:
| Rated voltage 0.6/1kV Single core Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 0.7 | 5.6 | 45 | 35 | ||||||
| 2.5 | 0.7 | 0.7 | 6.0 | 56 | 41 | ||||||
| 4 | 0.7 | 0.7 | 6.5 | 74 | 49 | ||||||
| 6 | 0.7 | 0.7 | 7.0 | 95 | 59 | ||||||
| 10 | 0.7 | 0.7 | 8.2 | 139 | 79 | ||||||
| 16 | 0.7 | 0.7 | 9.1 | 197 | 102 | ||||||
| 25 | 0.9 | 0.9 | 10.6 | 293 | 143 | 0.9 | 0.2 | 1.8 | 14.0 | 451 | 301 |
| 35 | 0.9 | 0.9 | 11.6 | 386 | 178 | 0.9 | 0.2 | 1.8 | 15.0 | 558 | 349 |
| 50 | 1.0 | 1.0 | 13.0 | 507 | 225 | 0.9 | 0.2 | 1.8 | 16.4 | 698 | 416 |
| 70 | 1.1 | 1.1 | 14.9 | 708 | 300 | 0.9 | 0.2 | 1.8 | 18.3 | 926 | 519 |
| 95 | 1.1 | 1.1 | 16.8 | 959 | 394 | 0.9 | 0.2 | 1.8 | 20.0 | 1194 | 628 |
| 120 | 1.2 | 1.2 | 18.5 | 1193 | 479 | 0.9 | 0.2 | 1.8 | 21.7 | 1450 | 737 |
| 150 | 1.4 | 1.4 | 20.6 | 1470 | 590 | 0.9 | 0.2 | 1.8 | 23.6 | 1745 | 865 |
| 185 | 1.6 | 1.6 | 22.8 | 1831 | 730 | 0.9 | 0.2 | 1.8 | 25.6 | 2122 | 1021 |
| 240 | 1.7 | 1.7 | 25.7 | 2380 | 933 | 0.9 | 0.2 | 1.9 | 28.5 | 2706 | 1259 |
| 300 | 1.8 | 1.8 | 28.3 | 2960 | 1144 | 0.9 | 0.2 | 1.9 | 30.9 | 3304 | 1488 |
| 400 | 2.0 | 2.0 | 31.3 | 3755 | 1433 | 1.2 | 0.5 | 2.1 | 35.9 | 4494 | 2173 |
| Rated voltage 0.6/1kV Two cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.2 | 114 | 96 | 0.9 | 0.2 | 1.8 | 12.8 | 232 | 214 |
| 2.5 | 0.7 | 1.8 | 11.0 | 141 | 111 | 0.9 | 0.2 | 1.8 | 13.6 | 269 | 238 |
| 4 | 0.7 | 1.8 | 12.0 | 181 | 132 | 0.9 | 0.2 | 1.8 | 14.6 | 320 | 271 |
| 6 | 0.7 | 1.8 | 13.0 | 228 | 156 | 0.9 | 0.2 | 1.8 | 15.6 | 379 | 306 |
| 10 | 0.7 | 1.8 | 15.4 | 331 | 211 | 0.9 | 0.2 | 1.8 | 18.0 | 509 | 389 |
| 16 | 0.7 | 1.8 | 17.2 | 458 | 268 | 0.9 | 0.2 | 1.8 | 19.8 | 657 | 467 |
| 25 | 0.9 | 1.8 | 20.2 | 672 | 371 | 0.9 | 0.2 | 1.8 | 22.8 | 905 | 604 |
| 35 | 0.9 | 1.8 | 22.2 | 873 | 455 | 0.9 | 0.2 | 1.8 | 24.8 | 1130 | 712 |
| 50 | 1.0 | 1.8 | 25.0 | 1140 | 574 | 0.9 | 0.2 | 1.8 | 27.6 | 1428 | 863 |
| 70 | 1.1 | 1.9 | 29.0 | 1592 | 775 | 1.2 | 0.2 | 2.0 | 33.6 | 2262 | 1445 |
| 95 | 1.1 | 2.0 | 32.6 | 2134 | 1000 | 1.2 | 0.2 | 2.2 | 37.4 | 2899 | 1765 |
| 120 | 1.2 | 2.1 | 36.2 | 2660 | 1229 | 1.2 | 0.5 | 2.3 | 41.0 | 3504 | 2074 |
| 150 | 1.4 | 2.3 | 40.4 | 3287 | 1522 | 1.2 | 0.5 | 2.4 | 45.0 | 4202 | 2437 |
