ABC cable
(Service drop cable)
1. Stranded aluminium conduct
2. PE or XLPE insulation
3. ACSR, AAAC Messenger wire
Application
It is preferred to use of service drop (ABC cables) instead of uninsulated conductors
At low voltage networks. Service drop (ABC cables)are especially used at areas
Where the cost of underground networks is expensive and also
For electrification of rural areas like villages.
Voltage
Rated voltage U0 / U = 0.6 /1 kV
VAC test voltage 5 kV
Technical Data
Maximum operating temperature 90 degree
Maximum short-circuit temperature 250 degree. Service drop( ABC cables) are especially used at areas where the cost of underground networks is expensive and also for electrification of rural areas like villages
Specification:
(1)Self-supporting
| Phase | Phase | Phase | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20ºC | |||
| AAC+UV-XLPE | Compact Conductor | UV-XLPE Insulation | |||||
| No.X Normal Cross Section of Cores | No.of Al Wires | Overall Diameter | Normal Thickness | Min. | Diameter | ||
| No. X mm2 | – | mm | mm | mm | mm | mm | ohm/km |
| 1 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 6.05 | 3.08 |
| 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 7.20 | 1.91 |
| 1 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 8.40 | 1.20 |
| 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 9.80 | 0.868 |
| 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 11.10 | 0.641 |
| 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 12.60 | 0.443 |
| 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 14.80 | 0.320 |
| 1 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 16.20 | 0.253 |
| 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 18.20 | 0.206 |
| 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 20.20 | 0.164 |
| 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 22.80 | 0.125 |
| 2 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 12.10 | 3.08 |
| 2 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 14.40 | 1.91 |
| 2 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 16.80 | 1.20 |
| 2 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 19.60 | 0.868 |
| 2 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 22.20 | 0.641 |
| 2 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 25.20 | 0.443 |
| 2 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 29.60 | 0.320 |
| 2 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 32.40 | 0.253 |
| 2 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 36.40 | 0.206 |
| 2 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 40.40 | 0.164 |
| 2 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 45.60 | 0.125 |
| 3 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 13.07 | 3.08 |
| 3 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 15.55 | 1.91 |
| 3 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 18.14 | 1.20 |
| 3 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 21.17 | 0.868 |
| 3 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 23.98 | 0.641 |
| 3 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 27.22 | 0.443 |
| 3 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 31.97 | 0.320 |
| 3 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 34.99 | 0.253 |
| 3 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 39.31 | 0.206 |
| 3 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 43.63 | 0.164 |
| 3 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 49.25 | 0.125 |
| 4 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 14.64 | 3.08 |
| 4 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 17.42 | 1.91 |
| 4 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 20.33 | 1.20 |
| 4 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 23.72 | 0.868 |
| 4 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 26.86 | 0.641 |
| 4 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 30.49 | 0.443 |
| 4 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 35.82 | 0.320 |
| 4 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 39.20 | 0.253 |
| 4 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 44.04 | 0.206 |
| 4 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 48.88 | 0.164 |
| 4 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 55.18 | 0.125 |
(2) Phase + Neutral
| Phase | Neutral | Phase | Neutral | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20ºC | ||||
| AAC+UV-XLPE | AAAC | Compact Conductor | UV-XLPE Insulation | Conductor | |||||
| Phase | Neutral | ||||||||
| No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No.of Al.Wire | Overall Dia. | Normal Thickness | Min. | No./Dia. of Al Alloy Wire | |||
| No. X mm2 | No. X mm2 | – | mm | mm | Min. | No./mm | mm | ohm/km | ohm/km |
| 1 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 12.30 | 1.91 | 2.217 |
| 1 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 14.70 | 1.20 | 1.393 |
| 1 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 17.30 | 0.868 | 1.007 |
| 1 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 20.10 | 0.641 | 0.744 |
| 1 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 23.10 | 0.443 | 0.514 |
| 1 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 27.30 | 0.320 | 0.371 |
| 1 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 30.20 | 0.253 | 0.294 |
| 1 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 33.95 | 0.206 | 0.239 |
