Copper Conductor Cable 4 Core PVC Insulated Power Cable
Copper Conductor Cable 4 Core PVC Insulated Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Application:
With the characteristics of stable capability,advanced technology,broad material resources,low price, good flexible and easy to lay and maintain, the PVC Insulated and Sheathed Power Cable are suitable to be laid for distribution line with A.C.50HZ and rated voltage up to 6kV.
Property:
1.The long-time permissible working temperature of cable conductive core is not more than 70 °C.
2.During short circuit (max. permanent time is not more than 5 seconds), the max temperature of cable conductor is not more than 165°C.
3.The difference level of laying cable is not restricted.When laying the cable,ambient temperature is not lower than 0°C.
4.They have good chemical stability,and properties of acid resistance,alkali resistance,salt resistance,oil resistance,solvent resistance and flame resistance.rty
5.Light weight,good bending property and easy installation and maintenance.
Specification:
Standard:
IEC,BS,VDE,AS/NZS,ICEA,JIS and so on,designing and manufacturing special power cable according to the other standards required by the customer
1)600/1000V, Single Core, Circular Compacted Al or Cu/PVC/PVC Unarmoured or Armoured Power Cable
| Cross Section of Conductor | No. of Wires | Thickness of Insulation | Unarmoured | Armoured | ||||||||
| Thickness of Sheath | Overall Dia. | jpcable99.en. Weight | Thickness of Bedding | Thickness of Al Tape | Thickness of Sheath | Overall Dia. | jpcable99.en. Weight | |||||
| Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||||
| mm2 | – | mm | mm | mm | kg/km | kg/km | mm | mm | mm | mm | kg/km | kg/km |
| 1.5 | 1 | 0.8 | 1.4 | 5.8 | – | 51 | – | – | – | – | – | – |
| 2.5 | 1 | 0.8 | 1.4 | 6.2 | – | 64 | – | – | – | – | – | – |
| 4 | 1 | 1 | 1.4 | 7.1 | – | 88 | – | – | – | – | – | – |
| 6 | 7 | 1 | 1.4 | 7.8 | 78 | 114 | – | – | – | – | – | – |
| 10 | 7 | 1 | 1.4 | 8.6 | 96 | 159 | 1 | 0.5 | 1.8 | 13.4 | 234 | 295 |
| 16 | 7 | 1 | 1.4 | 9.6 | 123 | 222 | 1 | 0.5 | 1.8 | 14.4 | 274 | 370 |
| 25 | 7 | 1.2 | 1.4 | 11.2 | 172 | 328 | 1 | 0.5 | 1.8 | 16 | 344 | 496 |
| 35 | 7 | 1.2 | 1.4 | 12.2 | 209 | 428 | 1 | 0.5 | 1.8 | 17 | 393 | 606 |
| 50 | 19 | 1.4 | 1.4 | 13.9 | 271 | 565 | 1 | 0.5 | 1.8 | 18.7 | 478 | 764 |
| 70 | 19 | 1.4 | 1.5 | 15.9 | 356 | 818 | 1 | 0.5 | 1.8 | 20.5 | 582 | 1020 |
