4 Core Low Voltage PVC Insulated and Sheathed Power Cable
4 Core Low Voltage PVC Insulated and Sheathed Power Cable image
Get Latest Price Request a quote
Basic Info.
Product Description
Application:
With the characteristics of stable capability,advanced technology,broad material resources,low price, good flexible and easy to lay and maintain, the PVC Insulated and Sheathed Power Cable are suitable to be laid for distribution line with A.C.50HZ and rated voltage up to 6kV.
Property:
1.The long-time permissible working temperature of cable conductive core is not more than 70 °C.
2.During short circuit (max. permanent time is not more than 5 seconds), the max temperature of cable conductor is not more than 165°C.
3.The difference level of laying cable is not restricted.When laying the cable,ambient temperature is not lower than 0°C.
4.They have good chemical stability,and properties of acid resistance,alkali resistance,salt resistance,oil resistance,solvent resistance and flame resistance.rty
5.Light weight,good bending property and easy installation and maintenance.
Specification:
Standard:
IEC,BS,VDE,AS/NZS,ICEA,JIS and so on,designing and manufacturing special power cable according to the other standards required by the customer
1)600/1000V, Single Core, Circular Compacted Al or Cu/PVC/PVC Unarmoured or Armoured Power Cable
| Cross Section of Conductor | No. of Wires | Thickness of Insulation | Unarmoured | Armoured | ||||||||
| Thickness of Sheath | Overall Dia. | jpcable99.en. Weight | Thickness of Bedding | Thickness of Al Tape | Thickness of Sheath | Overall Dia. | jpcable99.en. Weight | |||||
| Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||||
| mm2 | – | mm | mm | mm | kg/km | kg/km | mm | mm | mm | mm | kg/km | kg/km |
| 1.5 | 1 | 0.8 | 1.4 | 5.8 | – | 51 | – | – | – | – | – | – |
| 2.5 | 1 | 0.8 | 1.4 | 6.2 | – | 64 | – | – | – | – | – | – |
| 4 | 1 | 1 | 1.4 | 7.1 | – | 88 | – | – | – | – | – | – |
| 6 | 7 | 1 | 1.4 | 7.8 | 78 | 114 | – | – | – | – | – | – |
| 10 | 7 | 1 | 1.4 | 8.6 | 96 | 159 | 1 | 0.5 | 1.8 | 13.4 | 234 | 295 |
| 16 | 7 | 1 | 1.4 | 9.6 | 123 | 222 | 1 | 0.5 | 1.8 | 14.4 | 274 | 370 |
