ACSR Cable Features:
Simple structure / Easy installation and maintenance / Low circuit cost / Large transmission capacity / Good conductive performance / Sufficient mechanical strength / High tensile strength

ACSR Cable Advantage:
1. Convenient for laying across special geographical conditions such as rivers and valleys
2.The tower distance can be enlarged

ACSR Cable Application:
Widely used in overhead power transmission lines of various voltage levels

AAAC Cable Applications
AAAC Aluminum Alloy Conductor is Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum alloy to achieve a high strength-to-weight ratio; affords better sag characteristics. Aluminum alloy gives higher resistance to corrosion than ACSR.

Standard
 BS EN50183,IEC 61089, ASTM B399,BS 3242, DIN 48204,GB/T1179-2008

Specification
Physical contents of aluminum alloy :- 
1. Resistivity – 0.0326 Ohms mm2/m at 20°C 
2. Density – 2.70 kgm/dm3 at 20°C 
3. Coefficient of Linear Expansion – 23 x 10-6 / °C 
4. Constant Mass Temperature Coefficient (a) – 0.00360/ °C 
5. Material – Heat treated Al. Mg. Si. Alloy 
– Approximately 0.5% Mg & 0.5% Si 
 
ASTM B399

Code Name Area Size & Stranding of ACSR with Equal Diameter No. & Diameter of wires Overall Diameter Weight Nominal Breaking Load
Nominal Actual
MCM mm2 AWG or MCM Al/Steel mm mm kg/km kN
Akron 30.58 15.48 6 6/1 7/1.68 5.04 42.7 4.92
Alton 48.69 24.71 4 6/1 7/2.12 6.35 68.0 7.84
Ames 77.47 39.22 2 6/1 7/2.67 8.02 108 12.45
Azusa 123.3 62.38 1/0 6/1 7/3.37 10.11 172 18.97
Anaheim 155.4 78.65 2/0 6/1 7/3.78 11.35 217 23.93
Amherst 195.7 99.22 3/0 6/1 7/4.25 12.75 273 30.18
Alliance 246.9 125.1 4/0 6/1 7/4.77 14.31 345 38.05
Butte 312.8 158.6 266.8 26/7 19/3.26 16.30 437 48.76
Canton 394.5 199.9 336.4 26/7 19/3.66 18.30 551 58.91
Cairo 465.4 235.8 397.5 26/7 19/3.98 19.88 650 69.48
Darien 559.5 283.5 477.0 26/7 19/4.36 21.79 781 83.52
Elgin 652.4 330.6 556.5 26/7 19/4.71 23.54 911 97.42
Flint 740.8 375.3 636.0 26/7 37/3.59 25.16 1035 108.21
Greely 927.2 469.8 795.0 26/7 37/4.02 28.14 1295 135.47

 
IEC 61089

Code Number A2 Conductor A3 Conductor  Max.D.C. Resistance of Conductor at 20ºC
Number of Wires  Diameter of Wires Diameter of Conductor Approx. Weight Rated Strength Number of Wires  Diameter of Wires Diameter of Conductor Approx. Weight Rated Strength
mm² mm mm kg/km daN mm mm kg/km daN Ω/km
16 7 1.83 5.49 50.4 5.43 7 1.84 5.52 50.8 6.04 1.7896
25 7 2.29 6.87 78.7 8.49 7 2.30 6.9 79.5 9.44 1.1453
40 7 2.89 8.67 125.9 13.58 7 2.91 8.73 127.1 15.1 0.7158
63 7 3.63 10.8 198.3 21.39 7 3.65 10.95 200.2 23.06 0.4545
100 19 2.78 13.9 316.3 33.95 19 2.79 13.95 319.3 37.76 0.2877
125 19 3.10 15.5 395.4 42.44 19 3.12 15.6 399.2 47.20 0.2302
160 19 3.51 17.55 506.1 54.32 19 3.53 17.65 511.0 58.56 0.1798
200 19 3.93 19.65 623.7 67.91 19 3.95 19.75 638.7 73.20 0.1439
250 19 4.39 21.95 790.8 84.68 19 4.41 22.05 798.4 91.50 0.1151
315 37 3.53 24.71 998.9 106.95 37 3.55 24.85 1008.4 115.29 0.0916
400 37 3.98 27.86 1268.4 135.81 37 4.0 28 1280.5 146.4o 0.0721
450 37 4.22 29.54 1426.9 152.79 37 4.24 29.68 1440.5 164.70 0.0641
500 37 4.45 31.15 1585.5 169.76 37 4.47 31.29 1600.6 183.oo 0.0577
560 61 3.67 33.03 1778.4 190.14 61 3.69 33.21 1795.3 204.95 0.0516
630 61 3.89 35.01 2000.7 213.90 61 3.91 35.19 2019.8 230.58 0.0458
710 61 4.13 37.17 2254.8 241.07 61 4.15 37.35 2276.2 259.86 0.0407
800 61 4.38 39.42 2540.6 271.62 61 4.4 39.6 2564.8 282.80 0.0361
900 91 3.81 41.91 2861.1 305.58 91 3.83 42.13 2888.3 329.40 0.0321
1000 91 4.01 44.11 3179.0 339.53 91 4.03 44.33 3209.3 366.00 0.0289
1120 91 4.25 46.75 3560.5 380.27 91 4.27 46.97 3594.4 409.92 0 0258
1250 91 4.49 49.39 3973.7 424.41    

