AAC Cable BS 215-1 Electrical Cable and Wire Transmission Line Central Africa
AAC Cable BS 215-1 Electrical Cable and Wire Transmission Line Central Africa image
Get Latest Price Request a quote
Quick Details
Product Details
Applications:
Concentric lay stranded Aluminium Conductor ( AAC) is made up of one or more strands of hard drawn 1350 aluminum alloy. These conductors are used in low, medium and high voltage overhead lines. AAC has seen extensive use in urban areas where spans are usually short but high conductivity us required. The excellent corrosion resistance of aluminium has made AAC a conductor of choice in coastal areas. Because of its relatively poor strength to weight ratio, AAC had limited use in transmission lines and rural distribution because of long spans utilized.
The excellent corrosion resistance of aluminium has made AAC a conductor of choice in coastal areas.Although aluminium-to-copper connections can be made, it is better to use aluminium conductors for service connections, as various forms of covered cable are available for this purpose.
Advantage:
1. high Current Carrying Capacity
2. excellent resistance to corrosion
3. Ideal for use in coastal area
4. suitable for low & medium voltage lines in urban area
Standard
ASTM B231, BS215, IEC 61089, DIN 48201, BS EN 50182
| IEC 61089 | ||||||
| Code Name | Nominal | No./Nominal diameter of wires |
Approximate Overall Diameter |
Approximate Weight |
Nominal Breaking Load |
Nominal DC Resistance at 20°C |
| mm2 | No./mm | mm | kg/km | KN | ohm/km | |
| 10 | 10 | 7/1.35 | 4.05 | 27.4 | 2 | 2.8633 |
| 16 | 16 | 7/1.71 | 5.13 | 43.8 | 3 | 1.7896 |
| 25 | 25 | 7/2.13 | 6.39 | 68.4 | 4.5 | 1.1453 |
| 40 | 40 | 7/2.70 | 8.1 | 109.4 | 6.8 | 0.7158 |
| 63 | 63 | 7/3.39 | 10.17 | 172.3 | 10.4 | 0.4545 |
| 100 | 100 | 19/2.59 | 12.95 | 274.8 | 17 | 0.2877 |
| 125 | 125 | 19/2.89 | 14.45 | 343.6 | 21.3 | 0.2302 |
| 160 | 160 | 19/3.27 | 16.35 | 439.8 | 26.4 | 0.1798 |
| 200 | 200 | 19/3.66 | 18.3 | 549.7 | 32 | 0.1439 |
| 250 | 250 | 19/4.09 | 20.45 | 687.1 | 40 | 0.1151 |
| 315 | 315 | 37/3.29 | 23.03 | 867.9 | 52 | 0.0916 |
| 400 | 400 | 37/3.71 | 25.97 | 1102 | 64 | 0.0721 |
| 450 | 450 | 37/3.94 | 27.58 | 1239.8 | 72 | 0.0641 |
| 500 | 500 | 37/4.15 | 29.05 | 1377.6 | 80 | 0.0577 |
| 560 | 560 | 37/4.39 | 30.73 | 1542.9 | 89.6 | 0.0515 |
| 630 | 630 | 61/3.63 | 32.67 | 1738.3 | 100.8 | 0.0458 |
| 710 | 710 | 61/3.85 | 34.65 | 1959.1 | 113.6 | 0.0407 |
| 800 | 800 | 61/4.09 | 36.81 | 2207.4 | 128 | 0.0361 |
| 900 | 900 | 61/4.33 | 38.97 | 2483.3 | 144 | 0.0321 |
