BS En 50182 Upas All Aluminum Alloy Conductor AAAC Wire
BS En 50182 Upas All Aluminum Alloy Conductor AAAC Wire image
Get Latest Price Request a quote
- Overview
- Product Description
- Certificates
- Packing
- International Fairs
Basic Info.
Product Description
Aerial Bundled Cables
Aluminium Conductor Cables
All Aluminum Alloy Conductor (AAAC) Cables
Application
AAAC is mainly used as bare overhead transmission cable and as primary and secondary distribution cable. It is
also suitable for laying across basins, rivers and valleys where special geographical teatures exist.
Standard
Basic design to BS 3242 / BS EN 50182 / IEC 61089 / ASTM B 399/B 399M / DIN 48201-6 standards
Construction
AAAC cable bvconsists of aluminum alloy wires. The aluminum alloy wires are concentrically stranded.
This section deals with heat-treatable magnesium silicon type aluminium alloys to the applicable International
Standard, the electrical and mechanical properties of which all fall within the values suggested by relevant
standard.
Conductors to all other recognized specifications can also be supplied. The alloys referred to have higher trength
but lower conductivity than pure aluminium.
Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR;
Having lower breaking loads than the later, their use becomes particularly favourable when ice and wind
loadings are low.
Electrical Properties
| Density@20ºC | 2.70 kg/dm |
| Temperature Coefficient@20°C | 0.00360 (°C) |
| Resistivity@20°C | 0.0326 Ohms mm²/m |
| Linear Expansivity | 23 x10-6(°C) |
Service Conditions
| Ambient Temperature | -5°C – 50°C |
| Wind Pressure | 80 – 130kg/m² |
| Seismic Acceleration | 0.12 – 0.05g |
| Isokeraunic Level | 10 – 18 |
| Relative Humidity | 5 – 100% |
Construction Parameters
BS 3242
| Code | AL Nominal Area | Cu Nominal Area Equivalent | Total Area | Stranding | Overall Diameter | Weight |
| mm² | mm² | mm² | No.×mm | mm | kg/km | |
| – | – | 6.45 | 11.7 | 7/1.47 | 4.41 | 32.2 |
| Box | – | 9.68 | 18.8 | 7/1.85 | 5.55 | 51.7 |
| Acacia | – | 12.9 | 21.9 | 7/2.08 | 6.24 | 66.1 |
| Almond | 25 | 16.1 | 30.1 | 7/2.34 | 7.02 | 82.9 |
| Ceda | 30 | 19.4 | 35.5 | 7/2.54 | 7.62 | 97.8 |
| – | 40 | 22.6 | 42.2 | 7/2.77 | 8.31 | 116.4 |
| Fir | 50 | 25.8 | 47.8 | 7/2.95 | 8.85 | 131.8 |
| Hazel | 100 | 32.3 | 59.9 | 7/3.30 | 9.9 | 165 |
| Pine | – | 38.7 | 71.7 | 7/3.61 | 10.83 | 197.7 |
| – | – | 45.2 | 84.1 | 7/3.91 | 11.73 | 231.6 |
| Willow | 150 | 48.4 | 89.8 | 7/4.04 | 12.12 | 247.5 |
| – | 175 | 51.6 | 96.5 | 7/4.19 | 12.57 | 266.2 |
| – | 300 | 58.1 | 108.8 | 7/4.45 | 13.35 | 299.8 |
| Oak | – | 64.5 | 118.9 | 7/4.65 | 13.95 | 327.8 |
| – | – | 80.6 | 118.8 | 19/2.82 | 14.1 | 327.6 |
| Mulberry | – | 96.8 | 151.1 | 19/3.18 | 15.9 | 416.7 |
| Ash | – | 113 | 180.7 | 19/3.48 | 17.4 | 498.1 |
| Elm | – | 129 | 211 | 19/3.76 | 18.8 | 582.1 |
| Poplar | – | 145 | 239 | 37/2.87 | 20.09 | 658.8 |
| – | – | 161 | 270.8 | 37/3.05 | 21.35 | 746.7 |
| Sycamore | – | 194 | 303 | 37/3.23 | 22.61 | 834.9 |
| Upas | – | 226 | 362.1 | 37/3.53 | 24.71 | 998.6 |
| – | – | 258 | 421.8 | 37/3.81 | 26.47 | 1163 |
| Yew | – | – | 479.9 | 37/4.06 | 28.42 | 1323 |
(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.
