0.6/1kv Low Voltage Aluminum PVC Insulated PVC Sheath Electrical Power Cable
0.6/1kv Low Voltage Aluminum PVC Insulated PVC Sheath Electrical Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
1. Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 70° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed:
Nominal cross section of conductor ≤ 300mm2: 160° C;
Nominal cross section of conductor >300mm2: 140° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For multi-core cable: Not less than 15 times of the diameter of cable
2. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.
3. Manufacturing Standards
IEC 60502-1 & Chinese national standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
Main technical data of 0.6/1KV, Single core, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
| 1x10mm2 | RM | 1.0 | 0.2 | 1.8 | 12.9 | 3.08 |
| 1x16mm2 | RM | 1.0 | 0.2 | 1.8 | 13.9 | 1.91 |
| 1x25mm2 | RM | 1.2 | 0.2 | 1.8 | 14.3 | 1.20 |
| 1x35mm2 | RM | 1.2 | 0.2 | 1.8 | 15.5 | 0.868 |
| 1x50mm2 | RM | 1.4 | 0.2 | 1.8 | 17.2 | 0.641 |
| 1x70mm2 | RM | 1.4 | 0.2 | 1.8 | 19.0 | 0.443 |
| 1x95mm2 | RM | 1.6 | 0.2 | 1.8 | 21.3 | 0.320 |
| 1x120mm2 | RM | 1.6 | 0.2 | 1.8 | 22.9 | 0.253 |
| 1x150mm2 | RM | 1.8 | 0.2 | 1.8 | 24.9 | 0.206 |
| 1x185mm2 | RM | 2.0 | 0.2 | 1.8 | 27.1 | 0.164 |
| 1x240mm2 | RM | 2.2 | 0.2 | 1.8 | 30.2 | 0.125 |
| 1x300mm2 | RM | 2.4 | 0.5 | 2.0 | 35.2 | 0.100 |
| 1x400mm2 | RM | 2.6 | 0.5 | 2.1 | 38.8 | 0.0778 |
| 1x500mm2 | RM | 2.8 | 0.5 | 2.2 | 43.0 | 0.0605 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, two cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
| 2×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 12.9 | 18.1 |
| 2×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.7 | 12.1 |
| 2x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 15.5 | 7.41 |
| 2x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.5 | 4.61 |
| 2x10mm2 | RM | 1.0 | 0.2 | 1.8 | 19.1 | 3.08 |
| 2x16mm2 | RM | 1.0 | 0.2 | 1.8 | 21.2 | 1.91 |
| 2x25mm2 | SM | 1.2 | 0.2 | 1.8 | 18.6 | 1.20 |
| 2x35mm2 | SM | 1.2 | 0.2 | 1.8 | 20.1 | 0.868 |
| 2x50mm2 | SM | 1.4 | 0.2 | 1.8 | 22.4 | 0.641 |
| 2x70mm2 | SM | 1.4 | 0.5 | 2.0 | 26.9 | 0.443 |
| 2x95mm2 | SM | 1.6 | 0.5 | 2.1 | 30.3 | 0.320 |
| 2x120mm2 | SM | 1.6 | 0.5 | 2.2 | 32.6 | 0.253 |
| 2x150mm2 | SM | 1.8 | 0.5 | 2.3 | 35.5 | 0.206 |
| 2x185mm2 | SM | 2.0 | 0.5 | 2.5 | 39.1 | 0.164 |
| 2x240mm2 | SM | 2.2 | 0.5 | 2.7 | 43.6 | 0.125 |
| 2x300mm2 | SM | 2.4 | 0.5 | 2.8 | 47.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, three cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
| 3×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.4 | 18.1 |
| 3×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.3 | 12.1 |
| 3x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.1 | 7.41 |
| 3x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 4.61 |
| 3x10mm2 | RM | 1.0 | 0.2 | 1.8 | 20.0 | 3.08 |
| 3x16mm2 | RM | 1.0 | 0.2 | 1.8 | 22.3 | 1.91 |
| 3x25mm2 | SM | 1.2 | 0.2 | 1.8 | 21.3 | 1.20 |
| 3x35mm2 | SM | 1.2 | 0.2 | 1.8 | 23.2 | 0.868 |
| 3x50mm2 | SM | 1.4 | 0.2 | 1.9 | 26.2 | 0.641 |
| 3x70mm2 | SM | 1.4 | 0.5 | 2.0 | 31.1 | 0.443 |
| 3x95mm2 | SM | 1.6 | 0.5 | 2.2 | 35.4 | 0.320 |
| 3x120mm2 | SM | 1.6 | 0.5 | 2.3 | 38.2 | 0.253 |
| 3x150mm2 | SM | 1.8 | 0.5 | 2.4 | 41.7 | 0.206 |
| 3x185mm2 | SM | 2.0 | 0.5 | 2.6 | 46.0 | 0.164 |
| 3x240mm2 | SM | 2.2 | 0.5 | 2.8 | 51.4 | 0.125 |