| 95 | 19 | 1.6 | 1.5 | 18 | 471 | 1041 | 1 | 0.5 | 1.8 | 22.6 | 717 | 1291 |
| 120 | 37 | 1.6 | 1.6 | 19.6 | 563 | 1307 | 1 | 0.5 | 1.8 | 24 | 822 | 1545 |
| 150 | 37 | 1.8 | 1.6 | 21.3 | 684 | 1592 | 1 | 0.5 | 1.8 | 25.4 | 952 | 1857 |
| 185 | 37 | 2 | 1.7 | 23.9 | 840 | 1985 | 1 | 0.5 | 1.8 | 27.9 | 1136 | 2236 |
| 240 | 61 | 2.2 | 1.8 | 27 | 1071 | 2533 | 1 | 0.5 | 1.9 | 31 | 1404 | 2877 |
| 300 | 61 | 2.4 | 1.9 | 29.6 | 1317 | 3162 | 1.2 | 0.5 | 2.1 | 34.3 | 1722 | 3551 |
| 400 | 61 | 2.6 | 2 | 33.2 | 1666 | 4120 | 1.2 | 0.5 | 2.2 | 37.6 | 2114 | 4488 |
| 500 | 61 | 2.8 | 2.2 | 37.5 | 2089 | 5163 | 1.2 | 0.5 | 2.3 | 42.1 | 2592 | 5683 |
| 630 | 61 | 2.8 | 2.3 | 41.2 | 2581 | 6447 | 1.4 | 0.5 | 2.4 | 46.3 | 3184 | 7060 |
2)600/1000V, Multi Cores, Sectoral Compacted Al or Cu/PVC/PVC Unarmoured Power Cable
| Number of Cores | Cross-Section of Conductor | No. Of Wires | Thickness of Insulation | Thickness of Sheath | Overall Diameter | Approx. Net Weight | |
| Al Conductor | Cu Conductor | ||||||
| – | mm2 | – | mm | mm | mm | kg/km | kg/km |
| Three Cores | 3×35 | 16 | 1.2 | 1.8 | 21.9 | 601 | 1280 |
| 3×50 | 18 | 1.4 | 1.8 | 26.5 | 829 | 1732 | |
| 3×70 | 18 | 1.4 | 1.9 | 29.2 | 1067 | 2367 | |
| 3×95 | 36 | 1.6 | 2 | 32.9 | 1409 | 2317 | |
| 3×120 | 36 | 1.6 | 2.1 | 36.2 | 1705 | 3983 | |
| 3×150 | 36 | 1.8 | 2.2 | 38.8 | 2045 | 4872 | |
| 3×185 | 36 | 2 | 2.4 | 44.8 | 2596 | 6077 | |
| 3×240 | 60 | 2.2 | 2.6 | 51.5 | 3353 | 7953 | |
| 3×300 | 60 | 2.4 | 2.7 | 54.9 | 6069 | 9820 | |
| Four Cores with Reduced Neutral | 3×35+16 | 16-7 | 1.2-1 | 1.8 | 25.5 | 764 | 1107 |
| 3×50+25 | 18-16 | 1.4-1.2 | 1.9 | 28.7 | 982 | 1410 | |
| 3×70+35 | 18-16 | 1.4-1.2 | 2.0 | 32 | 1278 | 1733 | |
| 3×95+50 | 36-18 | 1.6-1.4 | 2.2 | 37.8 | 1711 | 2656 | |
| 3×120+70 | 36-18 | 1.6-1.4 | 2.3 | 40.5 | 2065 | 3137 | |
| 3×150+70 | 36-18 | 1.8-1.4 | 2.4 | 44.8 | 2480 | 3660 | |
| 3×185+95 | 36-36 | 2-1.6 | 2.6 | 49.7 | 3086 | 4345 | |
| 3×240+120 | 60-36 | 2.2-1.6 | 2.8 | 56 | 3894 | 5441 | |
| 3×300+150 | 60-36 | 1.4-1.8 | 2.9 | 60.3 | 4834 | 6494 | |
| Four Cores | 4×25 | 16 | 1.2 | 1.8 | 22.5 | 644 | 1286 |
| 4×35 | 16 | 1.2 | 1.8 | 24.6 | 799 | 1696 | |
| 4×50 | 18 | 1.4 | 1.8 | 28.6 | 1071 | 2275 | |
| 4×70 | 18 | 1.4 | 2 | 31.6 | 1387 | 3120 | |
| 4×95 | 36 | 1.6 | 2.1 | 35.9 | 1850 | 4262 | |
| 4×120 | 36 | 1.6 | 2.2 | 38.8 | 2209 | 5247 | |