| 25 | 7 | 1.2 | 1.4 | 11.2 | 172 | 328 | 1 | 0.5 | 1.8 | 16 | 344 | 496 |
| 35 | 7 | 1.2 | 1.4 | 12.2 | 209 | 428 | 1 | 0.5 | 1.8 | 17 | 393 | 606 |
| 50 | 19 | 1.4 | 1.4 | 13.9 | 271 | 565 | 1 | 0.5 | 1.8 | 18.7 | 478 | 764 |
| 70 | 19 | 1.4 | 1.5 | 15.9 | 356 | 818 | 1 | 0.5 | 1.8 | 20.5 | 582 | 1020 |
| 95 | 19 | 1.6 | 1.5 | 18 | 471 | 1041 | 1 | 0.5 | 1.8 | 22.6 | 717 | 1291 |
| 120 | 37 | 1.6 | 1.6 | 19.6 | 563 | 1307 | 1 | 0.5 | 1.8 | 24 | 822 | 1545 |
| 150 | 37 | 1.8 | 1.6 | 21.3 | 684 | 1592 | 1 | 0.5 | 1.8 | 25.4 | 952 | 1857 |
| 185 | 37 | 2 | 1.7 | 23.9 | 840 | 1985 | 1 | 0.5 | 1.8 | 27.9 | 1136 | 2236 |
| 240 | 61 | 2.2 | 1.8 | 27 | 1071 | 2533 | 1 | 0.5 | 1.9 | 31 | 1404 | 2877 |
| 300 | 61 | 2.4 | 1.9 | 29.6 | 1317 | 3162 | 1.2 | 0.5 | 2.1 | 34.3 | 1722 | 3551 |
| 400 | 61 | 2.6 | 2 | 33.2 | 1666 | 4120 | 1.2 | 0.5 | 2.2 | 37.6 | 2114 | 4488 |
| 500 | 61 | 2.8 | 2.2 | 37.5 | 2089 | 5163 | 1.2 | 0.5 | 2.3 | 42.1 | 2592 | 5683 |
| 630 | 61 | 2.8 | 2.3 | 41.2 | 2581 | 6447 | 1.4 | 0.5 | 2.4 | 46.3 | 3184 | 7060 |
2)600/1000V, Multi Cores, Sectoral Compacted Al or Cu/PVC/PVC Unarmoured Power Cable
| Number of Cores | Cross-Section of Conductor | No. Of Wires | Thickness of Insulation | Thickness of Sheath | Overall Diameter | Approx. Net Weight | |
| Al Conductor | Cu Conductor | ||||||
| – | mm2 | – | mm | mm | mm | kg/km | kg/km |
| Three Cores | 3×35 | 16 | 1.2 | 1.8 | 21.9 | 601 | 1280 |
| 3×50 | 18 | 1.4 | 1.8 | 26.5 | 829 | 1732 | |
| 3×70 | 18 | 1.4 | 1.9 | 29.2 | 1067 | 2367 | |
| 3×95 | 36 | 1.6 | 2 | 32.9 | 1409 | 2317 | |
| 3×120 | 36 | 1.6 | 2.1 | 36.2 | 1705 | 3983 | |
| 3×150 | 36 | 1.8 | 2.2 | 38.8 | 2045 | 4872 | |
| 3×185 | 36 | 2 | 2.4 | 44.8 | 2596 | 6077 | |
| 3×240 | 60 | 2.2 | 2.6 | 51.5 | 3353 | 7953 | |
| 3×300 | 60 | 2.4 | 2.7 | 54.9 | 6069 | 9820 | |
| Four Cores with Reduced Neutral | 3×35+16 | 16-7 | 1.2-1 | 1.8 | 25.5 | 764 | 1107 |
| 3×50+25 | 18-16 | 1.4-1.2 | 1.9 | 28.7 | 982 | 1410 | |
| 3×70+35 | 18-16 | 1.4-1.2 | 2.0 | 32 | 1278 | 1733 | |
| 3×95+50 | 36-18 | 1.6-1.4 | 2.2 | 37.8 | 1711 | 2656 | |
| 3×120+70 | 36-18 | 1.6-1.4 | 2.3 | 40.5 | 2065 | 3137 | |