| 1000 | 1000 | 61/4.57 | 41.13 | 2759.2 | 160 | 0.0289 |
| 1120 | 1120 | 91/3.96 | 43.56 | 3093.5 | 179.2 | 0.0258 |
| 1250 | 1250 | 91/4.18 | 45.98 | 3452.6 | 200 | 0.0231 |
| 1400 | 1400 | 91/4.43 | 48.73 | 3866.9 | 224 | 0.0207 |
| 1500 | 1500 | 91/4.58 | 50.38 | 4143.1 | 240 | 0.0193 |
| ASTM B231/B 231M | |||||||
| Code Name | Nominal Area |
No./Nominal diameter of wires |
Approximate Overall Diameter |
Approximate Weight |
Nominal Breaking Load |
Nominal DC Resistance at 20°C |
|
| AWG or MCM | mm2 | No./mm | mm | kg/km | KN | ohm/km | |
| Peachbell | 6 | 13.3 | 7/1.56 | 4.68 | 36.6 | 2.5 | 2.1477 |
| Rose | 4 | 21.1 | 7/1.96 | 5.88 | 58.2 | 3.9 | 1.3606 |
| Iris | 2 | 33.6 | 7/2.47 | 7.41 | 92.6 | 6 | 0.8567 |
| Pansy | 1 | 42.4 | 7/2.78 | 8.34 | 116.6 | 7.3 | 0.6763 |
| Poppy | 1/0.0 | 53.5 | 7/3.12 | 9.36 | 147.2 | 8.8 | 0.5369 |
| Aster | 2/0.0 | 67.4 | 7/3.50 | 10.5 | 185.7 | 11.1 | 0.4267 |
| Phlox | 3/0.0 | 85 | 7/3.93 | 11.79 | 233.9 | 13.5 | 0.3384 |
| Oxlip | 4/0.0 | 107.2 | 7/4.42 | 13.26 | 295.2 | 17 | 0.2675 |
| Valerian | 250 | 126.7 | 19/2.91 | 14.55 | 348.6 | 20.7 | 0.2274 |
| Sneezewort | 250 | 126.7 | 7/4.80 | 14.4 | 348.8 | 20.1 | 0.2269 |
| Laurel | 266.8 | 135.2 | 19/3.01 | 15.05 | 372.2 | 22.1 | 0.2125 |
| Daisy | 266.8 | 135.2 | 7/4.96 | 14.88 | 372.3 | 21.4 | 0.2125 |
| Peony | 300 | 152 | 19/3.19 | 15.95 | 418.3 | 24.3 | 0.1892 |
| Tulip | 336.4 | 170.5 | 19/3.38 | 16.9 | 469.5 | 27.3 | 0.1686 |
| Daffodil | 350 | 177.3 | 19/3.45 | 17.25 | 487.9 | 28.4 | 0.1618 |
| Canna | 397.5 | 201.4 | 19/3.67 | 18.35 | 554.9 | 31.6 | 0.143 |
| Goldentuft | 450 | 228 | 19/3.91 | 19.55 | 627.6 | 35 | 0.126 |
| Syringa | 477 | 241.7 | 37/2.88 | 20.16 | 664.8 | 38.6 | 0.1192 |
| Cosmos | 477 | 241.7 | 19/4.02 | 20.1 | 664.8 | 37 | 0.1192 |
| Hyacinth | 500 | 253.3 | 37/2.95 | 20.65 | 696.8 | 40.5 | 0.1136 |
| Zinnia | 500 | 253.3 | 19/4.12 | 20.6 | 697.1 | 38.9 | 0.1134 |
| Dahlia | 556.5 | 282 | 19/4.35 | 21.75 | 775.8 | 43.3 | 0.1018 |
| Mistletoe | 556.5 | 282 | 37/3.12 | 21.84 | 775.7 | 44.3 | 0.1016 |
| Meadowsweet | 600 | 304 | 37/3.23 | 22.61 | 836.3 | 47.5 | 0.0948 |
| Orchid | 636 | 322.3 | 37/3.33 | 23.31 | 886.9 | 50.4 | 0.0892 |
| Heuchera | 650 | 329.4 | 37/3.37 | 23.59 | 907.4 | 51.7 | 0.0871 |
| Flag | 700 | 354.7 | 61/2.72 | 24.48 | 975.8 | 57.1 | 0.0811 |
| Varbena | 700 | 354.7 | 37/3.49 | 24.43 | 975.7 | 55.4 | 0.0812 |
| Nasturtium | 715.5 | 362.6 | 61/2.75 | 24.75 | 998.5 | 58.4 | 0.0793 |
| Violet | 715.5 | 362.6 | 37/3.53 | 24.71 | 998.5 | 56.7 | 0.0794 |
