Standard
BS EN50183,IEC 61089, ASTM B399,BS 3242, DIN 48204,GB/T1179-2008
Specification
Physical contents of aluminum alloy :-
1. Resistivity – 0.0326 Ohms mm2/m at 20°C
2. Density – 2.70 kgm/dm3 at 20°C
3. Coefficient of Linear Expansion – 23 x 10-6 / °C
4. Constant Mass Temperature Coefficient (a) – 0.00360/ °C
5. Material – Heat treated Al. Mg. Si. Alloy
– Approximately 0.5% Mg & 0.5% Si
ASTM B399
Code Name | Area | Size & Stranding of ACSR with Equal Diameter | No. & Diameter of wires | Overall Diameter | Weight | Nominal Breaking Load | ||
Nominal | Actual | |||||||
MCM | mm2 | AWG or MCM | Al/Steel | mm | mm | kg/km | kN | |
Akron | 30.58 | 15.48 | 6 | 6/1 | 7/1.68 | 5.04 | 42.7 | 4.92 |
Alton | 48.69 | 24.71 | 4 | 6/1 | 7/2.12 | 6.35 | 68.0 | 7.84 |
Ames | 77.47 | 39.22 | 2 | 6/1 | 7/2.67 | 8.02 | 108 | 12.45 |
Azusa | 123.3 | 62.38 | 1/0 | 6/1 | 7/3.37 | 10.11 | 172 | 18.97 |
Anaheim | 155.4 | 78.65 | 2/0 | 6/1 | 7/3.78 | 11.35 | 217 | 23.93 |
Amherst | 195.7 | 99.22 | 3/0 | 6/1 | 7/4.25 | 12.75 | 273 | 30.18 |
Alliance | 246.9 | 125.1 | 4/0 | 6/1 | 7/4.77 | 14.31 | 345 | 38.05 |
Butte | 312.8 | 158.6 | 266.8 | 26/7 | 19/3.26 | 16.30 | 437 | 48.76 |
Canton | 394.5 | 199.9 | 336.4 | 26/7 | 19/3.66 | 18.30 | 551 | 58.91 |
Cairo | 465.4 | 235.8 | 397.5 | 26/7 | 19/3.98 | 19.88 | 650 | 69.48 |
Darien | 559.5 | 283.5 | 477.0 | 26/7 | 19/4.36 | 21.79 | 781 | 83.52 |
Elgin | 652.4 | 330.6 | 556.5 | 26/7 | 19/4.71 | 23.54 | 911 | 97.42 |
Flint | 740.8 | 375.3 | 636.0 | 26/7 | 37/3.59 | 25.16 | 1035 | 108.21 |
Greely | 927.2 | 469.8 | 795.0 | 26/7 | 37/4.02 | 28.14 | 1295 | 135.47 |
IEC 61089
Code Number | A2 Conductor | A3 Conductor | Max.D.C. Resistance of Conductor at 20ºC | ||||||||
Number of Wires | Diameter of Wires | Diameter of Conductor | Approx. Weight | Rated Strength | Number of Wires | Diameter of Wires | Diameter of Conductor | Approx. Weight | Rated Strength | ||
mm² | – | mm | mm | kg/km | daN | – | mm | mm | kg/km | daN | Ω/km |
16 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 7 | 1.84 | 5.52 | 50.8 | 6.04 | 1.7896 |
25 | 7 | 2.29 | 6.87 | 78.7 | 8.49 | 7 | 2.30 | 6.9 | 79.5 | 9.44 | 1.1453 |
40 | 7 | 2.89 | 8.67 | 125.9 | 13.58 | 7 | 2.91 | 8.73 | 127.1 | 15.1 | 0.7158 |
63 | 7 | 3.63 | 10.8 | 198.3 | 21.39 | 7 | 3.65 | 10.95 | 200.2 | 23.06 | 0.4545 |
100 | 19 | 2.78 | 13.9 | 316.3 | 33.95 | 19 | 2.79 | 13.95 | 319.3 | 37.76 | 0.2877 |
125 | 19 | 3.10 | 15.5 | 395.4 | 42.44 | 19 | 3.12 | 15.6 | 399.2 | 47.20 | 0.2302 |
160 | 19 | 3.51 | 17.55 | 506.1 | 54.32 | 19 | 3.53 | 17.65 | 511.0 | 58.56 | 0.1798 |
200 | 19 | 3.93 | 19.65 | 623.7 | 67.91 | 19 | 3.95 | 19.75 | 638.7 | 73.20 | 0.1439 |
250 | 19 | 4.39 | 21.95 | 790.8 | 84.68 | 19 | 4.41 | 22.05 | 798.4 | 91.50 | 0.1151 |
315 | 37 | 3.53 | 24.71 | 998.9 | 106.95 | 37 | 3.55 | 24.85 | 1008.4 | 115.29 | 0.0916 |
400 | 37 | 3.98 | 27.86 | 1268.4 | 135.81 | 37 | 4.0 | 28 | 1280.5 | 146.4o | 0.0721 |
450 | 37 | 4.22 | 29.54 | 1426.9 | 152.79 | 37 | 4.24 | 29.68 | 1440.5 | 164.70 | 0.0641 |