| 3×150+70 | 36-18 | 1.8-1.4 | 2.4 | 44.8 | 2480 | 3660 | |
| 3×185+95 | 36-36 | 2-1.6 | 2.6 | 49.7 | 3086 | 4345 | |
| 3×240+120 | 60-36 | 2.2-1.6 | 2.8 | 56 | 3894 | 5441 | |
| 3×300+150 | 60-36 | 1.4-1.8 | 2.9 | 60.3 | 4834 | 6494 | |
| Four Cores | 4×25 | 16 | 1.2 | 1.8 | 22.5 | 644 | 1286 |
| 4×35 | 16 | 1.2 | 1.8 | 24.6 | 799 | 1696 | |
| 4×50 | 18 | 1.4 | 1.8 | 28.6 | 1071 | 2275 | |
| 4×70 | 18 | 1.4 | 2 | 31.6 | 1387 | 3120 | |
| 4×95 | 36 | 1.6 | 2.1 | 35.9 | 1850 | 4262 | |
| 4×120 | 36 | 1.6 | 2.2 | 38.8 | 2209 | 5247 | |
| 4×150 | 36 | 1.8 | 2.3 | 43.1 | 2714 | 6483 | |
| 4×185 | 36 | 2 | 2.5 | 48.7 | 3403 | 8045 | |
| 4×240 | 60 | 2.2 | 2.7 | 53.6 | 4290 | 10422 | |
| 4×300 | 60 | 2.4 | 2.9 | 58.8 | 5302 | 12969 | |
3)600/1000V, Multi Cores, Circular Compacted Al or Cu/PVC/PVC Unarmoured Power Cable
| Number of Cores | Cross-Section of Conductor | No. Of Wires | Thickness of Insulation | Thickness of Sheath | Overall Diameter | Approx. Net Weight | ||
| Al Conductor | Cu Conductor | |||||||
| – | mm2 | – | mm | mm | mm | kg/km | kg/km | |
| Three Cores | 3×10 | 7 | 1 | 1.8 | 16.6 | 281 | 465 | |
| 3×16 | 7 | 1 | 1.8 | 18.7 | 387 | 679 | ||
| 3×25 | 7 | 1.2 | 1.8 | 22.2 | 536 | 996 | ||
| 3×35 | 7 | 1.2 | 1.8 | 24.4 | 665 | 1311 | ||
| 3×50 | 19 | 1.4 | 1.9 | 28.1 | 863 | 1729 | ||
| 3×70 | 19 | 1.4 | 2 | 32.3 | 1153 | 2480 | ||
| 3×95 | 19 | 1.6 | 2.1 | 37.1 | 1563 | 3301 | ||
| 3×120 | 37 | 1.6 | 2.3 | 40.4 | 1850 | 4040 | ||
| 3×150 | 37 | 1.8 | 2.4 | 43.9 | 2258 | 5000 | ||
| 3×185 | 37 | 2 | 2.5 | 49.2 | 2819 | 6151 | ||
| 3×240 | 61 | 2.2 | 2.8 | 55.9 | 3577 | 8040 | ||
| 3×300 | 61 | 2.4 | 3 | 62.1 | 4413 | 9955 | ||
| 3×400 | 61 | 2.6 | 3.2 | 69.3 | 5512 | 12705 | ||
| Four Cores | 4×10 | 7 | 1 | 1.8 | 18.1 | 343 | 589 | |
| 4×16 | 7 | 1 | 1.8 | 20.5 | 487 | 874 | ||
| 4×25 | 7 | 1.2 | 1.8 | 24.3 | 677 | 1291 | ||
| 4×35 | 7 | 1.2 | 1.8 | 26.8 | 821 | 1681 | ||
| 4×50 | 19 | 1.4 | 2 | 31.2 | 1118 | 2273 | ||
| 4×70 | 19 | 1.4 | 2.1 | 35.8 | 1494 | 3264 | ||
| 4×95 | 19 | 1.6 | 2.3 | 41.2 | 1993 | 4312 | ||
| 4×120 | 37 | 1.6 | 2.4 | 44.8 | 2370 | 5291 | ||
| 4×150 | 37 | 1.8 | 2.5 | 48.7 | 2959 | 6615 | ||
