Low/Medium Voltage XLPE Insulated Steel Wire Armoured Power Cable
Low/Medium Voltage XLPE Insulated Steel Wire Armoured Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Application:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.
Property:
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.
Specifications:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6.0 | 2.5 | 0.1 | 1.2 | 0.2 | 1.9 | 37.9 | 1.87 | 2.32 |
| 3 X 35 | 6.9 | 2.5 | 0.1 | 1.3 | 0.5 | 2.0 | 41.5 | 2.10 | 2.73 |
| 3 X50 | 8.2 | 2.5 | 0.1 | 1.3 | 0.5 | 2.0 | 44.3 | 2.37 | 3.22 |
| 3 X 70 | 9.7 | 2.5 | 0.1 | 1.4 | 0.5 | 2.1 | 47.9 | 2.77 | 4.00 |
| 3 X 95 | 11.3 | 2.5 | 0.1 | 1.4 | 0.5 | 2.2 | 51.6 | 3.21 | 4.91 |
| 3 X 120 | 12.8 | 2.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.4 | 3.69 | 5.84 |
| 3 X 150 | 14.2 | 2.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 4.15 | 6.85 |
| 3 X 185 | 15.9 | 2.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.5 | 4.73 | 8.11 |
| 3 X 240 | 18.3 | 2.6 | 0.1 | 1.6 | 0.5 | 2.7 | 68.5 | 5.62 | 10.05 |
| 3 X 300 | 20.4 | 2.8 | 0.1 | 1.7 | 0.5 | 2.9 | 74.5 | 6.55 | 12.11 |
| 3 X 400 | 23.2 | 3.0 | 0.1 | 1.9 | 0.8 | 3.2 | 83.6 | 8.78 | 15.86 |
| 3 X 500 | 26.4 | 3.2 | 0.1 | 2.1 | 0.8 | 3.4 | 93.0 | 10.52 | 18.85 |
2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6.0 | 3.4 | 0.1 | 1.3 | 0.5 | 2.0 | 43.4 | 2.16 | 2.61 |
| 3 X 35 | 6.9 | 3.4 | 0.1 | 1.3 | 0.5 | 2.0 | 45.4 | 2.36 | 2.99 |
| 3 X50 | 8.2 | 3.4 | 0.1 | 1.4 | 0.5 | 2.2 | 48.8 | 2.69 | 3.54 |
| 3 X 70 | 9.7 | 3.4 | 0.1 | 1.5 | 0.5 | 2.3 | 52.4 | 3.10 | 4.33 |
| 3 X 95 | 11.3 | 3.4 | 0.1 | 1.5 | 0.5 | 2.4 | 56.1 | 3.56 | 5.26 |
| 3 X 120 | 12.8 | 3.4 | 0.1 | 1.5 | 0.5 | 2.5 | 59.5 | 4.04 | 6.19 |
| 3 X 150 | 14.2 | 3.4 | 0.1 | 1.5 | 0.5 | 2.6 | 62.7 | 4.49 | 7.19 |
| 3 X 185 | 15.9 | 3.4 | 0.1 | 1.6 | 0.5 | 2.6 | 66.6 | 5.12 | 8.49 |
| 3 X 240 | 18.3 | 3.4 | 0.1 | 1.7 | 0.5 | 2.8 | 72.4 | 5.99 | 10.42 |
| 3 X 300 | 20.4 | 3.4 | 0.1 | 1.8 | 0.5 | 3.0 | 77.5 | 6.86 | 12.42 |
| 3 X 400 | 23.2 | 3.4 | 0.1 | 1.9 | 0.8 | 3.2 | 85.4 | 8.97 | 16.05 |
| 3 X 500 | 26.4 | 3.4 | 0.1 | 2.0 | 0.8 | 3.4 | 93.7 | 10.65 | 19.50 |
3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6.0 | 4.5 | 0.1 | 1.4 | 0.5 | 2.1 | 48.6 | 2.53 | 2.98 |
| 3 X 35 | 6.9 | 4.5 | 0.1 | 1.4 | 0.5 | 2.2 | 50.7 | 2.76 | 3.39 |
| 3 X50 | 8.2 | 4.5 | 0.1 | 1.5 | 0.5 | 2.3 | 53.9 | 3.10 | 3.95 |
| 3 X 70 | 9.7 | 4.5 | 0.1 | 1.5 | 0.5 | 2.4 | 57.4 | 3.51 | 4.74 |
| 3 X 95 | 11.3 | 4.5 | 0.1 | 1.5 | 0.5 | 2.6 | 61.2 | 4.05 | 5.75 |
| 3 X 120 | 12.8 | 4.5 | 0.1 | 1.6 | 0.5 | 2.6 | 64.7 | 4.56 | 6.72 |
| 3 X 150 | 14.2 | 4.5 | 0.1 | 1.6 | 0.5 | 2.7 | 67.9 | 5.04 | 7.74 |
| 3 X 185 | 15.9 | 4.5 | 0.1 | 1.7 | 0.5 | 2.8 | 71.9 | 5.66 | 9.04 |
| 3 X 240 | 18.3 | 4.5 | 0.1 | 1.8 | 0.5 | 3.0 | 77.7 | 6.56 | 11.00 |
| 3 X 300 | 20.4 | 4.5 | 0.1 | 1.9 | 0.8 | 3.2 | 84.1 | 8.39 | 13.96 |
| 3 X 400 | 23.2 | 4.5 | 0.1 | 2.0 | 0.8 | 3.3 | 90.5 | 9.71 | 16.79 |
| 3 X 500 | 26.4 | 4.5 | 0.1 | 2.1 | 0.8 | 3.5 | 98.8 | 11.45 | 20.57 |
4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | |||||||||
| 3 X 35 | 6.9 | 5.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.6 | 3.14 | 3.77 |