BS EN 50182
| Code | Stranding | Nominal Area | Overall Diameter | Weight | Rated Strength | Electrical Resistance | Current Rating* |
| No.×mm | mm² | mm | kg/km | KN | Ω/Km | A | |
| Box | 7/1.85 | 18.8 | 5.55 | 51.4 | 5.55 | 1.748 | 87 |
| Acacia | 7/2.08 | 23.8 | 6.24 | 64.9 | 7.02 | 1.3828 | 101 |
| Almond | 7/2.34 | 30.1 | 7.02 | 82.2 | 8.88 | 1.0926 | 116 |
| Cedar | 7/2.54 | 35.5 | 7.62 | 96.8 | 10.46 | 0.9273 | 129 |
| Deodar | 7/2.77 | 42.2 | 8.31 | 115.2 | 12.44 | 0.7797 | 143 |
| Fir | 7/2.95 | 47.8 | 8.85 | 130.6 | 14.11 | 0.6875 | 155 |
| Hazel | 7/3.30 | 59.9 | 9.9 | 163.4 | 17.66 | 0.5494 | 178 |
| Pine | 7/3.61 | 71.6 | 10.83 | 195.6 | 21.14 | 0.4591 | 199 |
| Holly | 7/3.91 | 84.1 | 11.73 | 229.5 | 24.79 | 0.3913 | 219 |
| Willow | 7/4.04 | 89.7 | 12.12 | 245 | 26.47 | 0.3665 | 228 |
| Oak | 7/4.65 | 118.9 | 13.95 | 324.5 | 35.07 | 0.2767 | 272 |
| Mulberry | 19/3.18 | 150.9 | 15.9 | 414.3 | 44.52 | 0.2192 | 314 |
| Ash | 19/3.48 | 180.7 | 17.4 | 496.1 | 53.31 | 0.183 | 351 |
| Elm | 19/3.76 | 211 | 18.8 | 579.2 | 62.24 | 0.1568 | 386 |
| Poplar | 37/2.87 | 239.4 | 20.09 | 659.4 | 70.61 | 0.1387 | 416 |
| Sycamore | 37/3.23 | 303.2 | 22.61 | 835.2 | 89.4 | 0.1095 | 480 |
| Upas | 37/3.53 | 362.1 | 24.71 | 997.5 | 106.82 | 0.0917 | 535 |
| Yew | 37/4.06 | 479 | 28.42 | 1319.6 | 141.31 | 0.0693 | 633 |
| Totara | 37/4.14 | 498.1 | 28.98 | 1372.1 | 146.93 | 0.0666 | 648 |
| Rubus | 61/3.50 | 586.9 | 31.5 | 1622 | 173.13 | 0.0567 | 714 |
| Sorbus | 61/3.71 | 659.4 | 33.39 | 1822.5 | 194.53 | 0.0505 | 764 |
| Araucaria | 61/4.14 | 821.1 | 37.26 | 2269.4 | 242.24 | 0.0406 | 868 |
| Redwood | 61/4.56 | 996.2 | 41.04 | 2753.2 | 293.88 | 0.0334 | 970 |
Note: *The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.
