Fuse Link, 6 AMPS -T
Fuse Link, 6 AMPS -T image
Get Latest Price Request a quote
Quick Details
Product Details
| Type | Order No. | Order No. | Rated voltage | Rated current | Length | Diameter | Breaking capacity | Min.breakk- ing current | Resistance | Power Dissipation | Weight | ||||
| 60N | 80N | kV | A | L, mm | D, mm | I1, kA | I3, A | R, mΩ | P, W | kg | |||||
| VvP 3/7,2kV 2A 192/53 | 1607002 | 1807002 | 3/7,2 | 2 | 192 | 53 | 50 | 15 | 340 | 3 | 1.3 | ||||
| VvP 3/7,2kV 4A 192/53 | 1607004 | 1807004 | 3/7,2 | 4 | 192 | 53 | 50 | 18 | 290 | 6 | 1.3 | ||||
| VvP 3/7,2kV 6.3A 192/53 | 1607006 | 1807006 | 3/7,2 | 6,3 | 192 | 53 | 50 | 25 | 220 | 12 | 1.3 | ||||
| VvP 3/7,2kV 10A 192/53 | 1607010 | 1807010 | 3/7,2 | 10 | 192 | 53 | 50 | 50 | 61 | 7 | 1.3 | ||||
| VvP 3/7,2kV 16A 192/53 | 1607016 | 1807016 | 3/7,2 | 16 | 192 | 53 | 50 | 63 | 38 | 12 | 1.3 | ||||
| VvP 3/7,2kV 20A 192/53 | 1607020 | 1807020 | 3/7,2 | 20 | 192 | 53 | 50 | 90 | 33 | 11 | 1.3 | ||||
| VvP 3/7,2kV 25A 192/53 | 1607025 | 1807025 | 3/7,2 | 25 | 192 | 53 | 50 | 105 | 28 | 11 | 1.3 | ||||
| VvP 3/7,2kV 31,5A 192/53 | 1607032 | 1807032 | 3/7,2 | 31,5 | 192 | 53 | 50 | 119 | 19 | 20 | 1.3 | ||||
| VvP 3/7,2kV 40A 192/53 | 1607040 | 1807040 | 3/7,2 | 40 | 192 | 53 | 50 | 137 | 11 | 22 | 1.3 | ||||
| VvP 3/7,2kV 50A 192/69 | 1607050 | 1807050 | 3/7,2 | 50 | 192 | 69 | 50 | 210 | 10 | 37 | 1.9 | ||||
| VvP 3/7,2kV 63A 192/69 | 1607063 | 1807063 | 3/7,2 | 63 | 192 | 69 | 50 | 255 | 7 | 46 | 1.9 | ||||
| VvP 3/7,2kV 80A 192/69 | 1607080 | 1807080 | 3/7,2 | 80 | 192 | 69 | 50 | 321 | 5 | 57 | 1.9 | ||||
| VvP 3/7,2kV 100A 192/85 | 1607100 | 1807100 | 3/7,2 | 100 | 192 | 85 | 50 | 420 | 4 | 86 | 2.6 | ||||
| VvP 3/7,2kV 125A 192/85 | 1607125 | 1807125 | 3/7,2 | 125 | 192 | 85 | 50 | 452 | 2.5 | 98 | 2.6 | ||||
| VvP 3/7,2kV 160A 192/85 | 1607160 | 1807160 | 3/7,2 | 160 | 192 | 85 | 50 | 560 | 2 | 130 | 2.6 | ||||
| VvP 3/7,2kV 200A 192/85 | 1607200 | 1807200 | 3/7,2 | 200 | 192 | 85 | 50 | 730 | 1.5 | 225 | 2.6 | ||||
| VvP 6/12kV 2A 292/53 | 1610002 | 1810002 | 6/12 | 2 | 292 | 53 | 63 | 17 | 585 | 2 | 1.7 | ||||
| VvP 6/12kV 4A 292/53 | 1610004 | 1810004 | 6/12 | 4 | 292 | 53 | 63 | 23 | 537 | 7 | 1.7 | ||||
| VvP 6/12kV 6.3A 292/53 | 1610006 | 1810006 | 6/12 | 6,3 | 292 | 53 | 63 | 32 | 405 | 10 | 1.7 | ||||
| VvP 6/12kV 10A 292/53 | 1610010 | 1810010 | 6/12 | 10 | 292 | 53 | 63 | 50 | 137 | 17 | 1.7 | ||||
| VvP 6/12kV 16A 292/53 | 1610016 | 1810016 | 6/12 | 16 | 292 | 53 | 63 | 61 | 96 | 40 | 1.7 | ||||
| VvP 6/12kV 20A 292/53 | 1610020 | 1810020 | 6/12 | 20 | 292 | 53 | 63 | 80 | 51 | 40 | 1.7 | ||||
| VvP 6/12kV 25A 292/53 | 1610025 | 1810025 | 6/12 | 25 | 292 | 53 | 63 | 101 | 48 | 48 | 1.7 | ||||
| VvP 6/12kV 31,5A 292/53 | 1610032 | 1810032 | 6/12 | 31,5 | 292 | 53 | 63 | 116 | 45 | 67 | 1.7 | ||||
| VvP 6/12kV 40A 292/53 | 1610040 | 1810040 | 6/12 | 40 | 292 | 53 | 63 | 145 | 26 | 70 | 1.7 | ||||
| VvP 6/12kV 50A 292/69 | 1610050 | 1810050 | 6/12 | 50 | 292 | 69 | 63 | 240 | 18 | 81 | 2.6 | ||||
| VvP 6/12kV 63A 292/69 | 1610063 | 1810063 | 6/12 | 63 | 292 | 69 | 50 | 315 | 12 | 93 | 2.6 | ||||
