33kv Double Pole Drop out Fuse
33kv Double Pole Drop out Fuse image
Get Latest Price Request a quote
Quick Details
Product Details
Features
Performance Data
Porcelain housed for outdoor application
CONSTRUCTION & OPERATING PRINCIPLE
11kV
| No. | DETAIL | UNITS | DATA |
| Type | 11kV gapless type metal oxide surge arrester – Distribution class |
||
| 1. | Nominal system voltage | kV | 11 |
| 2. | Highest system voltage | kV | 12 |
| 3. | Basic Insulation Level (BIL) | kV | 95 |
| 3. Ratings and type of surge arrester |
|||
| 4. | Specification to which surge arrester complies | IEC 60099–4 |
|
| 5. | Rated voltage of surge arrester | kV | 10 |
| 6. | Nominal, 8/20 µs, discharge current rating of surge arrester |
kA | 10 |
| 7. | Maximum continuous operating voltage of surge arrester |
kV | 7.3 |
| 8. | Gapless or gapped type metal–oxide surge arrester |
Gapless | |
| 9. | Material of insulation | High temperature vulcanised silicon rubber |
|
| 10. | Rated frequency of surge arrester | Hz | 50 |
| 11. | Design altitude of surge arrester (above sea level) |
m | 1 400m |
| 12. | Design ambient temperature of surge arrester | oC | –1 to40 |
| 13. | Specific creepage distance of surge arrester | .mm/kV | 25 |
| Automatic earth lead disconnectors requirements |
|||
| 14. | Automatic earth lead disconnectors to be fitted | Yes/No | YES |
| 15. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
To SABS 763, 316 | |
| Tests | |||
| 16. | Previous type test results/certificate to be provided with bid |
Yes/No | Yes |
| 17. | Routine test results/certificate to be provided on delivery |
Yes/No | Yes |
| 18. | Drawing showing dimensions of the arrestor to be provided with the bid |
Yes/No | Yes |
| 19. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kV | 28 |
| 20. | Maximum steep current impulse residual voltage for a 10 kA, 1/20 µs, discharge current |
kV | 50 |
| 21. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kV | 40 |
| 22. | Lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
kV | 95 |
| 23. | Line discharge class rating | 1 | |
| 24. | Long duration current, 2 000 µs, impulse withstand |
A | 250 A |
| 25. | High current, 4/10 µs, impulse withstand | kA | 100 kA |
| 26. | Automatic earth lead disconnector to be tested in accordance with IEC 60099–4 |
Yes/No | Yes |
33kV
| S/N | TECHNICAL DETAILS | UNITS | DATA | |
| 1. | Type | 33kV gapless type metal oxide surge arrester – Distribution class |
||
| 2. | Nominal system voltage | kV | 33 | |
| 3. | Highest system voltage | kV | 36 | |
| 4. | Power frequency | Hz | 50 | |
| 5. | Basic Insulation Level (BIL) | kV | 170 | |
| 3. Ratings and type of surge arrester |
||||
| 6. | Specification to which surge arrester complies | IEC 60099 | ||
| 7. | Rated voltage of surge arrester | kV | 29 | |
| 8. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA | 10 | |
| 9. | Maximum continuous operating voltage of surge arrester | kV | 22 | |
| 10. | Gapless or gapped type metal–oxide surge arrester | Gapless | ||
| 11. | Insulation Material | Silicon rubber | ||
| 12. | Cantilever strength of surge arrester | Nm | 300 | |
| 13. | Rated frequency of surge arrester | Hz | 50 | |
| 14. | Design altitude of surge arrester (above sea level) | m | 1 400m | |
| 15. | Design ambient temperature of surge arrester | oC | –1 to 40 | |
| 16. | Minimum phase–to–ground specific creepage distance of surge arrester |
.mm/kV | 25 | |
| Automatic earth lead disconnectors requirements | ||||
| 17. | Automatic earth lead disconnectors fitted | Yes/No | Yes | |
| 18. | Corrosion protection of metal and alloy parts: galvanising | To SABS 763, 316 | ||
| specification and/or stainless steel grade | |||
| Tests | |||
| 19. | Previous Type Test reports/certificate from recognized authority to be provided with bid |
Yes/No | Yes |
| 20. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kV | 70 |
| 21. | Maximum steep current impulse residual voltage for a 10 kA, 1/20 µs, discharge current |
kV | 99.7 |
| 22. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kV | 91.8 |
| 23. | Lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
kV | 170 |
| 24. | Line discharge class rating | Class | 1 |
| 25. | Long duration current, 2 000 µs, impulse withstand | A | 250 A |
| 26. | High current, 4/10 µs, impulse withstand | kA | 100 kA |
| 27. | Is the automatic earth lead disconnector tested in accordance with IEC 60099–4? |
Yes/No | Yes |
66kV
| S/N | TECHNICAL DETAILS | UNITS | DATA |
| 1. | Description | Station type lightning arrestor complete with steel support structures. |
|
| 2. | Type | Zinc oxide gapless lightning arrestor |
|
| System parameters | |||
| 3. | Nominal system voltage | kV | 66 |
| 4. | Highest system voltage | kV | 72.5 |
| 5. | Power frequency | Hz | 50 |
| 6. | Type of system earthing | Effective/Non effective | |
| 7. | Type of arrestor connection to system | Line to ground | |
| 3. Ratings and type of surge arrester |
|||
| 8. | Rated voltage of surge arrester | kV rms | 54 |
| 9. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