| 4×185 | 37 | 2 | 2.7 | 54.7 | 3601 | 8044 | ||
| 4×240 | 61 | 2.2 | 3 | 62.1 | 4596 | 10547 | ||
| 4×300 | 61 | 2.4 | 3.2 | 69.1 | 5614 | 13004 | ||
4)600/1000V, Multi Cores, Sectoral Compacted Al or Cu/PVC/PVC Armoured Power Cable
| Cross Section of Conductor | No. of Wires | Thickness of Insulation | Thickness of Inner Sheath | Thickness of Steel Tape | No./Dia. Of Steel Wires | Thickness of Sheath | Overall Diameter | Approx. Net Weight | ||||||
| STA | SWA | |||||||||||||
| STA | SWA | STA | SWA | STA | SWA | Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||
| mm2 | – | mm | mm | mm | No./mm | mm | mm | mm | mm | kg/km | kg/km | kg/km | kg/km | |
| Three Cores | ||||||||||||||
| 3×35 | 16 | 1.2 | 1 | 0.2 | 38/1.6 | 1.8 | 1.9 | 24.7 | 28.2 | 912 | 1591 | 1447 | 2126 | |
| 3×50 | 18 | 1.4 | 1 | 0.2 | 46/1.6 | 1.9 | 2 | 29.3 | 32.8 | 1202 | 2105 | 1842 | 2745 | |
| 3×70 | 18 | 1.4 | 1.2 | 0.2 | 41/2.0 | 2.0 | 2.2 | 32.5 | 37.1 | 1520 | 2820 | 2475 | 3775 | |
| 3×95 | 36 | 1.6 | 1.2 | 0.5 | 46/2.0 | 2.1 | 2.3 | 36.5 | 40.8 | 2241 | 4049 | 2989 | 4797 | |
| 3×120 | 36 | 1.6 | 1.2 | 0.5 | 50/2.0 | 2.2 | 2.4 | 39.8 | 44.1 | 2617 | 4895 | 3435 | 5713 | |
| 3×150 | 36 | 1.8 | 1.2 | 0.5 | 43/2.5 | 2.3 | 2.5 | 42.4 | 47.8 | 3019 | 5846 | 4258 | 7085 | |
| 3×185 | 36 | 2 | 1.4 | 0.5 | 50/2.5 | 2.5 | 2.7 | 48.8 | 54.2 | 3783 | 7264 | 5219 | 8700 | |
| 3×240 | 60 | 2.2 | 1.6 | 0.5 | 58/2.5 | 2.8 | 2.9 | 56 | 61.3 | 4790 | 9390 | 6444 | 11044 | |
| 3×300 | 60 | 2.4 | 1.6 | 0.5 | 61/2.5 | 2.9 | 3.1 | 59.3 | 64.7 | 5594 | 11345 | 7458 | 13209 | |
| Four Cores with Reduced Neutral | ||||||||||||||
| 3×35+16 | 16-7 | 1.2-1 | 1 | 0.2 | 43/1.6 | 1.9 | 2 | 28.5 | 31.3 | 1107 | 1528 | 1705 | 2469 | |
| 3×50+25 | 18-16 | 1.4-1.2 | 1.2 | 0.2 | 40/2.0 | 2.0 | 2.1 | 32.2 | 36.1 | 1410 | 2044 | 2326 | 3388 | |
| 3×70+35 | 18-16 | 1.4-1.2 | 1.2 | 0.2 | 44/2.0 | 2.0 | 2.2 | 35.2 | 39.3 | 1733 | 2801 | 2762 | 4285 | |
| 3×95+50 | 36-18 | 1.6-1.4 | 1.2 | 0.5 | 41/2.5 | 2.3 | 2.5 | 42.5 | 46.3 | 2656 | 3820 | 3816 | 5925 | |
| 3×120+70 | 36-18 | 1.6-1.4 | 1.4 | 0.5 | 45/2.5 | 2.4 | 2.6 | 45.6 | 49.4 | 3137 | 4777 | 4391 | 7103 | |