| Cattail | 750 | 380 | 61/2.82 | 25.38 | 1046 | 60.3 | 0.0754 |
| Petunia | 750 | 380 | 37/3.62 | 25.34 | 1046 | 58.6 | 0.0755 |
| Lilac | 795 | 402.8 | 61/2.90 | 26.1 | 1110 | 63.8 | 0.0713 |
| Arbutus | 795 | 402.8 | 37/3.72 | 26.04 | 1109 | 61.8 | 0.0715 |
| BS 215 Part 1 | |||||||
| Code name | Nominal | No./Nominal diameter of wires |
Sectional Area | Overall | Weight | Calculated Breaking Load | Max.D.C. Resistance at 20ºC |
| mm² | No./mm | mm² | mm | kg/km | daN | Ω/Km | |
| Midge | 22 | 7/2.06 | 23.33 | 6.18 | 64 | 399 | 1.227 |
| Aphis | 25 | 3/3.35 | 26.44 | 7.22 | 74 | 411 | 1.081 |
| Gnat | 25 | 7/2.21 | 26.85 | 6.63 | 73 | 459 | 1.066 |
| Weevil | 30 | 3/3.66 | 31.56 | 7.89 | 86 | 486 | 0.9082 |
| Mosquito | 35 | 7/2.59 | 36.88 | 7.77 | 101 | 603 | 0.7762 |
| Ladybird | 40 | 7/2.79 | 42.8 | 8.37 | 117 | 687 | 0.6689 |
| Ant | 50 | 7/3.10 | 52.83 | 9.3 | 145 | 828 | 0.5419 |
| Fly | 60 | 7/3.40 | 63.55 | 10.2 | 174 | 990 | 0.4505 |
| Bluebottle | 70 | 7/3.66 | 73.65 | 10.98 | 202 | 1134 | 0.3881 |
| Earwig | 75 | 7/3.78 | 78.55 | 11.34 | 215 | 1194 | 0.3644 |
| Grasshopper | 80 | 7/3.91 | 84.05 | 11.73 | 230 | 1278 | 0.3406 |
| Clegg | 90 | 7/4.17 | 95.6 | 12.51 | 262 | 1453 | 0.2994 |
| Wasp | 100 | 7/4.39 | 106 | 13.17 | 290 | 1600 | 0.2702 |
| Beetle | 100 | 19/2.67 | 106.4 | 13.35 | 293 | 1742 | 0.2704 |
| Bee | 125 | 7/4.90 | 132 | 14.7 | 361 | 1944 | 0.2169 |
| Cricket | 150 | 7/5.36 | 157.9 | 16.08 | 432 | 2385 | 0.1818 |
| Hornet | 150 | 19/3.25 | 157.6 | 16.25 | 434 | 2570 | 0.1825 |
| Caterpillar | 175 | 19/3.53 | 185.9 | 17.65 | 511 | 2863 | 0.1547 |
| Chafer | 200 | 19/3.78 | 213.2 | 18.9 | 587 | 3240 | 0.1349 |
| Spider | 225 | 19/3.99 | 237.6 | 19.95 | 654 | 3601 | 0.1211 |
| Cockroach | 250 | 19/4.22 | 265.7 | 21.1 | 731 | 4040 | 0.1083 |
| Butterfly | 300 | 19/4.65 | 322.7 | 23.25 | 888 | 4875 | 0.08916 |
| Moth | 350 | 19/5.00 | 373.1 | 25 | 1027 | 5637 | 0.07711 |
| Drone | 350 | 37/3.58 | 372.4 | 25.06 | 1027 | 5745 | 0.07741 |
| Locust | 400 | 19/5.36 | 428.7 | 26.8 | 1180 | 6473 | 0.0671 |
| Centipede | 400 | 37/3.78 | 415.2 | 26.46 | 1145 | 6310 | 0.06944 |
| Maybug | 450 | 37/4.09 | 486.1 | 28.63 | 1340 | 7401 | 0.05931 |
| Scorpion | 500 | 37/4.27 | 529.8 | 29.89 | 1461 | 7998 | 0.05441 |
| Cicada | 600 | 37/4.65 | 628.3 | 32.55 | 1732 | 9495 | 0.04588 |
| Tarantula | 750 | 37/5.23 | 794.9 | 36.61 | 2192 | 12010 | 0.03627 |
| BS EN 50182 | ||||||
| Code Name |
Nominal Area |
No. / Dia. of Wire |
Approx. Overall Diameter | Approx. Weight |