| 10. | Maximum continuous operating voltage of surge arrester | kV | 43 |
| 11. | Minimum one minute wet power frequency withstand voltage | kVrms | 140 |
151
| of external insulation of surge arrester housing | |||
| 12. | Maximum steep current impulse residual voltage for a 2 kA, 30/60 µs, discharge current |
kVpeak | 104 |
| 13. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kVpeak | 127 |
| 14. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
325 | |
| 15. | Line discharge class rating | 2 | |
| 16. | Lighting arrestor counter, leakage current meter and their accessories to be provided |
Yes/No | Yes |
| 17. | Gapless or gapped type metal–oxide surge arrester | Gapless | |
| 18. | Insulation Material | Porcelain | |
| 19. | Cantilever strength of surge arrester | Nm | 3000 |
| 20. | Rated frequency of surge arrester | Hz | 50 |
| 21. | Maximum angle from vertical at which surge arrester is fully functional |
Deg | 45 |
| 22. | Design altitude of surge arrester (above sea level) | m | 1400 m |
| 23. | Design ambient temperature of surge arrester | oC | –1 to 40 |
| 24. | Humidity | % | 85 |
| 25. | Specific phase–to–ground creepage of surge arrester | .mm/kV | 25 |
| 26. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
to SABS 763 or 316 stainless steel |
|
| 27. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
| 28. | Design drawings showing dimensions including foundations and brochures to be provided with bid |
Yes/No | Yes |
| 29. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
| 30. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
| 31. | Galvanized steel support structures complete with bolts & washers to be provided on delivery |
Yes/No | Yes |
| 32. | Applicable standard | IEC60099 |
152
88Kv
| S/N | TECHNICAL DETAILS | UNITS | DATA |
| 33. | Description | Station type lightning arrestor complete with steel support structures. |
|
| 34. | Type | Zinc oxide gapless lightning arrestor |
|
| System parameters | |||
| 35. | Nominal system voltage | kV | 88 |
| 36. | Highest system voltage | kV | 100 |
| 37. | Power frequency | Hz | 50 |
| 38. | Type of system earthing | Effective/Non effective | |
| 39. | Type of arrestor connection to system | Line to ground | |
| 3. Ratings and type of surge arrester |
|||
| 40. | Rated voltage of surge arrester | kV rms | 84 |
| 41. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
| 42. | Maximum continuous operating voltage of surge arrester | kV | 67 |
| 43. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kVrms | 185 |
| Maximum steep current impulse residual voltage for a 2 kA, | kVpeak | 188 | |
| 30/60 µs, discharge current | |||
| 45. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kVpeak | 218 |
| 46. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
450 | |
| 47. | Line discharge class rating | 2 | |
| 48. | Lighting arrestor counter, leakage current meter and their accessories to be provided |
Yes/No | Yes |
| 49. | Gapless or gapped type metal–oxide surge arrester | Gapless | |
| 50. | Insulation Material | Porcelain | |
| 51. | Cantilever strength of surge arrester | Nm | 3000 |
| 52. | Rated frequency of surge arrester | Hz | 50 |
| 53. | Maximum angle from vertical at which surge arrester is fully functional |
Deg | 45 |
| 54. | Design altitude of surge arrester (above sea level) | m | 1400 m |
| 55. | Design ambient temperature of surge arrester | oC | –1 to 40 |
| 56. | Humidity | % | 85 |
| 57. | Specific phase–to–ground creepage of surge arrester | .mm/kV | 25 |
| 58. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
to SABS 763 or 316 stainless steel |
|
| 59. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
| 60. | Design drawings showing dimensions including foundations and brochures to be provided with bid |
Yes/No | Yes |
| 61. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
| 62. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
| 63. | Galvanized steel support structures complete with bolts & washers to be provided on delivery |
Yes/No | Yes |
| 64. | Applicable standard | IEC60099 |
We are China 33kv Double Pole Drop out Fuse manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular jgtrade1 Products
Sleeve; Alum Tube Service Ysu 2W 4W
Terminal Connectors for Double Conductors Bolted Type, Type Ssl, Group a
Popular Lightning Arrester Products
10ka Polymer Type Gapless Lightning Arrester / Surge Arrester Moa
9-12kv Polymer Surge Arrester, Lightning Arrester
Hy5w-3.8/17 Zinc-Oxide Arrester
Kema 11kv Surge Arrestor Zinc Oxide Lightning Arresters
Popular Lightning Arrestors Products
High -Voltage Disconnect Switch 60kv 600A
Polymer Fuse Cutout, Drop out Fuses 96 Kv 100A
Fuse Cutout, Drop out Fuses 72kv 300A
Popular Surge Arrester Products
IEC Standard High Voltage Zinc Oxide Lightning Arrester
High Voltage Transmission Line Equipment Station Arrester with Disconnector
Yh10W-12, Sharp Head 10kv 12ka Surge Arrester
Ceramic Polymeric 36kv Lightning Arrester for Lightning Protection
Surge Protection Device Lightning Arrester
Tags: jgtrade1, Lightning Arrester, Lightning Arrestors, Surge Arrester