| 3 X50 | 8.2 | 5.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 3.49 | 4.34 |
| 3 X 70 | 9.7 | 5.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.1 | 3.93 | 5.16 |
| 3 X 95 | 11.3 | 5.5 | 0.1 | 1.6 | 0.5 | 2.6 | 65.7 | 4.46 | 6.16 |
| 3 X 120 | 12.8 | 5.5 | 0.1 | 1.7 | 0.5 | 2.7 | 69.4 | 5.00 | 7.15 |
| 3 X 150 | 14.2 | 5.5 | 0.1 | 1.7 | 0.5 | 2.8 | 72.6 | 5.49 | 8.19 |
| 3 X 185 | 15.9 | 5.5 | 0.1 | 1.8 | 0.5 | 3.0 | 76.9 | 6.16 | 9.53 |
| 3 X 240 | 18.3 | 5.5 | 0.1 | 1.9 | 0.8 | 3.2 | 83.9 | 7.87 | 12.31 |
| 3 X 300 | 20.4 | 5.5 | 0.1 | 2.0 | 0.8 | 3.2 | 88.6 | 8.96 | 14.52 |
| 3 X 400 | 23.2 | 5.5 | 0.1 | 2.1 | 0.8 | 3.5 | 95.4 | 10.35 | 17.43 |
| 3 X 500 | 26.4 | 5.5 | 0.1 | 2.2 | 0.8 | 3.7 | 103.7 | 12.45 | 20.23 |
5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | |||||||||
| 3 X 35 | |||||||||
| 3 X50 | 8.2 | 8.0 | 0.1 | 1.7 | 0.5 | 2.8 | 70.4 | 4.56 | 5.41 |
| 3 X 70 | 9.7 | 8.0 | 0.1 | 1.7 | 0.5 | 2.9 | 73.9 | 5.04 | 6.26 |
| 3 X 95 | 11.3 | 8.0 | 0.1 | 1.8 | 0.5 | 3.0 | 77.7 | 5.62 | 7.32 |
| 3 X 120 | 12.8 | 8.0 | 0.1 | 1.9 | 0.8 | 3.2 | 82.8 | 6.99 | 9.15 |
| 3 X 150 | 14.2 | 8.0 | 0.1 | 1.9 | 0.8 | 3.2 | 85.8 | 7.56 | 10.26 |
| 3 X 185 | 15.9 | 8.0 | 0.1 | 2.0 | 0.8 | 3.3 | 89.9 | 8.30 | 11.67 |
| 3 X 240 | 18.3 | 8.0 | 0.1 | 2.1 | 0.8 | 3.5 | 95.7 | 9.36 | 13.79 |
| 3 X 300 | 20.4 | 8.0 | 0.1 | 2.2 | 0.8 | 3.6 | 100.6 | 10.51 | 16.07 |
| 3 X 400 | 23.2 | 8.0 | 0.1 | 2.3 | 0.8 | 3.8 | 107.2 | 11.99 | 19.07 |
| 3 X 500 | 26.4 | 8.0 | 0.1 | 2.4 | 0.8 | 4.0 | 120.1 | 14.15 | 23.85 |
Workshop
Certificate
Shipment
We are China Low/Medium Voltage XLPE Insulated Steel Wire Armoured Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular jpcable99 Products
Nyy Electric Cable - 2/Building Wire
Copper Conductor Cable 3 Core PVC Power Cable
12/20kv XLPE Insulation Copper Swa Power Cable
12/20kv Copper Conductor XLPE Insulated Armoured Power Cable
150mm2 Bare Conductor ACSR Conductor
600V Duplex Conductor Urd Cable
Popular PVC Insulated Cable Products
BS 6346 Aluminum PVC Swa LV Electrical Power Cable Awa and Swa Cable
Copper/Aluminum Electric PVC Insulated Electric Cable Can Be Used Underground
ABC Cable Aluminum XLPE ABC Cable XLPE Insulated Overhead Cable
450/750V PVC Used as Electrical Power
0, 6/1 Kv Cu Conductor PVC/XLPE Insulated Power Cable
BS 6346 Copper PVC Steel Wire Armor Power Cable
Popular XLPE Cable Products
0.6/1kv Aerial Bundle Cable XLPE Insulated Cable ABC Cable
Cu/XLPE/Cts/PVC, Power Cable, 18/30 (36) Kv, 1/C (IEC 60502-2)
Low Voltage 3 Core Cu/Al Conductor XLPE Insulated PVC Sheathed Power Cable
Ser Seu Copper Conductor Concentric Cable
35kv XLPE Insulated Single Core 185mm2 Power Cable
Fire Resistant PVC XLPE Copper Aluminium Power Cable
Popular XLPE Insulated Cable Products
Low Voltage XLPE Insulated PVC Sheathed Swa Copper Power Cable
Security Fire Proof Resistance Flame Retardance Copper Electric Power Cable
Aluminum Alloy Conductor XLPE Insulated NFC Standard ABC Cable
0.6/1kv Popular PVC and XLPE Insulated Cable
Quadplex 4X185 XLPE Insulated Overhead Aerial Bundled Cable ABC Cable
Tags: jpcable99, PVC Insulated Cable, XLPE Cable, XLPE Insulated Cable