Traction Transformer Tap Changing Oltc 33kv
Traction Transformer Tap Changing Oltc 33kv image
Get Latest Price Request a quote
Quick Details
Product Details
Suzhou Silverstone Electric Co., Ltd
1. General
(1) Application:
>> 12, 24,36KV~220kv class transformers
are widely used in power transmission and distribution stations,
industry plants, Generation Setup Unit (GSU).
>> They have the characteristic of high efficiency, low loss and maintenance free.
(2) Type and Rating
**Capacity range :50-50000KVA.
**Secondary voltage: 415V ,400V etc.
**Frequency :50Hz ,60Hz.
**Type: Single phase, three phase.
**No-load tap changer and on-load tap changer.
**ONAN and ONAF.
**Set-up and set-down type.
(3) Standard: IEC60076-1, IEC60076-2, IEC60076-5, IEC60317, ANSI, IEEE, AS, etc.
2. Conditions of service
(1) Altitude: Up to 1,000m above sea level.
(2) Ambient temperature:
**Max: +40ºC.
**Average (daily, Max.): +30ºC.
**Average (yearly, Max.): +20ºC.
**Min: -45ºC.
(3) Environment: Outdoor.
(4) Special conditions:
It may be consulted between manufacturer and customer.
3. Structural Features
(1) Iron core
The iron core is made of cold rolled grain oriented silicon steel sheet. Laminations are cut to length
on GEORG cut to- length line with step lap cut and automatic stacking functions.
The multistep lamination structure can reduce the loss and noise.
The steel sheet in the core limbs and yokes are clamped together by glass-epoxy bonds.
(2) Winding
High quality enameled or paper covered copper is used as conductor, the winding was made as
drum type, spiral type, improved spiral type, continuous type and interleaved type to ensure the insulation strength. Standard tapings are ±2*2.5%of the HV winding.
(3) Tank
The tank, cover and the conservator are made by corrugated steel plate. For the small transformers,
we use a deep tank and a cover, but for larger transformers, we manufacture bell type. The corrugated construction is a effective way for oil cooling.
(4) Insulation oil
The tanks are filled with high quality grade mineral oil as per IEC296 and it is PCB and PCT free.
The oil is used to help cooling the transformer. It is also used provide part of the electrical insulation between internal live parts.
(5) Tap changer
Tap changers are used to regulate the output voltage of the transformers to required levels. We
achieve this by changing the ratios of the transformer on the system by altering the number of turns in the HV winding. Tap changers can be on load (OLTC) or off load(OCTC).
(6) Assembly
The core and the windings assembled together from the active part of the transformer. The active
body assembled with multi-windings and identical pressure dry method adopted, effectively improved
the electrical strength and the ability to short circuit withstanding.
4. Test equipment
Strict test should be done according to IEC standard, by high technical equipment to ensure the
quality and the reliable of every transformer.
5. Technical Data of Typical Products
