3X35/16mm2 N2xseyfgby 6/10 (12) Kv High Voltage Copper XLPE Insulated Cable
3X35/16mm2 N2xseyfgby 6/10 (12) Kv High Voltage Copper XLPE Insulated Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Application
They are used in cable ducts, outdoor installations, underground where the short circuit levels are high and industrial areas fed by electrical energy also these cables use where there is risk of mechanical damage.
01: Copper Conductor
02: Conductor Screen
03: XLPE Insulation
04: Insulation Screen
05: Semi-Conductive Tape
06: Copper Wire and Copper Tape Screen
07: PVC Filler
08: Binding Tape: non-hygroscopic tape
09: PVC Inner Sheath
10: Galvanised Round Steel Wire Armour
11: Binding Tape: non-hygroscopic tape
12: PVC Outer Sheath
Technical Data
| DESCRIPTION | UNIT | Supplier’s Offer |
| GENERAL | ||
| Cable Code | N2XSEYFGBY | |
| Applied Standards | IEC 60502-2 | |
| Voltage Rate (U0) | kV | 6 |
| Voltage Rate (U) | kV | 10 |
| Max. Operating Voltage (Um) | kV | 12 |
| 01: Conductor | ||
| Material | – | Plain annealed copper (free oxygen) |
| Cross-Section Area | mm² | 35 |
| Number & Diameter of Wires | No.*mm | 7*2.56 |
| Type of Stranding | CIRCULAR COMPACTED | |
| Outer Diameter (Approx.) | mm | 7.00 |
| Number of Core | No. | 3 |
| 02: Conductor Screen | ||
| Material | Extruded semi-conductive compound | |
| Nominal Thickness | mm | ≥0.5 |
| Minimum Thinkness | mm | ≥0.3 |
| Outer Diameter (Approx.) | mm | ≥8.0 |
| 03: Insulation | ||
| Material | XLPE | |
| Nominal Thickness | mm | ≥3.40 |
| Minimum Thickness | mm | ≥2.96 |
| Outer Diameter (Approx.) | mm | ≥14.80 |
| 04: Insulation Screen | ||
| Material | Extruded semi-conductive compound | |
| Nominal Thickness | mm | ≥0.50 |
| Minimum Thickness | mm | ≥0.30 |
| Outer Diameter (Approx.) | mm | ≥15.80 |
| 05: Semi-Conductive Tape | ||
| Tape Thickness | mm | 0.20 |
| 06: Metallic Screen | ||
| Material | Copper | |
| Type | Wire & Tape | |
| Number & Diameter of Wires | No.*mm | 12*0.85 (on each core) |
| Thickness & Width of Copper Tape | mm*mm | 0.10*(≥10)(on each core) |
| Tape for Protection | mm | |
| Outer Diameter (Approx.) | mm | ≥17.40 |
| Total Cross Section Area | mm² | ≥16.00 |
| 07: Filler | ||
| Material | PVC | |
| 08: Binding Tape: non-hygroscopic tape | ||
| Nominal Thickness | mm | 0.20 |
| 09: Inner Sheath | ||
| Material | PVC | |
| Nominal Thickness | mm | ≥1.40 |
| Minimum Thickness | mm | ≥0.92 |
| 10: Metallic Armour | ||
| Material | Galvanised Round Steel Wire | |
| Number*Diameter of Wires | No.*mm | (32~55) * 2.50 (up to IEC standard) |
| Thickness of Steel Tape | mm | ≥0.30 |
| Width of Steel Tape | mm | ≥20.00 |
| Binding Ratio | % | – |
| 11: Binding Tape: non-hygroscopic tape | ||
| Nominal Thickness | mm | 0.20 |
| 12: Outer Sheath | ||
| Material | PVC | |
| Colour | Red | |
| Nominal Thickness | mm | ≥2.60 |
| Minimum Thickness | mm | ≥1.88 |
| Electrical Properties | ||