| VvP 6/12kV 80A 292/69 | 1610080 | 1810080 | 6/12 | 80 | 292 | 69 | 50 | 370 | 8 | 115 | 2.6 | ||||
| VvP 6/12kV 100A 292/85 | 1610100 | 1810100 | 6/12 | 100 | 292 | 85 | 50 | 420 | 7 | 158 | 3.7 | ||||
| VvP 6/12kV 125A 292/85 | 1610125 | 1810125 | 6/12 | 125 | 292 | 85 | 50 | 490 | 5 | 170 | 3.7 | ||||
| VvP 6/12kV 160A 292/85 | 1610160 | 1810160 | 6/12 | 160 | 292 | 85 | 50 | 800 | 3 | 220 | 3.7 | ||||
| VvP 6/12kV 200A 292/85 | 1610200 | 1810200 | 6/12 | 200 | 292 | 85 | 50 | 1000 | 2 | 341 | 3.7 | ||||
| VvP 10/17.5kV 2А 53/367 | 1617002 | 1817002 | 10/17.5 | 2 | 367 | 53 | 50 | 16 | 980 | 4 | 2.0 | ||||
| VvP 10/17.5kV 4А 53/367 | 1617004 | 1817004 | 10/17.5 | 4 | 367 | 53 | 50 | 22 | 731 | 10 | 2.0 | ||||
| VvP 10/17.5kV 6.3А 53/367 | 1617006 | 1817006 | 10/17.5 | 6.3 | 367 | 53 | 50 | 30 | 550 | 13 | 2.0 | ||||
| VvP 10/17.5kV 10А 53/367 | 1617010 | 1817010 | 10/17.5 | 10 | 367 | 53 | 50 | 44 | 207 | 22 | 2.0 | ||||
| VvP 10/17.5kV 16А 53/367 | 1617016 | 1817016 | 10/17.5 | 16 | 367 | 53 | 50 | 62 | 117 | 55 | 2.0 | ||||
| VvP 10/17.5kV 20А 53/367 | 1617020 | 1817020 | 10/17.5 | 20 | 367 | 53 | 50 | 78 | 68 | 56 | 2.0 | ||||
Maximum altitude above mean sea level less than 1,000 m;
Maximum ambient air temperature 400C;
Maximum daily average ambient air temperature 300C;
Minimum ambient temperature150C; and
Maximum relative humidity 100%.
Requirements
The fuse-links and fuse-end fittings shall be of the following ratings (table below) and comply with the IEEE Std C37.4 -2016 or an equivalent international standard. The fuse- links shall be used primarily for protection of distribution transformers, laterals and sub- laterals.
The fuse links shall be capable of withstanding 125% ofthe transformer rated full load current continuously and periodic over-loads up to 150% ofthe transformer rated full load current.
The current-time characteristics of the fuse-links offered shall be submitted with the tender
Markings shall be provided on the fuse-links in accordance with ANSI/IEEE Standards.
Recommended for You
Not exactly what you want?
Post Sourcing Request
Hot Searches
Power Fuse
Voltage Fuse
Protection Fuse
Fuse Box
Fast Fuse
We are China Fuse Link, 6 AMPS -T manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Fuse Link Products
Imprint Nitrile Glovespolyester/Nyloncolorful 7-11
PVC Glovessmooth Finishred 27cm
Splicing Sleeves for Aluminium Conductor Compression with Pliers
Popular High Voltage Fuse Products
High Voltage Dropout Fuse or Fuse Cutout (Vc-6) , Silicon Dropout, Silicon Fuse Cutout, Fuse Cutout
Polymer Fuse Cutout, Drop out Fuses 33kv 100A
Popular jgtrade1 Products
PVC Gloves Sandy Finish Green 30cm
Terminal Connectors for Double Conductors Type Ssy, Compression Type
72.5kv 110kv 126kv 132kv 145kv Gw4 Outdoor High Voltage Disconnector
Dead End Clamp for Self Supporting LV. ABC
Yh10W-84, 84kv 10ka Surge Arrester
Popular Outdoor Products
Polyester Glove Nitrie Coated, Smooth Finish, (black)
Imprint Nitrile Glovespolyester/Nyloncolorful 7-11
High Temperature-Resistant Gloves (Kevlar)
PE/PVC Insulated 2 Core 4core Outdoor Telephone Twin Flat Drop Wire
Cowhide Split Leather Welding Gloves
Tags: Fuse Link, High Voltage Fuse, jgtrade1, Outdoor