| 3×150+70 | 36-18 | 1.8-1.4 | 1.4 | 0.5 | 49/2.5 | 2.6 | 2.7 | 49.9 | 53.6 | 3660 | 5709 | 5043 | 8272 | |
| 3×185+95 | 36-36 | 2-1.6 | 1.4 | 0.5 | 55/2.5 | 2.6 | 2.9 | 54.5 | 58.5 | 3445 | 7171 | 5902 | 9987 | |
| 3×240+120 | 60-36 | 2.2-1.6 | 1.6 | 0.5 | 62/2.5 | 2.9 | 3.1 | 61.6 | 65.3 | 5441 | 9272 | 7174 | 12552 | |
| 3×300+150 | 60-36 | 1.4-1.8 | 1.6 | 0.5 | 67/2.5 | 3.8 | 3.2 | 65.9 | 69.6 | 6494 | 11546 | 8355 | 15067 | |
| Four Cores | ||||||||||||||
| 4×25 | 16 | 1.2 | 1 | 0.2 | 38/1.6 | 1.8 | 1.9 | 25.3 | 28 | 934 | 1576 | 1450 | 2092 | |
| 4×35 | 16 | 1.2 | 1 | 0.2 | 41/1.6 | 1.8 | 1.9 | 27.4 | 30.2 | 1120 | 2017 | 1681 | 2578 | |
| 4×50 | 18 | 1.4 | 1 | 0.2 | 39/2.0 | 2 | 2.1 | 31.6 | 35.6 | 1454 | 2658 | 2336 | 3540 | |
| 4×70 | 18 | 1.4 | 1.2 | 0.5 | 43/2.0 | 2.1 | 2.2 | 36.3 | 39 | 2183 | 3916 | 2840 | 4573 | |
| 4×95 | 36 | 1.6 | 1.2 | 0.5 | 50/2.0 | 2.3 | 2.4 | 40.6 | 44.1 | 2748 | 5160 | 3545 | 5957 | |
| 4×120 | 36 | 1.6 | 1.4 | 0.5 | 42/2.5 | 2.4 | 2.5 | 43.9 | 47.2 | 3237 | 6214 | 4334 | 7372 | |
| 4×150 | 36 | 1.8 | 1.4 | 0.5 | 48/2.5 | 2.5 | 2.6 | 48.3 | 52 | 3853 | 7622 | 5148 | 8917 | |
| 4×185 | 36 | 2 | 1.6 | 0.5 | 54/2.5 | 2.7 | 2.8 | 54.3 | 57.6 | 4756 | 9323 | 6132 | 10774 | |
| 4×240 | 60 | 2.2 | 1.6 | 0.5 | 59/2.5 | 2.9 | 3 | 59.2 | 62.9 | 5774 | 11906 | 7374 | 13506 | |
| 4×300 | 60 | 2.4 | 1.6 | 0.5 | 65/2.5 | 3 | 3.2 | 64.3 | 68.1 | 6922 | 14589 | 8624 | 16291 | |
5)600/1000V, Multi Cores, Circular Compacted Al or Cu/PVC/PVC Armoured Power Cable
| Cross Section of Conductor | No. of Wires | Thickness of Insulation | Thickness of Inner Sheath | Thickness of Steel Tape | No./Dia. Of Steel Wires | Thickness of Sheath | Overall Diameter | Approx. Net Weight | |||||
| STA | SWA | ||||||||||||
| STA | SWA | STA | SWA | STA | SWA | Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||
| mm2 | – | mm | mm | mm | No./mm | mm | mm | mm | mm | kg/km | kg/km | kg/km | kg/km |
| Three Cores | |||||||||||||
| 3×10 | 7 | 1 | 1 | 0.2 | 35/1.25 | 1.8 | 1.8 | 19.4 | 21.5 | 494 | 679 | 988 | 1172 |
| 3×16 | 7 | 1 | 1 | 0.2 | 32/1.6 | 1.8 | 1.8 | 21.5 | 24.3 | 604 | 895 | 1051 | 1343 |
| 3×25 | 7 | 1.2 | 1 | 0.2 | 38/1.6 | 1.8 | 1.8 | 25 | 27.9 | 791 | 1252 | 1329 | 1790 |