| 4×150 | 36 | 1.8 | 2.3 | 43.1 | 2714 | 6483 | |
| 4×185 | 36 | 2 | 2.5 | 48.7 | 3403 | 8045 | |
| 4×240 | 60 | 2.2 | 2.7 | 53.6 | 4290 | 10422 | |
| 4×300 | 60 | 2.4 | 2.9 | 58.8 | 5302 | 12969 | |
3)600/1000V, Multi Cores, Circular Compacted Al or Cu/PVC/PVC Unarmoured Power Cable
| Number of Cores | Cross-Section of Conductor | No. Of Wires | Thickness of Insulation | Thickness of Sheath | Overall Diameter | Approx. Net Weight | ||
| Al Conductor | Cu Conductor | |||||||
| – | mm2 | – | mm | mm | mm | kg/km | kg/km | |
| Three Cores | 3×10 | 7 | 1 | 1.8 | 16.6 | 281 | 465 | |
| 3×16 | 7 | 1 | 1.8 | 18.7 | 387 | 679 | ||
| 3×25 | 7 | 1.2 | 1.8 | 22.2 | 536 | 996 | ||
| 3×35 | 7 | 1.2 | 1.8 | 24.4 | 665 | 1311 | ||
| 3×50 | 19 | 1.4 | 1.9 | 28.1 | 863 | 1729 | ||
| 3×70 | 19 | 1.4 | 2 | 32.3 | 1153 | 2480 | ||
| 3×95 | 19 | 1.6 | 2.1 | 37.1 | 1563 | 3301 | ||
| 3×120 | 37 | 1.6 | 2.3 | 40.4 | 1850 | 4040 | ||
| 3×150 | 37 | 1.8 | 2.4 | 43.9 | 2258 | 5000 | ||
| 3×185 | 37 | 2 | 2.5 | 49.2 | 2819 | 6151 | ||
| 3×240 | 61 | 2.2 | 2.8 | 55.9 | 3577 | 8040 | ||
| 3×300 | 61 | 2.4 | 3 | 62.1 | 4413 | 9955 | ||
| 3×400 | 61 | 2.6 | 3.2 | 69.3 | 5512 | 12705 | ||
| Four Cores | 4×10 | 7 | 1 | 1.8 | 18.1 | 343 | 589 | |
| 4×16 | 7 | 1 | 1.8 | 20.5 | 487 | 874 | ||
| 4×25 | 7 | 1.2 | 1.8 | 24.3 | 677 | 1291 | ||
| 4×35 | 7 | 1.2 | 1.8 | 26.8 | 821 | 1681 | ||
| 4×50 | 19 | 1.4 | 2 | 31.2 | 1118 | 2273 | ||
| 4×70 | 19 | 1.4 | 2.1 | 35.8 | 1494 | 3264 | ||
| 4×95 | 19 | 1.6 | 2.3 | 41.2 | 1993 | 4312 | ||
| 4×120 | 37 | 1.6 | 2.4 | 44.8 | 2370 | 5291 | ||
| 4×150 | 37 | 1.8 | 2.5 | 48.7 | 2959 | 6615 | ||
| 4×185 | 37 | 2 | 2.7 | 54.7 | 3601 | 8044 | ||
| 4×240 | 61 | 2.2 | 3 | 62.1 | 4596 | 10547 | ||
| 4×300 | 61 | 2.4 | 3.2 | 69.1 | 5614 | 13004 | ||
4)600/1000V, Multi Cores, Sectoral Compacted Al or Cu/PVC/PVC Armoured Power Cable
| Cross Section of Conductor | No. of Wires | Thickness of Insulation | Thickness of Inner Sheath | Thickness of Steel Tape | No./Dia. Of Steel Wires | Thickness of Sheath | Overall Diameter | Approx. Net Weight | ||||||
| STA | SWA | |||||||||||||
| STA | SWA | STA | SWA | STA | SWA | Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||
| mm2 | – | mm | mm | mm | No./mm | mm | mm | mm | mm | kg/km | kg/km | kg/km | kg/km | |
| Three Cores | ||||||||||||||
| 3×35 | 16 | 1.2 | 1 | 0.2 | 38/1.6 | 1.8 | 1.9 | 24.7 | 28.2 | 912 | 1591 | 1447 | 2126 | |