>S9, S10 series 10KV three phase off -load tap changer distribution transformer
| Type | Rating KVA |
On-load loss (w) |
Load loss (w) |
I (%) |
UK (%) |
Dimension (mm) | Weight (kg) |
||
| a | b | c | |||||||
| S9-M-50/11 | 50 | 170 | 870 | 2.0 | 4.0 | 1215 | 660 | 1170 | 430 |
| S9-M-250/11 | 250 | 560 | 3050 | 1.2 | 4.0 | 1190 | 815 | 1370 | 1115 |
| S9-M-400/11 | 400 | 800 | 4300 | 1.0 | 4.0 | 1515 | 770 | 1580 | 1380 |
| S9-M-500/11 | 500 | 960 | 5050 | 1.0 | 4.0 | 1635 | 840 | 1610 | 1600 |
| S9-M-1000/11 | 1000 | 1700 | 10300 | 0.7 | 4.5 | 1960 | 1095 | 1960 | 2860 |
| S9-M-2500/11 | 2500 | 3300 | 23000 | 0.55 | 5.5 | 2230 | 2305 | 2445 | 5660 |
| S10-M-30/10 | 30 | 110 | 600 | 1.8 | 4.0 | 870 | 645 | 1025 | 310 |
| S10-M-50/10 | 50 | 140 | 870 | 1.7 | 4.0 | 1090 | 650 | 1080 | 395 |
| S10-M-80/10 | 80 | 200 | 1250 | 1.6 | 4.0 | 1140 | 675 | 1110 | 490 |
| S10-M-100/10 | 100 | 240 | 1500 | 1.5 | 4.0 | 1185 | 690 | 1130 | 560 |
| S10-M-125/10 | 125 | 280 | 1800 | 1.4 | 4.0 | 1205 | 710 | 1180 | 670 |
| S10-M-160/10 | 160 | 340 | 2200 | 1.3 | 4.0 | 1255 | 720 | 1200 | 780 |
| S10-M-200/10 | 200 | 400 | 2600 | 1.2 | 4.0 | 1295 | 740 | 1215 | 875 |
| S10-M-250/10 | 250 | 470 | 3050 | 1.1 | 4.0 | 1340 | 755 | 1260 | 1115 |
| S10-M-315/10 | 315 | 560 | 3650 | 1.0 | 4.0 | 1400 | 770 | 1320 | 1280 |
| S10-M-400/10 | 400 | 680 | 4300 | 0.9 | 4.0 | 1500 | 860 | 1400 | 1490 |
| S10-M-500/10 | 500 | 810 | 5150 | 0.9 | 4.0 | 1575 | 895 | 1430 | 1740 |
| S10-M-630/10 | 630 | 1020 | 6200 | 0.8 | 4.5 | 1660 | 930 | 1545 | 2110 |
| S10-M-800/10 | 800 | 1190 | 7500 | 0.7 | 4.5 | 1830 | 1070 | 1590 | 2625 |
| S10-M-1000/10 | 1000 | 1450 | 10300 | 0.6 | 4.5 | 1935 | 1175 | 1685 | 2860 |
| S10-M-1250/10 | 1250 | 1650 | 12000 | 0.6 | 4.5 | 1960 | 1170 | 1730 | 3330 |
| S10-M-1600/10 | 1600 | 2040 | 14500 | 0.5 | 4.5 | 2325 | 1220 | 2120 | 3765 |
| S10-M-2000/10 | 2000 | 2140 | 17820 | 0.5 | 4.5 | 2395 | 1260 | 2225 | 4530 |
>>S11 series 20KV three phase off -load tap changer distribution transformer
| TYPE | Voltage ratio(kV) | Connection | No load Loss (W) |
Load loss (W) |
Io (%) |
UK (%) |
Dimensions (mm) | Weight (Kg) | |||||
| a | b | c | d | e | f | ||||||||
| S11-M-30/20 | 20(10) ±5%/0.4 |
Yyn0 Dyn11 |
100 | 690/ 660 |
2.1 | 5.5 |
1100 | 700 | 1240 | 14 | 400 | 400 | 640 |
| S11-M-50/20 | 130 | 1010/ 960 |
2.0 | 1130 | 710 | 1260 | 14 | 400 | 450 | 710 | |||
| S11-M-63/20 | 150 | 1200/1150 | 1.9 | 1160 | 740 | 1270 | 14 | 400 | 450 | 780 | |||
| S11-M-80/20 | 180 | 1440/1370 | 1.8 | 1200 | 770 | 1280 | 14 | 400 | 450 | 860 | |||
| S11-M-100/20 | 200 | 1730/ 1650 |
1.6 | 1220 | 800 | 1300 | 14 | 400 | 450 | 900 | |||
| S11-M-125/20 | 240 | 2080/ 1980 |
1.5 | 1270 | 840 | 1330 | 19 | 550 | 450 | 970 | |||
| S11-M-160/20 | 290 | 2540/ 2420 |
1.4 | 1320 | 870 | 1350 | 19 | 550 | 550 | 1100 | |||
| S11-M-200/20 | 340 | 3000/ 2860 |
1.3 | 1360 | 900 | 1380 | 19 | 550 | 550 | 1240 | |||
| S11-M-250/20 | 400 | 3520/ 3350 |
1.2 | 1430 | 910 | 1430 | 19 | 550 | 650 | 1420 | |||