| 3×35 | 7 | 1.2 | 1 | 0.2 | 42/1.6 | 1.8 | 1.9 | 27.2 | 30.2 | 950 | 1595 | 1551 | 2196 |
| 3×50 | 19 | 1.4 | 1.1 | 0.2 | 39/2.0 | 2 | 2.1 | 31.3 | 35.2 | 1213 | 2079 | 2128 | 2994 |
| 3×70 | 19 | 1.4 | 1.2 | 0.5 | 45/2.0 | 2.1 | 2.2 | 35.6 | 40.1 | 1567 | 2894 | 2678 | 4005 |
| 3×95 | 19 | 1.6 | 1.3 | 0.5 | 42/2.5 | 2.3 | 2.4 | 42 | 46.2 | 2449 | 4188 | 3689 | 5428 |
| 3×120 | 37 | 1.6 | 1.3 | 0.5 | 45/2.5 | 2.4 | 2.5 | 45.3 | 49.6 | 2823 | 5014 | 4174 | 6364 |
| 3×150 | 37 | 1.8 | 1.4 | 0.5 | 49/2.5 | 2.5 | 2.7 | 48.9 | 53.2 | 3327 | 6069 | 4795 | 7537 |
| 3×185 | 37 | 2 | 1.5 | 0.5 | 56/2.5 | 2.7 | 2.8 | 54.5 | 58.7 | 4038 | 7371 | 5686 | 9019 |
| 3×240 | 61 | 2.2 | 1.6 | 0.5 | 63/2.5 | 2.9 | 3.1 | 61.4 | 65.2 | 4994 | 9457 | 6862 | 11325 |
| 3×300 | 61 | 2.4 | 1.7 | 0.5 | 70/2.5 | 3.2 | 3.3 | 67.9 | 71.7 | 6022 | 11564 | 8101 | 13643 |
| 3×400 | 61 | 2.6 | 1.9 | 0.5 | 62/3.15 | 3.4 | 3.6 | 75.4 | 80.5 | 7350 | 14543 | 10535 | 17728 |
| Four Cores | |||||||||||||
| 4×10 | 7 | 1 | 1 | 0.2 | 39/1.25 | 1.8 | 1.8 | 20.9 | 23 | 552 | 798 | 1073 | 1319 |
| 4×16 | 7 | 1 | 1 | 0.2 | 35/1.6 | 1.8 | 1.8 | 23.3 | 26.1 | 723 | 1110 | 1213 | 1601 |
| 4×25 | 7 | 1.2 | 1 | 0.2 | 42/1.6 | 1.8 | 1.9 | 27.2 | 30.2 | 959 | 1573 | 1559 | 2173 |
| 4×35 | 7 | 1.2 | 1 | 0.2 | 37/2.0 | 1.9 | 2 | 29.7 | 33.6 | 1140 | 2000 | 2006 | 2866 |
| 4×50 | 19 | 1.4 | 1.2 | 0.2 | 44/2.0 | 2.1 | 2.2 | 34.6 | 38.4 | 1524 | 2679 | 2541 | 3696 |
| 4×70 | 19 | 1.4 | 1.2 | 0.5 | 50/2.0 | 2.3 | 2.3 | 40.5 | 43.7 | 2338 | 4107 | 3187 | 4956 |
| 4×95 | 19 | 1.6 | 1.2 | 0.5 | 46/2.5 | 2.4 | 2.6 | 45.9 | 50.2 | 2955 | 5274 | 4325 | 6644 |
| 4×120 | 37 | 1.6 | 1.4 | 0.5 | 51/2.5 | 2.6 | 2.7 | 50 | 54.2 | 3466 | 6387 | 4568 | 7888 |
| 4×150 | 37 | 1.8 | 1.4 | 0.5 | 55/2.5 | 2.7 | 2.8 | 53.8 | 58.1 | 4144 | 7800 | 5772 | 9428 |
| 4×185 | 37 | 2 | 1.6 | 0.5 | 62/2.5 | 2.9 | 3 | 60.2 | 64.5 | 4987 | 9430 | 6822 | 11266 |
| 4×240 | 61 | 2.2 | 1.6 | 0.5 | 70/2.5 | 3.1 | 3.3 | 67.7 | 71.5 | 6161 | 12111 | 8233 | 14184 |
| 4×300 | 61 | 2.4 | 1.6 | 0.5 | 61/3.15 | 3.4 | 3.5 | 74.7 | 78.8 | 7346 | 14735 | 10305 | 17694 |
Workshop:
FAQ:
1. How many years has Henan Jiapu Cable Group been in production?
Founded in October 1998 by Mr. Gu, our facility has three separate manufacturing workshops within its 100,000-sq.-ft. building. In 2012, we operates in a new 666,000 sq. foot state-of-the-art facility in Xiaodian Industry Park.,Xinxiang, Henan ,China
2. What kinds of products does Jiapu Cable manufacture?
1)Bare Conductor ,such as AAC,AAAC,ACSR,ACAR,AACSR,ACSR/AW and so on;
2)Aerial Bundled Cable (1kV-35kV ),such as Duplex,Triplex,Quadruplex Drop Wires and so on;
3)PVC Insulated (Flexible ) Wire ;
4) PVC Insulated and Sheathed (Armoured) Power Cable;
5)Low, Medium, High Voltage (1kV-220kV) XLPE Insulated (Armoured) Power Cable;
6)Welding Cable, Control Cable, Concentric Cable, Rubber Sheathed Cable and so on;
3. What kind of certifications do you have?
SABS, CE, ISO9001-2000, SGS
4.Which markets do you involve mainly in?
Our products have been exported mainly to Africa, Middle East, South-east Asia, South America,Central America,North America, Europe ,Australia, etc.
5. Which standards do you comply with when you produce the electrical wires and cables ?
We are able to produce electrical wires and cables based on GB, JB, IEC, BS, DIN, ASTM, JIS, NF, AS/NZS, CSA, etc. Meanwhile, we can design and manufacture the cables according to the samples and technical specification the customer supply.
6. What is the min.order quantity ?
It depends on the type and size of electrical wires and cables. For some small electrical wires, 100 meters can be accepted .But for the power cables with medium or high voltage, that should comply with the property of installed equipments. Anyhow,we will try our best to solve the problem and meet with the requirement If you have special request.
7. What is the production capacity per week or per month ?
For the bare conductor, we can finish 3000 tons within one month. For power cables, that depends on the type and size. The total output value per month is approx. USD3,000,000.00 for insulated aluminum cables and that is approx. USD8,000,000.00 for insulated copper cables.
8. Do you supply the customers with installation service in foreign country ?
We don’t have professional installation teams in foreign country.But if that is necessary, we will recommend our partners to cooperate with you.
We are China 4 Core Low Voltage PVC Insulated and Sheathed Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 4 Core Cable Products
PVC or XLPE Insulated 4 Core Cable 10mm2 120mm Copper Armoured Electric Power Cable
PVC Insulated Power Wire Manufacturer
3 4 Core Cable XLPE 0.6/1kv Tfr-CV 3cx50sqmm 4cx50sqmm 4cx4sqmm 4cx6sqmm
0.6/1kv 4 Core Armoured Cable 120mm PVC Armoured Power Cable
Popular 4 Core Low Voltage PVC Insulated and Sheathed Power Cable Products
Popular jpcable99 Products
100mm2 ACSR "Hare" Conductor Bare ACSR Conductor
Low Voltage 0.6/1kv PVC Power Cable
High Quality Overhead ABC Cable (JKLYJ)
Copper Conductor PVC Insulated Underground Power Cables (VV/VV22/VV32)
ASTM B524 Standard Acar Conductor
35kv XLPE Insulated Power Cable
Popular Low Voltage Cable Products
H03VV H05VV Electric Power Cable Wire 5X4mm2 Copper Wire
Low Voltage Aluminum Core XLPE Insulated Power Cable 0.6/1kv
120sqmm 70sqmm 185sqmm LV 4/C Al PVC Insulated Cable
Tightly-Pressed Sector (3+1) Low Voltage Cable
Swa Steel Wire Armored Cable Copper Aluminum Conductor XLPE PVC PE Insulation Polyolefin Sheath