| 3x300mm2 | SM | 2.4 | 0.5 | 3.0 | 56.5 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, 3+1 cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation(mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath (mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
|||
| Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
| 3×2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 14.9 | 12.1 | 18.1 |
| 3×4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 16.7 | 7.41 | 12.1 |
| 3×6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 18.2 | 4.61 | 7.41 |
| 3×10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 20.8 | 3.08 | 4.61 |
| 3×16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 23.5 | 1.91 | 3.08 |
| 3×25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 24.2 | 1.20 | 1.91 |
| 3×35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 25.9 | 0.868 | 1.91 |
| 3×50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.0 | 30.5 | 0.641 | 1.20 |
| 3×70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.9 | 0.443 | 0.868 |
| 3×95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.3 | 38.5 | 0.320 | 0.641 |
| 3×120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 41.8 | 0.253 | 0.443 |
| 3×150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.5 | 45.0 | 0.206 | 0.443 |
| 3×185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.7 | 49.9 | 0.164 | 0.320 |
| 3×240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 2.9 | 55.5 | 0.125 | 0.253 |
| 3×300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.1 | 61.0 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, four cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables
CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
| 4×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.2 | 18.1 |
| 4×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.1 | 12.1 |
| 4x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 7.41 |
| 4x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 4.61 |
| 4x10mm2 | RM | 1.0 | 0.2 | 1.8 | 21.6 | 3.08 |
| 4x16mm2 | RM | 1.0 | 0.2 | 1.8 | 24.1 | 1.91 |
| 4x25mm2 | SM | 1.2 | 0.2 | 1.8 | 23.8 | 1.20 |
| 4x35mm2 | SM | 1.2 | 0.2 | 1.8 | 25.9 | 0.868 |
| 4x50mm2 | SM | 1.4 | 0.5 | 2.0 | 31.4 | 0.641 |
| 4x70mm2 | SM | 1.4 | 0.5 | 2.1 | 35.0 | 0.443 |
| 4x95mm2 | SM | 1.6 | 0.5 | 2.3 | 39.9 | 0.320 |
| 4x120mm2 | SM | 1.6 | 0.5 | 2.4 | 43.1 | 0.253 |
| 4x150mm2 | SM | 1.8 | 0.5 | 2.6 | 47.3 | 0.206 |
| 4x185mm2 | SM | 2.0 | 0.5 | 2.8 | 52.3 | 0.164 |
| 4x240mm2 | SM | 2.2 | 0.5 | 3.0 | 58.4 | 0.125 |
| 4x300mm2 | SM | 2.4 | 0.5 | 3.2 | 64.3 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, five cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables , CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
| 5×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.0 | 18.1 |
| 5×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 16.1 | 12.1 |
| 5x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 7.41 |
| 5x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 19.8 | 4.61 |
| 5x10mm2 | RM | 1.0 | 0.2 | 1.8 | 23.3 | 3.08 |
| 5x16mm2 | RM | 1.0 | 0.2 | 1.8 | 26.2 | 1.91 |
| 5x25mm2 | SM | 1.2 | 0.2 | 1.8 | 26.1 | 1.20 |
| 5x35mm2 | SM | 1.2 | 0.5 | 2.0 | 30.7 | 0.868 |
| 5x50mm2 | SM | 1.4 | 0.5 | 2.1 | 34.6 | 0.641 |
| 5x70mm2 | SM | 1.4 | 0.5 | 2.3 | 38.9 | 0.443 |
| 5x95mm2 | SM | 1.6 | 0.5 | 2.5 | 44.4 | 0.320 |
| 5x120mm2 | SM | 1.6 | 0.5 | 2.6 | 47.9 | 0.253 |
| 5x150mm2 | SM | 1.8 | 0.5 | 2.8 | 52.6 | 0.206 |
| 5x185mm2 | SM | 2.0 | 0.5 | 2.9 | 57.9 | 0.164 |