500 | 37 | 4.45 | 31.15 | 1585.5 | 169.76 | 37 | 4.47 | 31.29 | 1600.6 | 183.oo | 0.0577 |
560 | 61 | 3.67 | 33.03 | 1778.4 | 190.14 | 61 | 3.69 | 33.21 | 1795.3 | 204.95 | 0.0516 |
630 | 61 | 3.89 | 35.01 | 2000.7 | 213.90 | 61 | 3.91 | 35.19 | 2019.8 | 230.58 | 0.0458 |
710 | 61 | 4.13 | 37.17 | 2254.8 | 241.07 | 61 | 4.15 | 37.35 | 2276.2 | 259.86 | 0.0407 |
800 | 61 | 4.38 | 39.42 | 2540.6 | 271.62 | 61 | 4.4 | 39.6 | 2564.8 | 282.80 | 0.0361 |
900 | 91 | 3.81 | 41.91 | 2861.1 | 305.58 | 91 | 3.83 | 42.13 | 2888.3 | 329.40 | 0.0321 |
1000 | 91 | 4.01 | 44.11 | 3179.0 | 339.53 | 91 | 4.03 | 44.33 | 3209.3 | 366.00 | 0.0289 |
1120 | 91 | 4.25 | 46.75 | 3560.5 | 380.27 | 91 | 4.27 | 46.97 | 3594.4 | 409.92 | 0 0258 |
1250 | 91 | 4.49 | 49.39 | 3973.7 | 424.41 | – | – | – | – |
BS EN50183
Code Name | Calculated Cross Section |
No..Dia.of Wires | Overall Diameter | Weight | Rated Strength |
mm² | No./mm | mm | kg/km | kN | |
Box | 18.8 | 7/1.85 | 5.55 | 51.4 | 5.55 |
Acacia | 23.8 | 7/2.08 | 6.24 | 64.9 | 7.02 |
Almond | 30.1 | 7/2.34 | 7.02 | 82.2 | 8.88 |
Cedar | 35.5 | 7/2.54 | 7.62 | 96.8 | 10.46 |
Deodar | 42.2 | 7/2.77 | 8.31 | 115.2 | 12.44 |
Fir | 47.8 | 7/2.95 | 8.85 | 130.6 | 14.11 |
Hazel | 59.9 | 7/3.30 | 9.90 | 163.4 | 17.66 |
Pine | 71.6 | 7/3.61 | 10.8 | 195.6 | 21.14 |
Holly | 84.1 | 7/3.91 | 11.7 | 229.5 | 24.79 |
Willow | 89.7 | 7/4.04 | 12.1 | 245,0 | 26.47 |
Oak | 118.9 | 7/4.65 | 14.0 | 324.5 | 35.07 |
Mulberry | 150.9 | 19/3.18 | 15.9 | 414.3 | 44.52 |
Ash | 180.7 | 19/3.48 | 17.4 | 496.1 | 53.31 |
Elm | 211.0 | 19/3.76 | 18.8 | 579.2 | 62.24 |
Poplar | 239.4 | 37/2.87 | 20.1 | 659.4 | 70.61 |
Sycamore | 303.2 | 37/3.23 | 22.6 | 835.2 | 89.40 |
Upas | 362.1 | 37/3.53 | 24.7 | 997.5 | 106.82 |
Yew | 479.0 | 37/4.06 | 28.4 | 1319.6 | 141.31 |
Totara | 498.1 | 37/4.14 | 29.0 | 1372.1 | 146.93 |
Rubus | 586.9 | 61/3.50 | 31.5 | 1622.0 | 173.13 |
Sorbus | 659.4 | 61/3.71 | 33.4 | 1822.5 | 194.53 |
Araucaria | 821.1 | 61/4.14 | 37.3 | 2269.4 | 242.24 |
Redwood | 996.2 | 61/4.56 | 41.0 | 2753.2 | 293.88 |
Din 48201
Code number | Calculated area | Number of wires | Diameter of wire | Overall diameter of conductor | Linear mass | Rated tensile strength | Max. DC resistance at 20ºC |
mm2 | mm2 | mm | mm | kg/km | daN | Ω/km | |
16 | 15.89 | 7 | 1.70 | 5.1 | 43 | 444 | 2.0910 |
25 | 24.25 | 7 | 2.10 | 6.3 | 66 | 677 | 1.3703 |
35 | 34.36 | 7 | 2.50 | 7.5 | 94 | 960 | 0.9669 |
50 | 49.48 | 7 | 3.00 | 9.0 | 135 | 1382 | 0.6714 |
50 | 48.35 | 19 | 1.80 | 9.0 | 133 | 1350 | 0.6905 |
70 | 65.81 | 19 | 2.10 | 10.5 | 181 | 1838 | 0.5073 |
95 | 93.27 | 19 | 2.50 | 12.5 | 256 | 2605 | 0.3579 |
120 | 116.99 | 19 | 2.80 | 14.0 | 322 | 3268 | 0.2854 |
150 | 147.11 | 37 | 2.25 | 15.8 | 406 | 4109 | 0.2274 |
185 | 181.62 | 37 | 2.50 | 17.5 | 500 | 5073 | 0.1842 |
240 | 242.54 | 61 | 2.25 | 20.3 | 670 | 6774 | 0.1383 |
300 | 299.43 | 61 | 2.50 | 22.5 | 827 | 8363 | 0.1120 |