| 185 | 1.6 | 2.4 | 44.6 | 4073 | 1864 | 1.2 | 0.5 | 2.5 | 49.2 | 5079 | 2870 |
| 240 | 1.7 | 2.6 | 50.4 | 5287 | 2384 | 1.4 | 0.5 | 2.8 | 55.6 | 6457 | 3554 |
| 300 | 1.8 | 2.8 | 55.6 | 6567 | 2925 | 1.4 | 0.5 | 2.9 | 60.6 | 7822 | 4180 |
| 400 | 2.0 | 2.9 | 61.4 | 8279 | 3622 | 1.4 | 0.5 | 3.1 | 66.6 | 9692 | 5034 |
| Rated voltage 0.6/1kV Three cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.7 | 135 | 107 | 0.9 | 0.2 | 1.8 | 13.3 | 259 | 231 |
| 2.5 | 0.7 | 1.8 | 11.5 | 171 | 125 | 0.9 | 0.2 | 1.8 | 14.1 | 304 | 259 |
| 4 | 0.7 | 1.8 | 12.6 | 225 | 152 | 0.9 | 0.2 | 1.8 | 15.2 | 370 | 297 |
| 6 | 0.7 | 1.8 | 13.7 | 291 | 182 | 0.9 | 0.2 | 1.8 | 16.3 | 449 | 341 |
| 10 | 0.7 | 1.8 | 16.3 | 429 | 250 | 0.9 | 0.2 | 1.8 | 18.9 | 618 | 438 |
| 16 | 0.7 | 1.8 | 18.2 | 609 | 324 | 0.9 | 0.2 | 1.8 | 20.8 | 820 | 534 |
| 25 | 0.9 | 1.8 | 21.4 | 907 | 455 | 0.9 | 0.2 | 1.8 | 24.0 | 1154 | 703 |
| 35 | 0.9 | 1.8 | 23.6 | 1194 | 567 | 0.9 | 0.2 | 1.8 | 26.2 | 1466 | 840 |
| 50 | 1.0 | 1.8 | 26.6 | 1570 | 722 | 0.9 | 0.2 | 1.9 | 29.4 | 1891 | 1042 |
| 70 | 1.1 | 1.9 | 30.9 | 2208 | 983 | 1.2 | 0.2 | 2.1 | 35.7 | 2936 | 1711 |
| 95 | 1.1 | 2.1 | 35.0 | 2995 | 1294 | 1.2 | 0.5 | 2.2 | 39.6 | 3794 | 2093 |
| 120 | 1.2 | 2.2 | 38.8 | 3741 | 1595 | 1.2 | 0.5 | 2.4 | 43.6 | 4642 | 2496 |
| 150 | 1.4 | 2.3 | 43.1 | 4601 | 1953 | 1.2 | 0.5 | 2.5 | 47.9 | 5598 | 2950 |
| 185 | 1.6 | 2.5 | 47.8 | 5738 | 2425 | 1.4 | 0.5 | 2.7 | 53.0 | 6851 | 3538 |
| 240 | 1.7 | 2.7 | 54.0 | 7462 | 3107 | 1.4 | 0.5 | 2.9 | 59.2 | 8711 | 4356 |
| 300 | 1.8 | 2.9 | 59.6 | 9283 | 3820 | 1.4 | 0.5 | 3.1 | 64.8 | 10655 | 5192 |
| 400 | 2.0 | 3.1 | 66.0 | 11771 | 4786 | 1.4 | 0.5 | 3.3 | 71.2 | 13284 | 6299 |
| Rated voltage 0.6/1kV Four cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 11.4 | 160 | 123 | 0.9 | 0.2 | 1.8 | 14.0 | 292 | 255 |
| 2.5 | 0.7 | 1.8 | 12.4 | 207 | 147 | 0.9 | 0.2 | 1.8 | 15.0 | 351 | 290 |
| 4 | 0.7 | 1.8 | 13.6 | 277 | 179 | 0.9 | 0.2 | 1.8 | 16.2 | 434 | 337 |
| 6 | 0.7 | 1.8 | 14.8 | 362 | 217 | 0.9 | 0.2 | 1.8 | 17.4 | 533 | 389 |
| 10 | 0.7 | 1.8 | 17.7 | 542 | 302 | 0.9 | 0.2 | 1.8 | 20.3 | 746 | 507 |
| 16 | 0.7 | 1.8 | 19.8 | 777 | 396 | 0.9 | 0.2 | 1.8 | 22.4 | 1005 | 625 |