| S11-M-315/20 | 480 | 4210/ 4010 |
1.1 | 1460 | 920 | 1450 | 19 | 550 | 650 | 1570 | |||
| S11-M-400/20 | 570 | 4970/ 4730 |
1.0 | 1490 | 940 | 1470 | 19 | 660 | 750 | 1740 | |||
| S11-M-500/20 | 680 | 5940/ 5660 |
1.0 | 1570 | 970 | 1540 | 19 | 660 | 750 | 1950 | |||
| S11-M-630/20 | 810 | 6820 | 0.9 | 6.0 |
1650 | 1000 | 1580 | 19 | 660 | 850 | 2290 | ||
| S11-M-800/20 | 980 | 8250 | 0.8 | 1750 | 1070 | 1650 | 19 | 820 | 850 | 2690 | |||
| S11-M-1000/20 | 1150 | 11330 | 0.7 | 1830 | 1170 | 1690 | 19 | 820 | 850 | 2880 | |||
| S11-M-1250/20 | 1380 | 13200 | 0.7 | 1900 | 1200 | 1790 | 19 | 820 | 850 | 3400 | |||
| S11-M-1600/20 | 1660 | 15950 | 0.6 | 1950 | 1250 | 1850 | 19 | 820 | 900 | 4100 | |||
>>>>S9 series 35kV three phase Off-load tap changer power transformer
| Capacity KVA |
Voltage and tap range | Connection | No-load loss (kW) |
Load loss (KW) |
NO-load current (%) |
Impedance (%) |
Dimensions (mm) LxWxH |
||
| HV (kV) | MV (kV) | LV (kV) | |||||||
| 50 | 35 | ± 5 | 0.4 | Dyn11 Yyn0 |
0.21 | 1.27/1.21 | 2.00 | 6.5 | 1100x845x1715 |
| 100 | 0.29 | 2.12/2.02 | 1.80 | 1190x915x1780 | |||||
| 125 | 0.34 | 2.50/2.38 | 1.70 | 1220x1040x1780 | |||||
| 160 | 0.36 | 2.97/2.83 | 1.60 | 1240x1070x1810 | |||||
| 200 | 0.43 | 3.50/3.33 | 1.50 | 1380x780x1875 | |||||
| 250 | 0.51 | 4.16/3.96 | 1.40 | 1540x880x1820 | |||||
| 315 | 0.61 | 5.01/4.77 | 1.40 | 1440x800x1975 | |||||
| 400 | 0.73 | 6.05/5.76 | 1.30 | 1660x825x1995 | |||||
| 500 | 0.86 | 7.28/6.93 | 1.20 | 1710x865x2030 | |||||
| 630 | 1.04 | 8.28 | 1.10 | 1630x1235x2070 | |||||
| 800 | 1.23 | 9.90 | 1.00 | 1655x1415x2120 | |||||
| 1000 | 1.44 | 12.15 | 1.00 | 1860x1435x2220 | |||||
| 1250 | 1.76 | 14.67 | 0.90 | 1890x1640x2260 | |||||
| 1600 | 2.12 | 17.55 | 0.80 | 2050x1720x2390 | |||||
| 630 | 3.15 6.3 10.5 |
Yd11 | 1.04 | 8.28 | 1.10 | 1630x1235x2070 | |||
| 800 | 1.23 | 9.90 | 1.00 | 1655x1415x2120 | |||||
| 1000 | 1.44 | 12.15 | 1.00 | 1860x1435x2220 | |||||
| 1250 | 1.76 | 14.67 | 0.90 | 1890x1640x2260 | |||||
| 1600 | 2.12 | 17.55 | 0.80 | 2050x1720x2390 | |||||
| 2000 | 2.72 | 19.35 | 0.70 | 2400x1900x2410 | |||||
| 2500 | 3.20 | 20.70 | 0.60 | 2500x1930x2700 | |||||
| 3150 | 35~ 38.5 |
± 5 | 3.15 6.3 10.5 |
3.80 | 24.30 | 0.56 | 7.0 | 2600x2100x2800 | |
| 4000 | 4.52 | 28.80 | 0.56 | 2830 x2350x2855 | |||||
| 5000 | 5.40 | 33.03 | 0.48 | 2930x2480x2930 | |||||
| 6300 | 6.56 | 36.90 | 0.48 | 7.5 | 3150x2330x3220 | ||||
| 8000 | ± 2 x 2.5 | 3.15 3.3 6.3 6.6 10.5 11 |
YNd11 | 9.00 | 40.50 | 0.42 | 3295x3110x3345 | ||
| 10000 | 10.88 | 47.70 | 0.42 | 3450x3210x3440 | |||||
| 12500 | 12.60 | 56.70 | 0.40 | 8.0 | 3620x3255x3500 | ||||
| 16000 | 15.20 | 69.30 | 0.40 | 3980x3420x3650 | |||||
| 20000 | 18.00 | 83.70 | 0.40 | 4030x3470x3690 | |||||
| 25000 | 21.28 | 99.00 | 0.32 | 5050x4640x3930 | |||||
| 31500 | 25.28 | 118.8 | 0.32 | 5120x4800x4030 | |||||
>>>>S9 series 35kV three phase on-load tap changer power transformer
| Type | Voltage compose and Tapping range (kV) | Connection |