| Test Voltage of 5 Minutes Duration | kV-rms | 21 |
| Impulse Test Voltage | kV-Peak | 75 |
| Continuous Current Carrying Capacity in Air at 30ºC | A | 182 |
| Continuous Current Carrying Capacity in Ground at 20ºC | A | 182 |
| Continuous Current Carrying Capacity in Duct | A | 163 |
| Ambient Temperature of Air | ºC | 30 |
| Soil Temperature | ºC | 20 |
| Depth of Laying | m | 0.8 |
| Thermal Resistivity of Soil | Km/W | 1.5 |
| Inductance | mH/km | 0.385 |
| Capacitance | μF/km | 0.226 |
| Insulation Resistance | MΩ/km | 14629 |
| Dielectric Losses (at 90ºC, 3phases) | W/km | 30.672 |
| Max. Continuous Conductor Temperature | ºC | 90 |
| Max. Conductor Temperature at Short Circuit Condition | ºC | 250 (5s max. duration) |
| Maximum Short-Circuit Current | ||
| Start Temperature 90ºC, End Temperature 250ºC | ||
| Duration of 5 seconds | kA | 2.24 |
| Duration of 1 seconds | kA | 5.01 |
| Duration of 0.5 seconds | kA | 7.08 |
| Maximum Short-Circuit Current at Metallic Screen | ||
| Duration of 1 seconds | kA | 2.048 |
| Duration of 0.5 seconds | kA | 2.896 |
| Dielectric Loss Factor | ||
| At 90ºC(Maximum Operating Temperature) | 40×10^4 | |
| Conductor Resistance at 20ºC | Ω/km | 0.5240 |
| Conductor Resistance at 90ºC | Ω/km | 0.6682 |
| Charging Current | A/km | 0.43 |
| Partial Discharge (at 2 U0) | pC | 5.00 |
| Other Properties | ||
| Outer Diameter of Cable (Approx.) | mm | ≥50.60 |
| Minimum Bending Radius | mm | ≥759 |
| Lowest Laying Temperature | ºC | -5.00 |
| Weight of Cable (Approx.) | kg/km | ≥4600 |
| Weight of Copper (Approx.) | kg/km | ≥1125 |
| Weight of Armour (Approx.) | kg/km | ≥1110 |
| Drums | ||
| Type | Steel & Wooden | |
| Flange (Wheel) Diameter | mm | 2200 |
| Barrel Diameter | mm | 900 |
| Barrel Length | mm | 1400 |
| Length of Cable | m | 1000 |
| Gross Weight | kg | ≥5225 |
We are China 3X35/16mm2 N2xseyfgby 6/10 (12) Kv High Voltage Copper XLPE Insulated Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular N2xseyfgby Products
Popular N2xseyfgby Cable Products
Popular XLPE Insulated Cable Products
0.6/1kv Cable Cu/PVC/Swa/PVC 2X16, 2X50, 2X70, 2X95, 2X120, 2X150, 2X185mm2
Steel Wire Armored 3 Core Copper XLPE Cable
Aerial Bundled Cable ABC Cable Overhead Cable ASTM BS NFC IEC DIN Standard
XLPE /PVC (Cross-linked polyethylene) Insulated/ Insulation Electric Power Cable
Quadruplex Service Drop ABC Cable XLPE Insulated Power Electric Cable
Copper Conductor XLPE Insulated Armoured Power Cable
Popular zzhongdacable Products
Tw/Thw 250mcm PVC Insualted Copper Cable
300/500V 2 3 4 5 Cores Copper Conductor PVC Insulated Flexible Wire
Preassembled Cable 2*16 4*16 54.6 Aluminum Cable
Copper Conductor PVC Wire Round or Flat Cable
3X240 1X120 mm2 N2xy Power Cable Cu XLPE PVC XLPE Cable 3 Core 240mm2 Copper Power
4*16+1*10 Copper Electrical Cable XLPE Insulated PVC Jacket Cable
Tags: N2xseyfgby, N2xseyfgby Cable, XLPE Insulated Cable, zzhongdacable