Calculated Breaking Load | Max.DC Resistance at 20° C |
| mm2 | No. / mm | mm | kg/km | kN | Ohm/km | |
| Box | 18.8 | 7/1.85 | 5.55 | 51.4 | 5.6 | 1.748 |
| Acacia | 23.8 | 7/2.08 | 6.24 | 64.9 | 7 | 1.3828 |
| Almond | 30.1 | 7/2.34 | 7.02 | 82.2 | 8.9 | 1.0926 |
| Cedar | 35.5 | 7/2.54 | 7.62 | 96.8 | 10.5 | 0.9273 |
| Deodar | 42.2 | 7/2.77 | 8.31 | 115.2 | 12.4 | 0.7797 |
| Fir | 47.8 | 7/2.95 | 8.85 | 130.6 | 14.1 | 0.6875 |
| Hazel | 59.9 | 7/3.30 | 9.9 | 163.4 | 17.7 | 0.5494 |
| Pine | 71.6 | 7/3.61 | 10.83 | 195.6 | 21.1 | 0.4591 |
| Holly | 84.1 | 7/3.91 | 11.73 | 229.5 | 24.8 | 0.3913 |
| Willow | 89.7 | 7/4.04 | 12.12 | 245 | 26.5 | 0.3665 |
| Oak | 118.9 | 7/4.65 | 13.95 | 324.5 | 35.1 | 0.2767 |
| Mulberry | 150.9 | 19/3.18 | 15.9 | 414.3 | 44.5 | 0.2192 |
| Ash | 180.7 | 19/3.48 | 17.4 | 496.1 | 53.3 | 0.183 |
| Elm | 211 | 19/3.76 | 18.8 | 579.2 | 62.2 | 0.1568 |
| Poplar | 239.4 | 37/2.87 | 20.09 | 659.4 | 70.6 | 0.1387 |
| Sycamore | 303.2 | 37/3.23 | 22.61 | 835.2 | 89.4 | 0.1095 |
| Upas | 362.1 | 37/3.53 | 24.71 | 997.5 | 106.8 | 0.0917 |
| Yew | 479 | 37/4.06 | 28.42 | 1319.6 | 141.3 | 0.0693 |
| Totara | 498.1 | 37/4.14 | 28.98 | 1372.1 | 146.9 | 0.0666 |
| Rubus | 586.9 | 61/3.50 | 31.5 | 1622 | 173.1 | 0.0567 |
| Sorbus | 659.4 | 61/3.71 | 33.39 | 1822.5 | 194.5 | 0.0505 |
| Araucaria | 821.1 | 61/4.14 | 37.26 | 2269.4 | 242.2 | 0.0406 |
| Redwood | 996.2 | 61/4.56 | 41.04 | 2753.2 | 293.9 | 0.0334 |
As a leading manufacture in China,Our customers come from around the world,Welcome to visit us at any time!
Just leave your message if you are interested in our products,We will contact you very soon!
We are China AAC Cable BS 215-1 Electrical Cable and Wire Transmission Line Central Africa manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAC Cable Electrical Cable BS 215-1 Products
Popular Electrical Cable and Wire Products
High Quality Buliding Wire Cables
0.6/1kv Copper XLPE Insulated Underground Electric Cable 5X25mm2 16mm2
Henan Jiapu Cable Good Quality Flat Wire PVC Insulated
Electrical Wire and Cable BV/BVVB.
Medium Voltage XLPE Insulated Power Cable
Electrical Wire and Cable BV/BVVB.
Popular kingyear Products
1cx400mm Sq. Medium Voltage Single Core Copper Conductor XLPE Insulated Metal Screened Power Cable
ASTM BS IEC Standards Overhead Bare Aluminium ACSR Conductor
Medium Voltage XLPE Insulated Swa Armoured Underground Electrical Power Cable 500mm2 3.6/6kv
Overhead Bare Aluminium/Aluminum ACSR Conductor 350mm2 Bison Sheep Antelope
Hot Sale Bare Stranded Overhead Alloy Aluminum AAAC Cable