| 3×50 | 18 | 1.4 | 1 | 0.2 | 46/1.6 | 1.9 | 2 | 29.3 | 32.8 | 1202 | 2105 | 1842 | 2745 | |
| 3×70 | 18 | 1.4 | 1.2 | 0.2 | 41/2.0 | 2.0 | 2.2 | 32.5 | 37.1 | 1520 | 2820 | 2475 | 3775 | |
| 3×95 | 36 | 1.6 | 1.2 | 0.5 | 46/2.0 | 2.1 | 2.3 | 36.5 | 40.8 | 2241 | 4049 | 2989 | 4797 | |
| 3×120 | 36 | 1.6 | 1.2 | 0.5 | 50/2.0 | 2.2 | 2.4 | 39.8 | 44.1 | 2617 | 4895 | 3435 | 5713 | |
| 3×150 | 36 | 1.8 | 1.2 | 0.5 | 43/2.5 | 2.3 | 2.5 | 42.4 | 47.8 | 3019 | 5846 | 4258 | 7085 | |
| 3×185 | 36 | 2 | 1.4 | 0.5 | 50/2.5 | 2.5 | 2.7 | 48.8 | 54.2 | 3783 | 7264 | 5219 | 8700 | |
| 3×240 | 60 | 2.2 | 1.6 | 0.5 | 58/2.5 | 2.8 | 2.9 | 56 | 61.3 | 4790 | 9390 | 6444 | 11044 | |
| 3×300 | 60 | 2.4 | 1.6 | 0.5 | 61/2.5 | 2.9 | 3.1 | 59.3 | 64.7 | 5594 | 11345 | 7458 | 13209 | |
| Four Cores with Reduced Neutral | ||||||||||||||
| 3×35+16 | 16-7 | 1.2-1 | 1 | 0.2 | 43/1.6 | 1.9 | 2 | 28.5 | 31.3 | 1107 | 1528 | 1705 | 2469 | |
| 3×50+25 | 18-16 | 1.4-1.2 | 1.2 | 0.2 | 40/2.0 | 2.0 | 2.1 | 32.2 | 36.1 | 1410 | 2044 | 2326 | 3388 | |
| 3×70+35 | 18-16 | 1.4-1.2 | 1.2 | 0.2 | 44/2.0 | 2.0 | 2.2 | 35.2 | 39.3 | 1733 | 2801 | 2762 | 4285 | |
| 3×95+50 | 36-18 | 1.6-1.4 | 1.2 | 0.5 | 41/2.5 | 2.3 | 2.5 | 42.5 | 46.3 | 2656 | 3820 | 3816 | 5925 | |
| 3×120+70 | 36-18 | 1.6-1.4 | 1.4 | 0.5 | 45/2.5 | 2.4 | 2.6 | 45.6 | 49.4 | 3137 | 4777 | 4391 | 7103 | |
| 3×150+70 | 36-18 | 1.8-1.4 | 1.4 | 0.5 | 49/2.5 | 2.6 | 2.7 | 49.9 | 53.6 | 3660 | 5709 | 5043 | 8272 | |
| 3×185+95 | 36-36 | 2-1.6 | 1.4 | 0.5 | 55/2.5 | 2.6 | 2.9 | 54.5 | 58.5 | 3445 | 7171 | 5902 | 9987 | |
| 3×240+120 | 60-36 | 2.2-1.6 | 1.6 | 0.5 | 62/2.5 | 2.9 | 3.1 | 61.6 | 65.3 | 5441 | 9272 | 7174 | 12552 | |
| 3×300+150 | 60-36 | 1.4-1.8 | 1.6 | 0.5 | 67/2.5 | 3.8 | 3.2 | 65.9 | 69.6 | 6494 | 11546 | 8355 | 15067 | |
| Four Cores | ||||||||||||||
| 4×25 | 16 | 1.2 | 1 | 0.2 | 38/1.6 | 1.8 | 1.9 | 25.3 | 28 | 934 | 1576 | 1450 | 2092 | |
| 4×35 | 16 | 1.2 | 1 | 0.2 | 41/1.6 | 1.8 | 1.9 | 27.4 | 30.2 | 1120 | 2017 | 1681 | 2578 | |
| 4×50 | 18 | 1.4 | 1 | 0.2 | 39/2.0 | 2 | 2.1 | 31.6 | 35.6 | 1454 | 2658 | 2336 | 3540 | |
| 4×70 | 18 | 1.4 | 1.2 | 0.5 | 43/2.0 | 2.1 | 2.2 | 36.3 | 39 | 2183 | 3916 | 2840 | 4573 | |
| 4×95 | 36 | 1.6 | 1.2 | 0.5 | 50/2.0 | 2.3 | 2.4 | 40.6 | 44.1 | 2748 | 5160 | 3545 | 5957 | |
| 4×120 | 36 | 1.6 | 1.4 | 0.5 | 42/2.5 | 2.4 | 2.5 | 43.9 | 47.2 | 3237 | 6214 | 4334 | 7372 | |
| 4×150 | 36 | 1.8 | 1.4 | 0.5 | 48/2.5 | 2.5 | 2.6 | 48.3 | 52 | 3853 | 7622 | 5148 | 8917 | |
| 4×185 | 36 | 2 | 1.6 | 0.5 | 54/2.5 | 2.7 | 2.8 | 54.3 | 57.6 | 4756 | 9323 | 6132 | 10774 | |
| 4×240 | 60 | 2.2 | 1.6 | 0.5 | 59/2.5 | 2.9 | 3 | 59.2 | 62.9 | 5774 | 11906 | 7374 | 13506 | |
| 4×300 | 60 | 2.4 | 1.6 | 0.5 | 65/2.5 | 3 | 3.2 | 64.3 | 68.1 | 6922 | 14589 | 8624 | 16291 | |
5)600/1000V, Multi Cores, Circular Compacted Al or Cu/PVC/PVC Armoured Power Cable
| Cross Section of Conductor | No. of Wires | Thickness of Insulation | Thickness of Inner Sheath | Thickness of Steel Tape | No./Dia. Of Steel Wires | Thickness of Sheath | Overall Diameter | Approx. Net Weight | |||||
| STA | SWA | ||||||||||||
| STA | SWA | STA | SWA | STA | SWA | Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||
| mm2 | – | mm | mm | mm | No./mm | mm | mm | mm | mm | kg/km | kg/km | kg/km | kg/km |
| Three Cores | |||||||||||||
| 3×10 | 7 | 1 | 1 | 0.2 | 35/1.25 | 1.8 | 1.8 | 19.4 | 21.5 | 494 | 679 | 988 | 1172 |
| 3×16 | 7 | 1 | 1 | 0.2 | 32/1.6 | 1.8 | 1.8 | 21.5 | 24.3 | 604 | 895 | 1051 | 1343 |
| 3×25 | 7 | 1.2 | 1 | 0.2 | 38/1.6 | 1.8 | 1.8 | 25 | 27.9 | 791 | 1252 | 1329 | 1790 |
| 3×35 | 7 | 1.2 | 1 | 0.2 | 42/1.6 | 1.8 | 1.9 | 27.2 | 30.2 | 950 | 1595 | 1551 | 2196 |
| 3×50 | 19 | 1.4 | 1.1 | 0.2 | 39/2.0 | 2 | 2.1 | 31.3 | 35.2 | 1213 | 2079 | 2128 | 2994 |
| 3×70 | 19 | 1.4 | 1.2 | 0.5 | 45/2.0 | 2.1 | 2.2 | 35.6 | 40.1 | 1567 | 2894 | 2678 | 4005 |
| 3×95 | 19 | 1.6 | 1.3 | 0.5 | 42/2.5 | 2.3 | 2.4 | 42 | 46.2 | 2449 | 4188 | 3689 | 5428 |
| 3×120 | 37 | 1.6 | 1.3 | 0.5 | 45/2.5 | 2.4 | 2.5 | 45.3 | 49.6 | 2823 | 5014 | 4174 | 6364 |
| 3×150 | 37 | 1.8 | 1.4 | 0.5 | 49/2.5 | 2.5 | 2.7 | 48.9 | 53.2 | 3327 | 6069 | 4795 | 7537 |
| 3×185 | 37 | 2 | 1.5 | 0.5 | 56/2.5 | 2.7 | 2.8 | 54.5 | 58.7 | 4038 | 7371 | 5686 | 9019 |
| 3×240 | 61 | 2.2 | 1.6 | 0.5 | 63/2.5 | 2.9 | 3.1 | 61.4 | 65.2 | 4994 | 9457 | 6862 | 11325 |
| 3×300 | 61 | 2.4 | 1.7 | 0.5 | 70/2.5 | 3.2 | 3.3 | 67.9 | 71.7 | 6022 | 11564 | 8101 | 13643 |
| 3×400 | 61 | 2.6 | 1.9 | 0.5 | 62/3.15 | 3.4 | 3.6 | 75.4 | 80.5 | 7350 | 14543 | 10535 | 17728 |
| Four Cores | |||||||||||||
| 4×10 | 7 | 1 | 1 | 0.2 | 39/1.25 | 1.8 | 1.8 | 20.9 | 23 | 552 | 798 | 1073 | 1319 |
| 4×16 | 7 | 1 | 1 | 0.2 | 35/1.6 | 1.8 | 1.8 | 23.3 | 26.1 | 723 | 1110 | 1213 | 1601 |
| 4×25 | 7 | 1.2 | 1 | 0.2 | 42/1.6 | 1.8 | 1.9 | 27.2 | 30.2 | 959 | 1573 | 1559 | 2173 |
| 4×35 | 7 | 1.2 | 1 | 0.2 | 37/2.0 | 1.9 | 2 | 29.7 | 33.6 | 1140 | 2000 | 2006 | 2866 |
| 4×50 | 19 | 1.4 | 1.2 | 0.2 | 44/2.0 | 2.1 | 2.2 | 34.6 | 38.4 | 1524 | 2679 | 2541 | 3696 |
| 4×70 | 19 | 1.4 | 1.2 | 0.5 | 50/2.0 | 2.3 | 2.3 | 40.5 | 43.7 | 2338 | 4107 | 3187 | 4956 |
| 4×95 | 19 | 1.6 | 1.2 | 0.5 | 46/2.5 | 2.4 | 2.6 | 45.9 | 50.2 | 2955 | 5274 | 4325 | 6644 |
| 4×120 | 37 | 1.6 | 1.4 | 0.5 | 51/2.5 | 2.6 | 2.7 | 50 | 54.2 | 3466 | 6387 | 4568 | 7888 |
| 4×150 | 37 | 1.8 | 1.4 | 0.5 | 55/2.5 | 2.7 | 2.8 | 53.8 | 58.1 | 4144 | 7800 | 5772 | 9428 |
| 4×185 | 37 | 2 | 1.6 | 0.5 | 62/2.5 | 2.9 | 3 | 60.2 | 64.5 | 4987 | 9430 | 6822 | 11266 |
| 4×240 | 61 | 2.2 | 1.6 | 0.5 | 70/2.5 | 3.1 | 3.3 | 67.7 | 71.5 | 6161 | 12111 | 8233 | 14184 |
| 4×300 | 61 | 2.4 | 1.6 | 0.5 | 61/3.15 | 3.4 | 3.5 | 74.7 | 78.8 | 7346 | 14735 | 10 | |
5)Workshop
We are China Copper Conductor Cable 4 Core PVC Insulated Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 70mm2 Power Cable Products
High Quality 70mm2 PVC Insulated Power Cable
0.6/1kv Cu Conductor PVC/XLPE Insulated Aluminum/Steel Tape Armour Power Cable
150mm2 Copper Conductor Cable PVC Insulated Cable
25mm2 50mm2 70mm2 95mm2 240mm2 PVC/XLPE Insulated Power Cable
Popular jpcable99 Products
AAC 250sqmm 315sqmm 400sqmm All Aluminium Stranded Conductor Bare Conductor
6.35/10kv XLPE Insulated Power Cable
BS 215 -Part 1standard AAC Conductor
Steel Tape Armoured Power Cable (STA Cable)
High Quality 50mm PVC Insulated Electric Cable, Power Cable
Bare Conduct AAAC with ASTM B399/BS En50183/ IEC 61086
Popular PVC Insulated Cable Products
0.6/1kv PVC or XLPE Insulated Power Cable
1.5mm / 2.5mm / 10mm Flexible Copper Electrical Cable Wire PVC Insulated Cable
Low Voltage 240mm2 PVC Insulated Underground Power Cable
35kv Copper or Aluminium 4 Core XLPE Insulated Power Cables
Underground Power Cable 4 Core PVC Armored Cable
2.5mm2, 27 Core, Stranded, PVC Insulated Swa Armour Control Cable
Popular PVC Power Cable Products
3X50+25mm2 Copper Conductor XLPE Insulation PVC Sheath Electric Power Cable
Low Voltage Fire Resistant Flame Retardant PVC Sheathed Copper/Aluminum Core Power Cable
Low Voltage PVC 4 Cores Cable Wire with Flame Retardance or Fire-Resistant
4 Cores PVC Insulated Power Cable
4X95mm2 Copper or Aluminum Conductor XLPE/PVC Insulated PVC Sheath Power Cable
Tags: 70mm2 Power Cable, jpcable99, PVC Insulated Cable, PVC Power Cable