No-load Loss (kW) |
Load loss (kW) |
No- load current (I%) |
Impedance voltage (%) | Transport weight (t) | Gross weight (t) | Dimensions L×W×H (mm) |
|
| HV | LV | |||||||||
| SZ9-2000/35 | 35 ±3×2.5% |
6.3 10.5 |
Yd11 | 2.88 | 18.7 | 1.00 | 6.5 | 4.93 | 5.97 | 3010×2070×2540 |
| SZ9-2500/35 | 3.40 | 21.7 | 1.00 | 6.5 | 5.68 | 6.95 | 3040×2270×2610 | |||
| SZ9-3150/35 | 4.04 | 26.0 | 0.90 | 7.0 | 6.08 | 7.90 | 3160×2300×2640 | |||
| SZ9-4000/35 | 35 38.5 ±3×2.5% |
6.3 10.5 |
4.84 | 30.7 | 0.90 | 7.0 | 7.10 | 9.11 | 3300×2330×2890 | |
| SZ9-5000/35 | 5.80 | 36.0 | 0.85 | 7.0 | 8.47 | 10.86 | 3350×2520×3000 | |||
| SZ9-6300/35 | 7.04 | 38.7 | 0.85 | 7.5 | 9.87 | 12.30 | 3680×2650×3050 | |||
| SZ9-8000/35 | 9.84 | 42.8 | 0.75 | 7.5 | 12.55 | 15.30 | 4190×2930×3280 | |||
| SZ9-10000/35 | 35 38.5 ±3×2.5% |
6.3 6.6 10.5 11 |
Ynd11 |
11.6 | 50.6 | 0.75 | 7.5 | 14.70 | 17.86 | 4620×3160×3400 |
| SZ9-12500/35 | 13.7 | 60.0 | 0.70 | 8.0 | 17.35 | 20.05 | 4740×3200×3540 | |||
| SZ9-16000/35 | 16.0 | 73.0 | 0.70 | 8.0 | 19.45 | 23.74 | 4810×3360×3790 | |||
| SZ9-20000/35 | 18.9 | 88.3 | 0.70 | 8.0 | 27.50 | 34.95 | 4880×3540×4150 | |||
| SZ9-25000/35 | 22.4 | 104.4 | 0.65 | 8.0 | 32.51 | 40.22 | 4920×3920×4200 | |||
| SZ9-31500/35 | 26.6 | 125.3 | 0.65 | 8.0 | 37.73 | 45.53 | 5010×4270×4460 | |||
We are China Traction Transformer Tap Changing Oltc 33kv manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Oil Transformet Products
33kv S11 Type off-Circuit Tap Changer Transformers
Pad Mounted Three Phase; Compact Type Distribution Transformer
Single Phase Overhead Step up Step Down Distribution Transformer 11kv
Intelligent Capacity Regulate and Tap Change Oil Immersed Transformer
Step Voltage Regulator 11kv Voltage Stabilizer
Amorphous Alloy Oil-Immersed Distribution Transformer 11kv Power Distribution
Popular Power Transformer Products
Vacuum Resin Cast Dry Transformer
Oil Immersed Distribution Transformer 24kv IEC Standard
3kV/6300A DIN 42539 Porcelain Transformer Bushing Insulator
630-3150kVA 11kv Dimension with Protection Enclosure
69kv 66kv Oil-Immersed Power Transformer
11kv Scb10-630~3150kVA Distribution Transformer
Popular Rectifier Transformer Products
3D Delta Core Dry-Type Transformer29
Zhstk-13000/110 12.85mva/18.1mva 110kv Electrolyed Electro-Chemistry Rectifier Transformer
110kv and Above Rectifier Special Transformer
Energy Saving Delta Core Oil Immersed Transformer
Amorphous Alloy Oil-Immersed Power Distribution Transformer
66kv and 69kv Rectifier Special Transformer
Popular silverstone-electric Products
33kv 80kn Cantilever Suspension Composite Insulator Catenary Type
33kv Dry Type Power Transformers with off-Circuit Switch
100kVA Micro Power Pole Mounted Distribution Transformer
U300 150kn High Voltage Disk Suspension Toughened Glass Insulator IEC
Resin Post Support Insulator APG Cast Epoxy Insulator
Current Ceramic Transformer Bushing Porcelain Insulator
Tags: Oil Transformet, Power Transformer, Rectifier Transformer, silverstone-electric