 
BS EN50183

Code Name  Calculated
Cross Section
No..Dia.of Wires  Overall Diameter Weight Rated Strength
  mm² No./mm mm kg/km kN
Box 18.8 7/1.85 5.55 51.4 5.55
Acacia 23.8 7/2.08 6.24 64.9 7.02
Almond 30.1 7/2.34 7.02 82.2 8.88
Cedar 35.5 7/2.54 7.62 96.8 10.46
Deodar 42.2 7/2.77 8.31 115.2 12.44
Fir 47.8 7/2.95 8.85 130.6 14.11
Hazel 59.9 7/3.30 9.90 163.4 17.66
Pine 71.6 7/3.61 10.8 195.6 21.14
Holly 84.1 7/3.91 11.7 229.5 24.79
Willow 89.7 7/4.04 12.1 245,0 26.47
Oak 118.9 7/4.65 14.0 324.5 35.07
Mulberry 150.9 19/3.18 15.9 414.3 44.52
Ash 180.7 19/3.48 17.4 496.1 53.31
Elm 211.0 19/3.76 18.8 579.2 62.24
Poplar 239.4 37/2.87 20.1 659.4 70.61
Sycamore 303.2 37/3.23 22.6 835.2 89.40
Upas 362.1 37/3.53 24.7 997.5 106.82
Yew 479.0 37/4.06 28.4 1319.6 141.31
Totara 498.1 37/4.14 29.0 1372.1 146.93
Rubus 586.9 61/3.50 31.5 1622.0 173.13
Sorbus 659.4 61/3.71 33.4 1822.5 194.53
Araucaria 821.1 61/4.14 37.3 2269.4 242.24
Redwood 996.2 61/4.56 41.0 2753.2 293.88

 
Din 48201

Code number Calculated area Number of wires Diameter of wire Overall diameter of conductor Linear mass Rated tensile strength Max. DC resistance at 20ºC
mm2 mm2   mm mm kg/km daN Ω/km
16 15.89 7 1.70 5.1 43 444 2.0910
25 24.25 7 2.10 6.3 66 677 1.3703
35 34.36 7 2.50 7.5 94 960 0.9669
50 49.48 7 3.00 9.0 135 1382 0.6714
50 48.35 19 1.80 9.0 133 1350 0.6905
70 65.81 19 2.10 10.5 181 1838 0.5073
95 93.27 19 2.50 12.5 256 2605 0.3579
120 116.99 19 2.80 14.0 322 3268 0.2854
150 147.11 37 2.25 15.8 406 4109 0.2274
185 181.62 37 2.50 17.5 500 5073 0.1842
240 242.54 61 2.25 20.3 670 6774 0.1383
300 299.43 61 2.50 22.5 827 8363 0.1120
400 400.14 61 2.89 26.0 1104 11176 0.0838
500 499.63 61 3.23 29.1 1379 13960 0.06709
625 626.20 91 2.96 32.6 1732 17490 0.0540
800 802.09 91 3.35 36.9 2218 22402 0.0418
1000 999.71 91 3.74 41.1 2767 27922 0.0335

We are China AAC/AAAC/ACSR/ Conductor Overhead Bare Conductors manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular AAAC Conductor Products

DIN 48201 AAAC Aluminum Alloy Conductor AAAC 120mm2

All Aluminum Alloy Conductor AAAC

Overhead ACSR, AAC, AAAC, Acss/Tw, Accc, Aacsr, Acar

Electric Wire Cable Overhead AAAC Aluminium Alloy Conductor

All Aluminum Alloy Conductor AAAC Canton Cairo Darien Flint Greely

Code Name Box BS En 50182 AAAC Conductor Cable

Popular AAC Products

Rose/Iris/Pansy All Alumininum Conductors with ASTM B 231

Stranded All Aluminum AAC Conductor

Aerial Bundled Conductor 70mm2 Hard drawn Aluminum ABC Cable for 400V Distribution Line

IEC 61089 Standard Overhead Conductors AAC Aluminium Cable 25mm

Conductor, ABC, LV, 3X185+120+16 mm2, MDPE Cable UV Resistant, 0.6/1kV

ASTM BS IEC Standard Customized Overhead Cable ACSR AAAC Conductor

Popular ASTM B399 Products

Aluminum Conductor Steel Reinforced ACSR Conductor

Overhead Aluminium Bare ACSR Conductor for Transmission Line

All Conductor Steel Reinforced ACSR Conductor

All Aluminum Alloy Conductor 500sqmm AAAC Conductor for Overhead Power Transmission Lines

DIN48201 All Aluminum Alloy Condcutor AAAC 25mm2

High Quality Bare Conductor AAAC Conductor

Popular wuhancable Products

Aluminum Wire with Steel Core Reinforced

Multicore Yjv, Yjy, Yjlv, Yjly XLPE Insulated Flexible Flame Retardant Control Power Low Smoke Cable

600/1000V Bare AAC/AAAC/ACSR Cable BS Standard ACSR Conductor

Overhead Conductors AAC/ AAAC/ ACSR Bare Conductors

ASTM B231 Overhead Bare Stranded All Aluminum AAC Bitterroot Conductor

USA Sizes ASTM B232 Overhead Conductor Steel Reinforced ACSR Thrasher

Tags: , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION