Maximum altitude above mean sea level less than 1,000 m;
Maximum ambient air temperature 400C;
Maximum daily average ambient air temperature 300C;
Minimum ambient temperature150C; and
Maximum relative humidity 100%.
Requirements
The fuse-links and fuse-end fittings shall be of the following ratings (table below) and comply with the IEEE Std C37.4 -2016 or an equivalent international standard. The fuse- links shall be used primarily for protection of distribution transformers, laterals and sub- laterals.
The fuse links shall be capable of withstanding 125% ofthe transformer rated full load current continuously and periodic over-loads up to 150% ofthe transformer rated full load current.
The current-time characteristics of the fuse-links offered shall be submitted with the tender
Markings shall be provided on the fuse-links in accordance with ANSI/IEEE Standards.
METAL OXIDE SURGE ARRESTER
Features
Performance Data
Porcelain housed for outdoor application
CONSTRUCTION & OPERATING PRINCIPLE
| No. | DETAIL | UNITS | DATA |
| Type | 11kV gapless type metal oxide surge arrester – Distribution class |
||
| 1. | Nominal system voltage | kV | 11 |
| 2. | Highest system voltage | kV | 12 |
| 3. | Basic Insulation Level (BIL) | kV | 95 |
| 3. Ratings and type of surge arrester |
|||
| 4. | Specification to which surge arrester complies | IEC 60099–4 |
|
| 5. | Rated voltage of surge arrester | kV | 10 |
| 6. | Nominal, 8/20 µs, discharge current rating of surge arrester |
kA | 10 |
| 7. | Maximum continuous operating voltage of surge arrester |
kV | 7.3 |
| 8. | Gapless or gapped type metal–oxide surge arrester |
Gapless | |
| 9. | Material of insulation | High temperature vulcanised silicon rubber |
|
| 10. | Rated frequency of surge arrester | Hz | 50 |
| 11. | Design altitude of surge arrester (above sea level) |
m | 1 400m |
| 12. | Design ambient temperature of surge arrester | oC | –1 to40 |
| 13. | Specific creepage distance of surge arrester | .mm/kV | 25 |
| Automatic earth lead disconnectors requirements |
|||
| 14. | Automatic earth lead disconnectors to be fitted | Yes/No | YES |
| 15. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
To SABS 763, 316 | |
| Tests | |||
| 16. | Previous type test results/certificate to be provided with bid |
Yes/No | Yes |
| 17. | Routine test results/certificate to be provided on delivery |
Yes/No | Yes |
| 18. | Drawing showing dimensions of the arrestor to be provided with the bid |
Yes/No | Yes |
| 19. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kV | 28 |
| 20. | Maximum steep current impulse residual voltage for a 10 kA, 1/20 µs, discharge current |
kV | 50 |
| 21. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kV | 40 |
| 22. | Lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
kV | 95 |
| 23. | Line discharge class rating | 1 | |
| 24. | Long duration current, 2 000 µs, impulse withstand |
A | 250 A |
| 25. | High current, 4/10 µs, impulse withstand | kA | 100 kA |
| 26. | Automatic earth lead disconnector to be tested in accordance with IEC 60099–4 |
Yes/No | Yes |
| S/N | TECHNICAL DETAILS | UNITS | DATA | |
| 1. | Type | 33kV gapless type metal oxide surge arrester – Distribution class |
||
| 2. | Nominal system voltage | kV | 33 | |
| 3. | Highest system voltage | kV | 36 | |
| 4. | Power frequency | Hz | 50 | |
| 5. | Basic Insulation Level (BIL) | kV | 170 | |
| 3. Ratings and type of surge arrester |
||||
| 6. | Specification to which surge arrester complies | IEC 60099 | ||
| 7. | Rated voltage of surge arrester | kV | 29 | |
| 8. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA | 10 | |
| 9. | Maximum continuous operating voltage of surge arrester | kV | 22 | |
| 10. | Gapless or gapped type metal–oxide surge arrester | Gapless | ||
| 11. | Insulation Material | Silicon rubber | ||
| 12. | Cantilever strength of surge arrester | Nm | 300 | |
| 13. | Rated frequency of surge arrester | Hz | 50 | |
| 14. | Design altitude of surge arrester (above sea level) | m | 1 400m | |
| 15. | Design ambient temperature of surge arrester | oC | –1 to 40 | |
| 16. | Minimum phase–to–ground specific creepage distance of surge arrester |
.mm/kV | 25 | |
| Automatic earth lead disconnectors requirements | ||||
| 17. | Automatic earth lead disconnectors fitted | Yes/No | Yes | |
| 18. | Corrosion protection of metal and alloy parts: galvanising | To SABS 763, 316 | ||
| specification and/or stainless steel grade | |||
| Tests | |||
| 19. | Previous Type Test reports/certificate from recognized authority to be provided with bid |
Yes/No | Yes |
| 20. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kV | 70 |
| 21. | Maximum steep current impulse residual voltage for a 10 kA, 1/20 µs, discharge current |
kV | 99.7 |
| 22. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kV | 91.8 |
| 23. | Lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
kV | 170 |
| 24. | Line discharge class rating | Class | 1 |
| 25. | Long duration current, 2 000 µs, impulse withstand | A | 250 A |
| 26. | High current, 4/10 µs, impulse withstand | kA | 100 kA |
| 27. | Is the automatic earth lead disconnector tested in accordance with IEC 60099–4? |
Yes/No | Yes |
| S/N | TECHNICAL DETAILS | UNITS | DATA |
| 1. | Description | Station type lightning arrestor complete with steel support structures. |
|
| 2. | Type | Zinc oxide gapless lightning arrestor |
|
| System parameters | |||
| 3. | Nominal system voltage | kV | 66 |
| 4. | Highest system voltage | kV | 72.5 |
| 5. | Power frequency | Hz | 50 |
| 6. | Type of system earthing | Effective/Non effective | |
| 7. | Type of arrestor connection to system | Line to ground | |
| 3. Ratings and type of surge arrester |
|||
| 8. | Rated voltage of surge arrester | kV rms | 54 |
| 9. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
| 10. | Maximum continuous operating voltage of surge arrester | kV | 43 |
| 11. | Minimum one minute wet power frequency withstand voltage | kVrms | 140 |
| of external insulation of surge arrester housing | |||
| 12. | Maximum steep current impulse residual voltage for a 2 kA, 30/60 µs, discharge current |
kVpeak | 104 |
| 13. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kVpeak | 127 |
| 14. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
325 | |
| 15. | Line discharge class rating | 2 | |
| 16. | Lighting arrestor counter, leakage current meter and their accessories to be provided |
Yes/No | Yes |
| 17. | Gapless or gapped type metal–oxide surge arrester | Gapless | |
| 18. | Insulation Material | Porcelain | |
| 19. | Cantilever strength of surge arrester | Nm | 3000 |
| 20. | Rated frequency of surge arrester | Hz | 50 |
| 21. | Maximum angle from vertical at which surge arrester is fully functional |
Deg | 45 |
| 22. | Design altitude of surge arrester (above sea level) | m | 1400 m |
| 23. | Design ambient temperature of surge arrester | oC | –1 to 40 |
| 24. | Humidity | % | 85 |
| 25. | Specific phase–to–ground creepage of surge arrester | .mm/kV | 25 |
| 26. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
to SABS 763 or 316 stainless steel |
|
| 27. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
| 28. | Design drawings showing dimensions including foundations and brochures to be provided with bid |
Yes/No | Yes |
| 29. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
| 30. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
| 31. | Galvanized steel support structures complete with bolts & washers to be provided on delivery |
Yes/No | Yes |
| 32. | Applicable standard | IEC60099 |
| S/N | TECHNICAL DETAILS | UNITS | DATA |
| 33. | Description | Station type lightning arrestor complete with steel support structures. |
|
| 34. | Type | Zinc oxide gapless lightning arrestor |
|
| System parameters | |||
| 35. | Nominal system voltage | kV | 88 |
| 36. | Highest system voltage | kV | 100 |
| 37. | Power frequency | Hz | 50 |
| 38. | Type of system earthing | Effective/Non effective | |
| 39. | Type of arrestor connection to system | Line to ground | |
| 3. Ratings and type of surge arrester |
|||
| 40. | Rated voltage of surge arrester | kV rms | 84 |
| 41. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
| 42. | Maximum continuous operating voltage of surge arrester | kV | 67 |
| 43. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kVrms | 185 |
| Maximum steep current impulse residual voltage for a 2 kA, | kVpeak | 188 | |
| 30/60 µs, discharge current | |||
| 45. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kVpeak | 218 |
| 46. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
450 | |
| 47. | Line discharge class rating | 2 | |
| 48. | Lighting arrestor counter, leakage current meter and their accessories to be provided |
Yes/No | Yes |
| 49. | Gapless or gapped type metal–oxide surge arrester | Gapless | |
| 50. | Insulation Material | Porcelain | |
| 51. | Cantilever strength of surge arrester | Nm | 3000 |
| 52. | Rated frequency of surge arrester | Hz | 50 |
| 53. | Maximum angle from vertical at which surge arrester is fully functional |
Deg | 45 |
| 54. | Design altitude of surge arrester (above sea level) | m | 1400 m |
| 55. | Design ambient temperature of surge arrester | oC | –1 to 40 |
| 56. | Humidity | % | 85 |
| 57. | Specific phase–to–ground creepage of surge arrester | .mm/kV | 25 |
| 58. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
to SABS 763 or 316 stainless steel |
|
| 59. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
| 60. | Design drawings showing dimensions including foundations and brochures to be provided with bid |
Yes/No | Yes |
| 61. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
| 62. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
| 63. | Galvanized steel support structures complete with bolts & washers to be provided on delivery |
Yes/No | Yes |
| 64. | Applicable standard | IEC60099 |
Recommended for You
Not exactly what you want?
Post Sourcing Request
Hot Searches
Protective Device
Power Surge
Surge Protection
Arrester
Surge Protector
We are China Fuse Link, - 6 AMP -K manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular jgtrade1 Products
Pigtailbolt Withshoulder, Galvanized
Indoor/Outdoor, Air and Gas for Use in Switch-Fuse Combinations
Hot Selling Polymer 24kv Surge Lightning Arrester
Polymer Fuse Cutout, Drop out Fuses 12kv 300A
Popular Lightning Arrester Products
Yh10W-72.5, Sharp Head 48kv 10ka Surge Arrester
18kv Polymeric Housed Metal Oxide Lightning Arrester
Surge Suppressor Lightning Arrester
9kv 24kv Composite Silicon Rubber ZnO Lightning Arrester 11kv
Lightning Arrester, Surge Arrester, Pararrayos, Parafoudre 3-132kv, 10ka
Popular Lightning Arrestors Products
Hot Sale Surge Lightning 24kv Arrester High Voltage Arrestor Arresters
High Voltage Lightning and Surge Arrester
Polymer Fuse Cutout, Drop out Fuses 18kv 200A
36kv 10ka Polymer Housed Gapless Surge Arrester
Maintenance Platform (220kV, 110kV)
Popular Surge Arrester Products
Insulator, Hardware Accessories
Al-Cu Transition Connectors Type Syg, Compression Type, Group a
2016 New Technology 100kv Lightning Surge Arrester Without Gap Series
Polymer Housed Metal Oxide Surge Arrester Without Gaps
10kv Composite Zinc-Oxide Lightning Surge Arrester
Tags: jgtrade1, Lightning Arrester, Lightning Arrestors, Surge Arrester