IEC 61089
| Code | Nominal Area | Stranding | Overall Diameter | Weight | Rated Strength | Electrical Resistance | Current Rating* |
| mm² | No.×mm | mm | kg/km | KN | Ω/Km | A | |
| 16 | 18.4 | 18.4 | 5.49 | 50.4 | 5.43 | 1.7896 | 86 |
| 25 | 28.8 | 28.8 | 6.87 | 78.7 | 8.49 | 1.1453 | 113 |
| 40 | 46 | 46 | 8.67 | 125.9 | 13.58 | 0.7158 | 151 |
| 63 | 72.5 | 72.5 | 10.89 | 198.3 | 21.39 | 0.4545 | 200 |
| 100 | 115 | 115 | 13.9 | 316.3 | 33.95 | 0.2877 | 266 |
| 125 | 144 | 144 | 15.5 | 395.4 | 42.44 | 0.2302 | 305 |
| 160 | 184 | 184 | 17.55 | 506.1 | 54.32 | 0.1798 | 355 |
| 200 | 230 | 230 | 19.65 | 632.7 | 67.91 | 0.1439 | 407 |
| 250 | 288 | 288 | 21.95 | 790.8 | 84.88 | 0.1151 | 466 |
| 315 | 363 | 363 | 24.71 | 998.9 | 106.95 | 0.0916 | 535 |
| 400 | 460 | 460 | 27.86 | 1268.4 | 135.81 | 0.0721 | 618 |
| 450 | 518 | 518 | 29.54 | 1426.9 | 152.79 | 0.0641 | 663 |
| 500 | 575 | 575 | 31.15 | 1585.5 | 169.76 | 0.0577 | 706 |
| 560 | 645 | 645 | 33.03 | 1778.4 | 190.14 | 0.0516 | 755 |
| 630 | 725 | 725 | 35.01 | 2000.7 | 213.9 | 0.0458 | 809 |
| 710 | 817 | 817 | 37.17 | 2254.8 | 241.07 | 0.0407 | 866 |
| 800 | 921 | 921 | 39.42 | 2540.6 | 271.62 | 0.0361 | 928 |
| 900* | 1036 | 1036 | 41.91 | 2861.1 | 305.58 | 0.0321 | 992 |
| 1000* | 1151 | 1151 | 44.11 | 3179 | 339.53 | 0.0289 | 1051 |
| 1120* | 1289 | 1289 | 46.75 | 3560.5 | 380.27 | 0.0258 | 1118 |
| 1250* | 1439 | 1439 | 49.39 | 3973.7 | 424.41 | 0.0231 | 1185 |
(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.
ASTM B 399/B 399M
| Nominal Area | Stranding | Overall Diameter | Weight | Rated Strength | Electrical Resistance | Current Rating* | |
| AWG&MCM | mm² | No.×mm | mm | kg/km | KN | Ω/Km | A |
| 6 | 13.2 | 7/1.55 | 4.65 | 36.2 | 4.18 | 2.5361 | 69 |
| 4 | 21.1 | 7/1.96 | 5.88 | 57.9 | 6.69 | 1.586 | 93 |
| 2 | 33.5 | 7/2.47 | 7.41 | 92 | 10.6 | 0.9987 | 123 |
| 0 | 53.5 | 7/3.12 | 9.36 | 146.8 | 17 | 0.62592 | 165 |
| 2/0 | 67.3 | 7/3.50 | 10.5 | 184.8 | 20.4 | 0.49738 | 190 |
| 3/0 | 84.9 | 7/3.93 | 11.79 | 233 | 25.7 | 0.3945 | 219 |
| 4/0 | 107 | 7/4.42 | 13.26 | 294.7 | 32.5 | 0.31188 | 253 |
| 250 | 126 | 19/2.91 | 14.55 | 346.7 | 38.8 | 0.26509 | 280 |
| 300 | 152 | 19/3.19 | 15.95 | 416.7 | 46.6 | 0.22059 | 313 |
| 350 | 178 | 19/3.45 | 17.25 | 487.3 | 52 | 0.1886 | 345 |