| 25 | 0.9 | 1.8 | 23.5 | 1169 | 566 | 0.9 | 0.2 | 1.8 | 26.1 | 1440 | 838 |
| 35 | 0.9 | 1.8 | 25.9 | 1546 | 710 | 0.9 | 0.2 | 1.9 | 28.7 | 1858 | 1022 |
| 50 | 1.0 | 1.9 | 29.5 | 2054 | 923 | 1.2 | 0.2 | 2.1 | 34.3 | 2751 | 1620 |
| 70 | 1.1 | 2.1 | 34.4 | 2909 | 1275 | 1.2 | 0.2 | 2.2 | 39.0 | 3695 | 2061 |
| 95 | 1.1 | 2.2 | 38.8 | 3930 | 1661 | 1.2 | 0.5 | 2.4 | 43.6 | 4831 | 2563 |
| 120 | 1.2 | 2.3 | 43.1 | 4913 | 2051 | 1.2 | 0.5 | 2.5 | 47.9 | 5909 | 3048 |
| 150 | 1.4 | 2.5 | 48.0 | 6067 | 2537 | 1.4 | 0.5 | 2.7 | 53.2 | 7184 | 3654 |
| 185 | 1.6 | 2.7 | 53.3 | 7566 | 3148 | 1.4 | 0.5 | 2.8 | 58.3 | 8772 | 4355 |
| 240 | 1.7 | 2.9 | 60.2 | 9839 | 4033 | 1.4 | 0.5 | 3.1 | 65.4 | 11225 | 5419 |
| 300 | 1.8 | 3.1 | 66.4 | 12242 | 4957 | 1.4 | 0.5 | 3.3 | 71.6 | 13764 | 6479 |
| 400 | 2.0 | 3.3 | 73.5 | 15526 | 6212 | 1.4 | 0.5 | 3.5 | 78.7 | 17205 | 7891 |
| Rated voltage 0.6/1kV Five cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 12.2 | 186 | 140 | 0.9 | 0.2 | 1.8 | 14.8 | 328 | 281 |
| 2.5 | 0.7 | 1.8 | 13.3 | 244 | 168 | 0.9 | 0.2 | 1.8 | 15.9 | 398 | 322 |
| 4 | 0.7 | 1.8 | 14.6 | 329 | 207 | 0.9 | 0.2 | 1.8 | 17.2 | 498 | 376 |
| 6 | 0.7 | 1.8 | 16.0 | 434 | 254 | 0.9 | 0.2 | 1.8 | 18.6 | 619 | 439 |
| 10 | 0.7 | 1.8 | 19.2 | 655 | 356 | 0.9 | 0.2 | 1.8 | 21.8 | 877 | 578 |
| 16 | 0.7 | 1.8 | 21.7 | 948 | 472 | 0.9 | 0.2 | 1.8 | 24.3 | 1199 | 723 |
| 25 | 0.9 | 1.8 | 25.7 | 1432 | 679 | 0.9 | 0.2 | 1.9 | 28.5 | 1742 | 989 |
| 35 | 0.9 | 1.9 | 28.6 | 1914 | 869 | 0.9 | 0.2 | 2.0 | 31.4 | 2257 | 1213 |
| 50 | 1.0 | 2.0 | 32.6 | 2546 | 1131 | 1.2 | 0.2 | 2.2 | 37.4 | 3310 | 1896 |
| 70 | 1.1 | 2.2 | 38.1 | 3607 | 1565 | 1.2 | 0.5 | 2.3 | 42.7 | 4473 | 2431 |
| 95 | 1.1 | 2.3 | 42.9 | 4876 | 2040 | 1.2 | 0.5 | 2.5 | 47.7 | 5868 | 3032 |
| 120 | 1.2 | 2.5 | 47.9 | 6120 | 2543 | 1.4 | 0.5 | 2.7 | 53.1 | 7235 | 3658 |
| 150 | 1.4 | 2.7 | 53.4 | 7556 | 3143 | 1.4 | 0.5 | 2.8 | 58.4 | 8765 | 4352 |
| 185 | 1.6 | 2.9 | 59.2 | 9419 | 3897 | 1.4 | 0.5 | 3.0 | 64.2 | 10752 | 5230 |
| 240 | 1.7 | 3.1 | 66.9 | 12249 | 4992 | 1.4 | 0.5 | 3.3 | 72.1 | 13783 | 6525 |
| 300 | 1.8 | 3.4 | 74.0 | 15273 | 6168 | 1.4 | 0.5 | 3.5 | 79.0 | 16925 | 7820 |