| 5x240mm2 | SM | 2.2 | 0.5 | 3.2 | 65.0 | 0.125 |
| 5x300mm2 | SM | 2.4 | 0.5 | 3.4 | 71.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, 4+1 cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
| Cable size |
Conductor type |
Nominal thickness of PVC insulation(mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath (mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
|||
| Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
| 4×2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 15.9 | 12.1 | 18.1 |
| 4×4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 18.0 | 7.41 | 12.1 |
| 4×6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 19.6 | 4.61 | 7.41 |
| 4×10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 22.6 | 3.08 | 4.61 |
| 4×16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 25.6 | 1.91 | 3.08 |
| 4×25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 26.6 | 1.20 | 1.91 |
| 4×35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.9 | 28.7 | 0.868 | 1.91 |
| 4×50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.8 | 0.641 | 1.20 |
| 4×70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.3 | 37.8 | 0.443 | 0.868 |
| 4×95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 42.8 | 0.320 | 0.641 |
| 4×120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.6 | 46.6 | 0.253 | 0.443 |
| 4×150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.7 | 50.4 | 0.206 | 0.443 |
| 4×185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.9 | 55.9 | 0.164 | 0.320 |
| 4×240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 3.1 | 62.2 | 0.125 | 0.253 |
| 4×300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.3 | 68.4 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
We are China 0.6/1kv Low Voltage Aluminum PVC Insulated PVC Sheath Electrical Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Aluminium Power Cable Products
PVC/XLPE Insulated Sheathed Power Cable 25mm2
1kv 4 Core Aluminium Power Cable with Steel Wire/Tape Armour
AAC/AAAC/ACSR Overhead Conductor Bare Cable
0.6/1kv 3 Cores Aluminium/Copper Conductor XLPE Insulated PVC Sheathed Power Cable Yjv/Yjlv
35 Sqmm 4 Core Aluminium Armoured Power Cable
Power Cables, Aliminum XLPE Insulated PVC Sheathed Power Cable Yjv, Yjlv
Popular jytopcable Products
Acss/Aw Aluminium Conductor Steel Supported Acss Conductor
LV 0.6/1kv PVC Insulated Power Cable with 4+1 Core
Overhead Bare Aluminium ACSR Conductor for ASTM BS IEC Standards
Single Core Overhead XLPE Insulated Aluminium Covered Line Wire and Cable
3 Core Copper Conductor XLPE Insulated PVC Sheath Jacks Electric Wire
Low Voltage LV Aerial Bundled Cables Triplex Cable ABC Cable Overhead Cable
Popular Low Voltage Cable Products
33kv 3X185mm2 XLPE Insulated Armour Power Cable
AS/NZS 35 50 70 95mm2 Copper XLPE Power Cable Flexible Electric Cable Wire
Electric Cable Three Phase Aluminum Cable 240mm2 XLPE Cable
Overhead Insulated XLPE Medium Voltage Power Cable
0.6/1kv Cu/PVC/Swa/PVC 4X185mm2
0.6/1kV 4X2.5mm2 Copper XLPE Insulated PVC Jacket Low Voltage Power Cable
Popular PVC Power Cable Products
3.6/6 Kw Mv Flame Retardant XLPE Power Cable 4 Core 120mm 150mm 185mm Armoured Power Cable
Multicore Underground Cable PVC Insulated Electric Power Cable
PVC Insulated Power Cable, Aluminum Conductor Fire Resistant Cable
IEC Al/XLPE/PVC Power Cable 0.6/1kv
Copper Conductor PVC Insulated PVC Sheathed Power Cable
Tags: Aluminium Power Cable, jytopcable, Low Voltage Cable, PVC Power Cable