| 400 | 203 | 19/3.69 | 18.45 | 557.5 | 59.5 | 0.16486 | 375 |
| 450 | 228 | 19/3.91 | 19.55 | 626 | 66.8 | 0.14683 | 402 |
| 500 | 253 | 19/4.12 | 20.6 | 695 | 74.2 | 0.13224 | 429 |
| 550 | 279 | 37/3.10 | 21.7 | 766.2 | 83.9 | 0.11995 | 455 |
| 600 | 303 | 37/3.23 | 22.61 | 831.9 | 91 | 0.11049 | 478 |
| 650 | 330 | 37/3.37 | 23.59 | 905.5 | 94.9 | 0.1015 | 504 |
| 700 | 354 | 37/3.49 | 24.43 | 971.2 | 101 | 0.09464 | 525 |
| 750 | 381 | 37/3.62 | 25.34 | 1045 | 109 | 0.08796 | 549 |
| 800 | 404 | 37/3.73 | 26.11 | 1109 | 116 | 0.08285 | 569 |
| 900 | 456 | 37/3.96 | 27.72 | 1250 | 131 | 0.07351 | 612 |
| 1000 | 508 | 37/4.18 | 29.26 | 1393 | 146 | 0.06597 | 653 |
| 1250 | 631 | 61/3.63 | 32.67 | 1732 | 179 | 0.05306 | 743 |
| 1500 | 759 | 61/3.98 | 35.82 | 2082 | 215 | 0.04414 | 827 |
| 1750 | 886 | 61/4.30 | 38.7 | 2431 | 251 | 0.03781 | 904 |
(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.
DIN 48201 Part 6
| Nominal Area | Stranding | Overall Diameter | Weight | Rated Strength | Electrical Resistance | Current Rating* | |
| Nominal | Teorical | ||||||
| mm² | mm² | No.×mm | mm | kg/km | KN | Ω/Km | A |
| 16 | 15.89 | 7/1.70 | 5.1 | 43 | 4.44 | 2.0742 | 78 |
| 25 | 24.25 | 7/2.10 | 6.3 | 66 | 6.77 | 1.3593 | 102 |
| 35 | 34.36 | 7/2.50 | 7.5 | 94 | 9.6 | 0.9591 | 126 |
| 50 | 49.48 | 7/3.00 | 9 | 135 | 13.82 | 0.666 | 158 |
| 50 | 48.35 | 19/1.80 | 9 | 133 | 13.5 | 0.6849 | 156 |
| 70 | 65.81 | 19/2.10 | 10.5 | 181 | 18.38 | 0.5032 | 189 |
| 95 | 93.27 | 19/2.50 | 12.5 | 256 | 26.05 | 0.3551 | 234 |
| 120 | 116.99 | 19/2.80 | 14 | 322 | 32.68 | 0.2831 | 269 |
| 150 | 147.11 | 37/2.25 | 15.8 | 406 | 41.09 | 0.2256 | 309 |
| 185 | 181.62 | 37/2.50 | 17.5 | 500 | 50.73 | 0.1828 | 352 |
| 240 | 242.54 | 61/2.25 | 20.3 | 670 | 67.74 | 0.1371 | 420 |
| 300 | 299.43 | 61/2.50 | 22.5 | 827 | 83.63 | 0.111 | 477 |
| 400 | 400.14 | 61/2.89 | 26 | 1104 | 111.76 | 0.0831 | 568 |
| 500 | 499.83 | 61/3.23 | 29.1 | 1379 | 139.6 | 0.0665 | 649 |
| 625* | 626.2 | 91/2.96 | 32.6 | 1732 | 174.9 | 0.0531 | 742 |
| 800* | 802.09 | 91/3.35 | 36.9 | 2218 | 224.02 | 0.0415 | 857 |
| 1000* | 999.71 | 91/3.74 | 41.1 | 2767 | 279.22 | 0.0333 | 971 |
* The items marked with "*" are not in our current product range and the details are for information only.
(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.
