Air Break Switch Disconnector Hv Removable Isolating Links
Air Break Switch Disconnector Hv Removable Isolating Links image
Get Latest Price Request a quote
Quick Details
Product Details
The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.
IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) – a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.
SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.
4.2. DESIGN AND CONSTRUCTION
4.2.1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.
4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.
4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on ‘U’ type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.
4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.
4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.
4.2.7 The solid link shall be removable from the mounting by use of operating rod.
4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.
4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium (ACSR)conductor of up to 18.2mm diameter.
The rating of the complete isolator shall be as follows: –
Rated voltage
36 kV
Rated frequency
50 Hz
Rated lightning impulse withstand voltage
200 kV
Rated power frequency withstand voltage, dry
95 kV
Rated normal current
400 Amps
Rated short time withstand current for 3 sec, min.
18.0 kA
Minimum creepage distance of insulators
900 mm
S.No | DESCRIPTION | UNITS | BIDDER OFFERED VALUE |
1. | Rated Voltage | KV | 12 KV |
2. | Frequency | Hz | 50 Hz |
3 | Rated continuous current | A | 630 |
4 | Impulse withstand voltage to ground | KV | 95 |
5 | Impulse withstand voltage across gaps | KV | 110 |
6 | Dry one-minute power frequency withstand voltage to ground | KV | 35 |
7 | Dry one minute power frequency withstand voltage across gap | KV | 45 |
8 | Wet one minute power frequency withstand voltage to ground | KV | 30 |
9 | Limits of radio interference 10KV and 1000 K.C/Sec | 250 uV | |
10 | Temperature rise at rated current (max.) | 30oC at 50oC ambient | |
11 | Dimensions and mechanical ,Electrical values Of Polymer Insulator |
||
12 | Leaking distance | mm | 508 (minimum) |
13 | Dry arcing distance | mm | 210 (minimum) |
14 | Cantilever strength | kg | 400 |
15 | Tensile strength | kg | 1000 |
16 | Compressive strength | kg | 5400 |
17 | Tensile proof test load | kg | 700 |
18 | Dry power frequency flashover | KV | 85 |
19 | Wet power frequency flashover | KV | 55 |
20 | Dry one-minute power frequency withstand | KV | 70 |
21 | Wet one-minute power frequency withstand | KV | 45 |
22 | Impulse flash over positive | KV | 115 |
23 | Impulse flashover negative | KV | 140 |
24 | Power frequency puncture voltage | KV | 150 |
We are China Air Break Switch Disconnector Hv Removable Isolating Links manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Disconnector Switch Products
a. C Load Interrupter Air Switchs 11kv 630A Single Type
Strain Composite Epoxy Resin Polymer Long Rod Insulators
Gw5 Type Serial High Voltage Isolator Switch
33kv Isolator Current 2000A with Earth Switch Isolator
Popular jgtrade1 Products
High Quality 11kv 33kv Outdoor High Voltage Drop out Fuse Cut out Polymer
Top Quality Toughened Disc Glass Insulator
Best Price 11kv 200A Ceramic Types Drop out Fuses Cutout/Cut out Fuse
24 Kv Porcelain Pin-Type Insulator
Popular Rotary Switch Products
Rgw 1 Type Three Pole Outdoor Disconnector with Fuse -Bases (Export)
Gw High Voltage Isolation Disconnecting Outdoor Type Disconnector Switch
34.5/0.433kv, 500kVA Ground Mounted Distribution Transformer
Popular Switch Disconnector Products
Disconnect Switch 145 Kv, 40 Ka, 3150 a
High and Low Voltage Electroscope
Electrical Supplier 11kv to 66kv High Voltage Drop out Fuse
12kv Outdoor Disconnect Switch Three Phases
Gw13-72.5 Free Standing Earthing Switches
Factory Price 25kv High Voltage Electric Isolator
Tags: Disconnector Switch, jgtrade1, Rotary Switch, Switch Disconnector