| 1 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 37.70 | 0.164 | 0.190 |
| 1 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 43.05 | 0.125 | 0.145 |
| 2 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 14.04 | 1.91 | 2.217 |
| 2 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 16.63 | 1.20 | 1.393 |
| 2 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 19.51 | 0.868 | 1.007 |
| 2 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 22.46 | 0.641 | 0.744 |
| 2 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 25.70 | 0.443 | 0.514 |
| 2 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 30.31 | 0.320 | 0.371 |
| 2 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 33.41 | 0.253 | 0.294 |
| 2 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 37.55 | 0.206 | 0.239 |
| 2 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 41.69 | 0.164 | 0.190 |
| 2 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 47.41 | 0.125 | 0.145 |
| 3 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 16.15 | 1.91 | 2.217 |
| 3 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 19.06 | 1.20 | 1.393 |
| 3 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 22.32 | 0.868 | 1.007 |
| 3 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 25.59 | 0.641 | 0.744 |
| 3 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 29.22 | 0.443 | 0.514 |
| 3 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 34.42 | 0.320 | 0.371 |
| 3 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 37.87 | 0.253 | 0.294 |
| 3 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 42.56 | 0.206 | 0.239 |
| 3 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 47.25 | 0.164 | 0.190 |
| 3 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 53.63 | 0.125 | 0.145 |
(3) Phase + Neutral + Service Connection
| Phase | Neutral | Service Connection | Phase | Neutral | Service Connection | Approx.Overall Diameter of Bundled Cable | |||||
| AAC+UV-XLPE | AAAC+UV-XLPE | AAC+UV-XLPE | Conductor | UV-XLPE | Conductor | UV-XLPE | Compact Conductor | UV-XLPE | |||
| No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No. of Al. Wire | Overall Dia. | Normal Thickness |
No./Dia. of Al. Wire | Normal Thickness |
No. of Al. Wire | Overall Dia. | Normal Thickness |
|
| No. X mm2 | No. X mm2 | No. X mm2 | – | mm | mm | mm | mm | No./mm | mm | mm | mm |
| 3 X 16 | 1 X 50 | 1 X 16 | 7 | 4.8 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 26.2 |
| 3 X 25 | 1 X 50 | 1 X 16 | 7 | 6 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 28.6 |
| 3 X 35 | 1 X 50 | 1 X 16 | 7 | 7.0 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 31.4 |
| 3 X 50 | 1 X 50 | 1 X 16 | 7 | 8.3 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 34 |
| 3 X 70 | 1 X 50 | 1 X 16 | 19 | 9.8 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 37 |
| 3 X 95 | 1 X 50 | 1 X 16 | 19 | 11.6 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 41.4 |
| 3 X 120 | 1 X 50 | 1 X 16 | 19 | 13 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 44.2 |
| 3 X 16 | 1 X 50 | 2 X 16 | 7 | 4.8 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 26.2 |
| 3 X 25 | 1 X 50 | 2 X 16 | 7 | 6 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 28.6 |
| 3 X 35 | 1 X 50 | 2 X 16 | 7 | 7.0 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 31.4 |
| 3 X 50 | 1 X 50 | 2 X 16 | 7 | 8.3 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 34 |
| 3 X 70 | 1 X 50 | 2 X 16 | 19 | 9.8 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 37 |
| 3 X 95 | 1 X 50 | 2 X 16 | 19 | 11.6 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 41.4 |
| 3 X 120 | 1 X 50 | 2 X 16 | 19 | 13 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 44.2 |
We are China Hot Sales 15kv Overhead ABC Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular ABC Cable Products
ABC Aerial Bundled AS/NZS 3599.2 6.35/11kv ABC Cable (AL/XLPE/HDPE)
Overhead XLPE Insulated Aluminum Cable ABC Cable Caai Cable
ABC Cable Aluminum Cable XLPE Cover 3*50+54.6mm2
PE/XLPE Insulation Aluminum Conductor ABC Cable
Low Voltage XLPE Insulated Overhead Cable 3*35+54.6 3*70+54.6 3*50+54.6
0.6/1kv XLPE Insulation Triplex Aerial Bundled ABC Cable
Popular Insulated Cable Products
Rubber Insulated Copper Conductor Super Flexible Machine Cable
ASTM Standard Kvvrp/Kvvrp1/Kvvrp3/Zr-Kvvrp Control Cable
All Aluminium Conductors Type 8 PVC Insulation (AAC/PVC) with DIN 48210/BS 6485
Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 12/20 (24) Kv, 3/C (IEC 60502-2)
ABC Aerial Bunded Cable for Overhead Line
Electric Single Core Insulated Copper Wire Shield Aluminum Power Cable
Popular jpcable99 Products
Copper Core PVC Insulated Building Electrical Wire
Copper/Aluminum Conductor XLPE Insulated Power Cable
High Quality Service Drop Aerial Bundled Cable
95mm2 New Self-Supporting ABC Cable
Nyy Power and Control Cable for Fixed Installation HD 603 DIN VDE 0276 Bs 6346
120mm2 Bare Conductor ACSR Conductor
Popular Overhead ABC Cable Products
ABC Cable Eskimo Quadruplex Service Drop ABC Cable
Overhead Cable XLPE ABC Cable 0.6/1 Kv ABC Cable
100mm2 Cable AAAC Conductor/XLPE Insulation Overhead ABC Cable
Low Voltage 2/3/4 Cores ABC Cable Everhead Aerial Bundled Cable
1, 2, 3, 4 Core 25mm 35mm 70mm 16mm ABC Cable for Power Distribution
Aerial Bundled Triplex Aluminum Wire ABC Power Cable
Tags: ABC Cable, Insulated Cable, jpcable99, Overhead ABC Cable