400 | 400.14 | 61 | 2.89 | 26.0 | 1104 | 11176 | 0.0838 |
500 | 499.63 | 61 | 3.23 | 29.1 | 1379 | 13960 | 0.06709 |
625 | 626.20 | 91 | 2.96 | 32.6 | 1732 | 17490 | 0.0540 |
800 | 802.09 | 91 | 3.35 | 36.9 | 2218 | 22402 | 0.0418 |
1000 | 999.71 | 91 | 3.74 | 41.1 | 2767 | 27922 | 0.0335 |
Production process
Package
Package in Export Wooden or Steel Wooden or Steel Drums
About us
We were founded in 2007, located in Gongyi Henan,China. We have 2 factories (Headquarters Factory-produce insulated cables and Zhulin branch-produce bare conductors), occupies total area of more than 300,000 square meters, with building area 230,000 square meters.
Certificate
As first rank of the cable supplier in China, we have obtained CCC, ISO9001, ISO14001, OHSAS certificates, passed the SGS and BV test, and our brand "RMJT" be given China famous brand.
Customer Visit
We have a professional sales team with each of them has engaged in this job for 3-10 years, so that we can provide the comprehensive and professional technology for you. With the perfect quality and after sales service, till now we have exported to more than 80 countries, welcome to visit us and establish win-win establish relationship!
Contact us
We are China ACSR ACSR /Aw Overhead Conductor for Power Transmission manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAAC Cable Products
High Quality Manufacturer ACSR AAC AAAC Overhead Bare Conductor
AAAC/Aluminum Alloy Bare Conductor
Overhead All Aluminum Stranded Conductor AAC Conductor for Aerial Cable
ASTM B232 795mcm ACSR Conductor AAC AAAC Conductor for Overhead Line
100mm 200mm 300mm 500mm All Aluminum Stranded AAC Conductor Cable
Popular Overhead Transmission Line Products
Bison BS215 Stanard ACSR for Overhead Transmission Line
Line Post Composite Insulator for High Voltage Overhead Transmission Line
Power Cable Bare Conductor DIN ACSR 150/25 (Aluminum Conductor Steel Reinforced)
Overhead Bare Aluminium Conductor, ACSR Aluminium Conductor Steel Reinforced with BS Standard.
Overhead Aluminium Cable Bare Aluminium Conductor Steel Reinforced Overhead ACSR Conductor
100mm 125mm 160mm 200mm 250mm All Aluminum Stranded Conductor AAC AAAC Cable
Popular renmincable Products
NFC Standard Aluminium Conductor Single Core XLPE ABC Cable
ASTM B524 Standard Aluminium Conductor Alloy Reinforced Acar
Electric Aluminum Cable Aerial Bounded Cable ABC Cable 0.6/1kv
High Quality Rubber Flexible Cable
Ho7V_K PVC Insulated Flexible Electric Wire
AAAC Cable 120 Sq mm Single Core Aluminium Cable Price All Aluminium Conductor Specifications
Popular Transmission Line Products
High Voltage Xyay-70 Aerodynamic Type Glass Suspension Insulator String
ACSR 70/12mm2 Aluminimum Conductor Steel Reinforced for 20kV Distribution Networks
ACSR Conductor (Aluminum Conduct Steel Reinforced) ACSR Dove
High Voltage Aerodynamic Type Toughened Glass Isolators
BS215 All Aluminium Stranded Conductor 100mm2 AAC Wasp Conductor
Tags: AAAC Cable, Overhead Transmission Line, renmincable, Transmission Line