| 400 | 2.0 | 3.6 | 82.0 | 19369 | 7726 | 1.4 | 0.5 | 3.8 | 88.4 | 22080 | 10437 |
| Rated voltage 0.6/1kV 3+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 12.4 | 198 | 143 | 0.9 | 0.2 | 1.8 | 15.0 | 342 | 287 |
| 4/2.5 | 0.7/0.7 | 1.8 | 13.6 | 262 | 174 | 0.9 | 0.2 | 1.8 | 16.2 | 420 | 332 |
| 6/4 | 0.7/0.7 | 1.8 | 14.8 | 343 | 211 | 0.9 | 0.2 | 1.8 | 17.4 | 515 | 382 |
| 10/6 | 0.7/0.7 | 1.8 | 17.7 | 506 | 290 | 0.9 | 0.2 | 1.8 | 20.3 | 710 | 495 |
| 16/10 | 0.7/0.7 | 1.8 | 19.8 | 724 | 378 | 0.9 | 0.2 | 1.8 | 22.4 | 953 | 607 |
| 25/16 | 0.9/0.7 | 1.8 | 23.5 | 1083 | 536 | 0.9 | 0.2 | 1.8 | 26.1 | 1354 | 807 |
| 35/16 | 0.9/0.7 | 1.8 | 25.3 | 1371 | 649 | 0.9 | 0.2 | 1.9 | 28.1 | 1676 | 954 |
| 50/25 | 1.0/0.9 | 1.9 | 28.8 | 1852 | 853 | 0.9 | 0.2 | 2.0 | 31.6 | 2198 | 1199 |
| 70/35 | 1.1/0.9 | 2.0 | 33.5 | 2593 | 1158 | 1.2 | 0.2 | 2.2 | 38.3 | 3378 | 1944 |
| 95/50 | 1.1/1.0 | 2.2 | 37.9 | 3506 | 1522 | 1.2 | 0.5 | 2.3 | 42.5 | 4367 | 2383 |
| 120/70 | 1.2/1.1 | 2.3 | 42.1 | 4452 | 1897 | 1.2 | 0.5 | 2.5 | 46.9 | 5425 | 2871 |
| 150/70 | 1.4/1.1 | 2.5 | 46.9 | 5361 | 2305 | 1.4 | 0.5 | 2.6 | 51.9 | 6430 | 3373 |
| 185/95 | 1.6/1.1 | 2.6 | 51.8 | 6732 | 2851 | 1.4 | 0.5 | 2.8 | 57.0 | 7933 | 4053 |
| 240/120 | 1.7/1.2 | 2.9 | 58.8 | 8740 | 3670 | 1.4 | 0.5 | 3.0 | 63.8 | 10065 | 4995 |
| 300/150 | 1.8/1.4 | 3.1 | 64.8 | 10850 | 4504 | 1.4 | 0.5 | 3.2 | 69.8 | 12304 | 5958 |
| 400/185 | 2.0/1.6 | 3.3 | 71.8 | 13718 | 5628 | 1.4 | 0.5 | 3.5 | 77.0 | 15359 | 7269 |
| Rated voltage 0.6/1kV 3+2 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 225 | 161 | 0.9 | 0.2 | 1.8 | 15.9 | 379 | 315 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 300 | 197 | 0.9 | 0.2 | 1.8 | 17.2 | 469 | 366 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 398 | 241 | 0.9 | 0.2 | 1.8 | 18.6 | 583 | 426 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 584 | 332 | 0.9 | 0.2 | 1.8 | 21.8 | 806 | 554 |
| 16/10 | 0.7/0.7 | 1.8 | 21.8 | 844 | 439 | 0.9 | 0.2 | 1.8 | 24.4 | 1096 | 691 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1262 | 620 | 0.9 | 0.2 | 1.9 | 28.5 | 1572 | 930 |
| 35/16 | 0.9/0.7 | 1.8 | 27.5 | 1557 | 740 | 0.9 | 0.2 | 1.9 | 30.3 | 1889 | 1072 |
| 50/25 | 1.0/0.9 | 2.0 | 31.6 | 2148 | 998 | 1.2 | 0.2 | 2.1 | 36.2 | 2873 | 1724 |
| 70/35 | 1.1/0.9 | 2.1 | 36.7 | 2993 | 1350 | 1.2 | 0.2 | 2.3 | 41.5 | 3849 | 2206 |
| 95/50 | 1.1/1.0 | 2.3 | 41.5 | 4037 | 1770 | 1.2 | 0.5 | 2.4 | 46.1 | 4976 | 2709 |
| 120/70 | 1.2/1.1 | 2.4 | 46.1 | 5186 | 2223 | 1.4 | 0.5 | 2.6 | 51.3 | 6262 | 3299 |
| 150/70 | 1.4/1.1 | 2.6 | 51.5 | 6133 | 2669 | 1.4 | 0.5 | 2.8 | 56.7 | 7328 | 3863 |
| 185/95 | 1.6/1.1 | 2.8 | 57.1 | 7789 | 3341 | 1.4 | 0.5 | 3.0 | 62.3 | 9106 | 4658 |
| 240/120 | 1.7/1.2 | 3.0 | 64.5 | 10040 | 4255 | 1.4 | 0.5 | 3.2 | 69.7 | 11521 | 5736 |
| 300/150 | 1.8/1.4 | 3.3 | 71.3 | 12479 | 5251 | 1.4 | 0.5 | 3.4 | 76.3 | 14074 | 6845 |
| 400/185 | 2.0/1.6 | 3.5 | 79.0 | 15742 | 6547 | 1.4 | 0.5 | 3.7 | 85.4 | 18358 | 9163 |
| Rated voltage 0.6/1kV 4+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 235 | 165 | 0.9 | 0.2 | 1.8 | 15.9 | 389 | 319 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 315 | 202 | 0.9 | 0.2 | 1.8 | 17.2 | 483 | 371 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 416 | 247 | 0.9 | 0.2 | 1.8 | 18.6 | 601 | 432 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 620 | 344 | 0.9 | 0.2 | 1.8 | 21.8 | 842 | 566 |
| 16/10 | 0.7/0.7 | 1.8 | 21.7 | 896 | 455 | 0.9 | 0.2 | 1.8 | 24.3 | 1146 | 706 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1347 | 650 | 0.9 | 0.2 | 1.9 | 28.5 | 1657 | 960 |
| 35/16 | 0.9/0.7 | 1.9 | 28.2 | 1742 | 811 | 0.9 | 0.2 | 1.9 | 30.8 | 2067 | 1136 |
| 50/25 | 1.0/0.9 | 2.0 | 32.1 | 2347 | 1065 | 1.2 | 0.2 | 2.1 | 36.7 | 3083 | 1802 |
| 70/35 | 1.1/0.9 | 2.2 | 37.5 | 3308 | 1466 | 1.2 | 0.5 | 2.3 | 42.1 | 4161 | 2318 |
| 95/50 | 1.1/1.0 | 2.3 | 42.2 | 4456 | 1905 | 1.2 | 0.5 | 2.5 | 47.0 | 5432 | 2881 |
| 120/70 | 1.2/1.1 | 2.5 | 47.1 | 5663 | 2394 | 1.4 | 0.5 | 2.6 | 52.1 | 6736 | 3466 |
| 150/70 | 1.4/1.1 | 2.7 | 52.6 | 6857 | 2918 | 1.4 | 0.5 | 2.8 | 57.6 | 8048 | 4109 |
| 185/95 | 1.6/1.1 | 2.8 | 58.1 | 8591 | 3606 | 1.4 | 0.5 | 3.0 | 63.3 | 9931 | 4946 |
| 240/120 | 1.7/1.2 | 3.1 | 65.8 | 11159 | 4638 | 1.4 | 0.5 | 3.3 | 71.0 | 12668 | 6146 |
| 300/150 | 1.8/1.4 | 3.3 | 72.6 | 13860 | 5693 | 1.4 | 0.5 | 3.5 | 77.8 | 15518 | 7351 |
| 400/185 | 2.0/1.6 | 3.6 | 80.6 | 17573 | 7154 | 1.4 | 0.5 | 3.8 | 87.0 | 20238 | 9819 |
4. Our Factory
5. Exhibition/ Customer Visit
6. Our Honor
7. Contact Details
Dan zhao | Taifeng Cable Co., Ltd.
Add.: Heda Center, No.177 Tailiu Road, Shibei District, Qingdao, China
Factory Add.: No.1 Taifeng Road, Dacaozhuang Administrative Zone, Xingtai City, Hebei Province, China
Tel: 0086 532 85611663
Phone: 0086 17863817629
Website: taifengcable.en.
We are China Low Voltage XLPE Insulated PVC Sheathed Steel Tape Armoured Aluminum Electrical Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Cable Products
Armoured Cable Aia Armor Power Electric Wire cUL Copper C. S. a Teck90 Cables
Aluminum Armor Amoured Cable Power Electric Wire C. S. a Copper cUL Teck90 Cables
1kv XLPE/PE Insulated Aluminum Conductor ABC Cable
Building Wire Household Electrical Wire Insulated Copper Wire
Cu / XLPE / PVC 0.6 / 1kv Flame Retardant Cable / Flame Resistant Cable
Popular Electric Cable Products
H05V-K / H07V-K PVC Insulated Electrical Cable Wire Non Sheated Single Core Cables
ABC Cable Insulated Overhead Aerial Bundled Cable
600V 1Cx(Main 95mm2) & (Two Feeder 95mm2) Cable (for Tr(100) kVA) CU/XLPE/PVC
Fkkj, Power Cable, 0.6/1 Kv, Cu/PVC/Cws/Cts/PVC (HD 603.3/IEC 60502-1)
ASTM AAAC Conductor Bare All Aluminum Alloy Stranded Conductor for Power Transmission
Popular Power Cable Products
Low Voltage XLPE Insulated PVC Sheathed Aluminum Copper Conductor Electrical Wire Cable
XLPE Insulated Armored Copper Power Cable
0.6/1kv-20/35kv, Copper/Aluminium Conductor XLPE PVC Insulated and Sheathed Power Cable
Copper Conductor XLPE Insulated PVC Sheathed Copper Wire Power Cable
Top Quality IEC Standard Copper Conductor Power Cable
Multi-Core Silicone Insulated Silicone Sheath High Temperature Resistant Wire
Popular taifengcable Products
LV Mv XLPE Insulation PVC Armored Aluminum Copper Power Cable
Aluminum Conductor Steel Reinforced Overhead ACSR Aerial Bundle Cable
PVC Insulated Sheathed Braid Shield Electric Wire Control Cable
Kyjv Kyjvp XLPE Insulated PVC Sheathed Copper Conductor Control Cable
Copper/Aluminium Electric Power Cable Multi Cores Building Wire for House
China Manufacturer CB/ ISO/TUV/CCC Certificated Electrical Power Cable
Tags: Cable, Electric Cable, Power Cable, taifengcable