Technical Data
| Code | AL Nominal Area | Maximum Resistance DC at 20º | Current Rating | ||
| Temperate | Tropical | ||||
| mm² | Ω / km | Ω / 1000ft | Amp | Amp | |
| – | – | 2.87 | 0.873 | 90 | 73 |
| Box | – | 1.79 | 0.544 | 121 | 98 |
| Acacia | – | 1.4 | 0.426 | 140 | 114 |
| Almond | 25 | 1.11 | 0.339 | 162 | 131 |
| Ceda | 30 | 0.944 | 0.288 | 180 | 145 |
| – | 40 | 0.794 | 0.242 | 200 | 162 |
| Fir | 50 | 0.7 | 0.213 | 217 | 175 |
| Hazel | 100 | 0.559 | 0.17 | 250 | 201 |
| Pine | – | 0.467 | 0.142 | 279 | 224 |
| – | – | 0.398 | 0.121 | 309 | 247 |
| Willow | 150 | 0.373 | 0.114 | 322 | 258 |
| – | 175 | 0.347 | 0.106 | 337 | 270 |
| – | 300 | 0.308 | 0.0938 | 343 | 290 |
| Oak | – | 0.282 | 0.0859 | 384 | 307 |
| – | – | 0.282 | 0.086 | 385 | 307 |
| Mulberry | – | 0.222 | 0.0676 | 448 | 356 |
| Ash | – | 0.185 | 0.0565 | 501 | 398 |
| Elm | – | 0.159 | 0.048 | 553 | 438 |
| Poplar | – | 0.14 | 0.0427 | 598 | 473 |
| – | – | 0.124 | 0.0337 | 647 | 511 |
| Sycamore | – | 0.111 | 0.0377 | 694 | 547 |
| Upas | – | 0.0925 | 0.0282 | 776 | 610 |
| – | – | 0.0794 | 0.0242 | 854 | 669 |
| Yew | – | 0.0698 | 0.0213 | 925 | 723 |
Why Choose Us
1. Strict quality control system, excellent quality with reasonable price.
2. Strong and professional R&D team to meet your specific needs.
3. Rapid delivery and feedback. Faster lead time than our competitors.
4. OEM service available based on offical & legal authorization.
5. Free sample is available.
6. Appointed shipping company is acceptable.
We are China BS En 50182 Upas All Aluminum Alloy Conductor AAAC Wire manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 740.8mcm AAAC Flint Conductor Products
BS En 50182 Yew All Aluminum Alloy Conductor AAAC Wire
DIN 48201 All Aluminum Alloy Conductor AAAC
ASTM B399 All Aluminum Alloy Conductor
BS En 50183 All Aluminum Alloy Conductor AAAC
6AWG ASTM B399 All Aluminum Alloy Conductor AAAC
2/0AWG ASTM B399 All Aluminum Alloy Conductor AAAC
Popular All Aluminium Alloy Conductor AAAC Products
IEC61089 315 Code All Aluminum Alloy Conductor Wire
BS En50183 Standard All Aluminium Alloy Conductor AAAC
Ant BS215 All Aluminum Conductor AAC
Mosquito BS215 All Aluminum Conductor AAC
Almond 25 mm2 Aluminum Alloy Conductor AAAC
ASTM B399 All Aluminum Alloy Conductor
Popular BS En 50182 Upas All Aluminum Alloy Conductor AAAC Wire Products
Popular hnbfcable Products
Quadruplex PE/XLPE Secondary Ud Cable ABC Cable Wire
Hot Sale Dyke 2AWG ASTM Standard Secondary Ud Cable Duplex/Triplex/Quadruplex Aerial Cable
Low Voltage Aluminum Conductor XLPE/PE Insulation Overhead 3*35sqmm ABC Cable
DIN 48206 Aluminum Alloy Conductors Steel Reinforced Aacsr
BS Standard Greased Bare Aluminium Alloy Conductor AAAC Conductor
ACSR Lapw Conductor Compress Connector
Tags: 740.8mcm AAAC Flint Conductor, All Aluminium Alloy Conductor AAAC, BS En 50182 Upas All Aluminum Alloy Conductor AAAC Wire, hnbfcable