Aluminum Conductor Alloy Reinforced Bare Overhead Concentric La Stranded Conductor

China 
                        Aluminum Conductor Alloy Reinforced Bare Overhead Concentric La Stranded Conductor
                      manufacture and supplier

Aluminum Conductor Alloy Reinforced Bare Overhead Concentric La Stranded Conductor image

Get Latest Price Request a quote

Quick Details

Aluminum Conductor Alloy Reinforced Bare Overhead Concentric La Stranded Conductor

bare conductor

ISO, CCC

Bare

AC Cable

Low and Medium Voltage Cable

Construction, Overhead, Power Station

Qing Dao or as Request

Jin Shui

Iron-Wooden Drum. Iron Drum

ASTM, DIN. IEC or as request

Zhengzhou, Hean, China

Product Details

Bare conductor—–AAC/AAAC/ACSR conductor
AAC, AAAC, ACSR, AACSR&ACAR conductor widely used in power transmission lines with various voltage levels. Since they have such good characteristics as simple structure, convenient installation and maintenance, low cost for the line, large transmission capacity and are also suitable for laying across rivers and valleys where special geographical teatures exist.

1. Specification:
(1) all aluminium conductor (AAC)
(2) all aluminimum alloy conductor(AAAC)
(3) aluminum conductor steel reinforced (ACSR)
(4) anti-corrosion type ACSR
(5) aluminimum conductor aluminimum clad steel reinforced(ACSR/AW)
(6)rear earth aluminimum conductor steel reinforced(ACSR/RE)
(7)aluminimum conductor aluminimum alloy reinforced(ACAR)

2. Elative manufacturing standards:
1). Standard: IEC61089, BS215 part2, ASTM B232, DIN48204, BS EN50182.
2). Specification: ACSR is composed by bare concentric-lay-stranded galvanized steel wire(s) with aluminum wires surrounded by one or more layers of helically. Greased ACSR can also be supplied.
3). Application: ACSR is widely used in overhead electric power transmission and distribution lines with
Various voltage levels.

All Aluminum Conductor(AAC)& Aluminum Conductor Steel Reinforced(ACSR))for ASTM
(AAC, ACCR, AAAC, ACSR) Generally Confirming to IS 398 (Part-I, II, IV), IEC-228
(AAAC) Conductor as per ASTM-B-399-1992
(AAAC) Conductor as per BS-3242-1970
(AAAC) Conductor IS: 398-IV-1994
(ACSR) as per ASTM-B-233-1992
(AAC) as per BS-215-1-1970
(AAC) as per IS-398-1: 1976
(AAC) as per ASTM-B-231-1990
(ACSR) as per IS: 398-II: 1976 & IS: 398-V: 1992
(ACSR) BS-215-II-1970
(AACSR) as per IEC-1089-1191
AAC(All aluminum conductor) are suited for overhead power line.

We can supply this conductor according to different recognized standards, distribution and transmission lines for distributing power.

Applications:
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.

Construction:
Aluminum alloy 1350-H-19 wires, concentrically stranded about a steel core. Core wire for ACSR is available with class A, B, or C galvanizing; ""aluminized"" aluminum coated (AZ); Or aluminum-clad (AW). Additional corrosion protection is available through the application of grease to the corrosion or infusion of the complete cable with grease.

Specifications:
ACSR bare conductor meets or exceeds the following ASTM specifications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-341 Aluminum-clad Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AW)
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ)
B-500 Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced (ACSR)

Notes:
Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 61.2% IACS for EC (1350) and 8% IACS for steel. AC (60Hz) resistance includes current dependent hysteresis loss factor for 1 and 3 layer constructions.
Current ratings are based on 75oC conductor temperature, 25oC ambient, 2ft/s wind, 96/watts/sq. Ft sun, 0.5 coefficients of emissivity and absorption.

Nominal
Alum
mm 2
Number/Diameter
mm
Calculation Area  
mm 2
Approx.
Overall Diameter
mm
 
Max. D. C.
Resistance
At 20  degrees Celsius
≤ Ω /km
 
Nominal breaking load
KN
 
Weight
kg/km
 
Al
 
Steel
 
Al
 
Steel
 
Total
10 6/1.50 1/1.50 10.62 1.77 12.39 4.50 2.706 4.14 43
20 6/2.11 1/2.11 20.94 3.49 24.43 6.33 1.368 7.88 85
25 6/2.36 1/2.36 26.25 4.37 30.62 7.08 1.093 9.61 106
30 6/2.59 1/2.59 31.61 5.27 36.88 7.77 0.9077 11.45 128
35 6/2.79 1/2.79 36.66 6.11 42.70 8.37 0.7822 13.20 149
40 6/3.00 1/3.00 42.41 7.07 49.48 9.00 0.6766 15.20 172
50 6/3.35 1/3.35 52.88 8.82 61.70 10.05 0.5426 18.35 214
60 6/3.66 1/3.66 63.18 10.53 73.71 10.98 0.4545 21.80 255
60 12/2.59 7/2.59 63.27 36.93 100.30 12.95 0.4567 53.00 465
70 6/3.99 1/3.99 74.82 12.47 87.29 11.97 0.3825 25.70 302
70 12/2.79 7/2.79 73.37 42.80 116.17 13.95 0.3936 61.20 538
75 6/4.10 1/4.10 79.20 13.20 92.40 12.30 0.3622 27.20 320
80 6/4.22 1/4.22 83.88 13.98 97.86 12.66 0.3419 28.80 339
90 6/4.50 1/4.50 95.40 15.90 111.30 13.50 0.3007 32.70 386
100 6/4.72 1/4.72 105.00 17.50 122.50 14.16 0.2733 36.00 425
100 6/4.72 7/1.57 105.00 13.50 118.50 14.15 0.2733 32.70 394
100 7/4.39 7/1.93 105.80 20.44 126.20 14.57 0.2712 40.90 450
125 6/5.28 7/1.75 131.30 16.80 148.10 15.81 0.2184 40.70 492
125 26/2.54 7/1.91 132.10 20.10 152.20 15.89 0.2187 46.40 522
125 18/3.05 1/3.05 130.30 7.25 137.50 15.25 0.2189 29.80 419
125 30/2.36 7/2.36 131.10 30.60 161.70 16.52 0.2202 58.00 602
150 30/2.59 7/2.59 158.00 36.90 194.90 18.13 0.1828 69.20 726
150 18/3.35 1/3.35 158.70 8.80 167.50 16.57 0.1815 35.70 506
175 30/2.79 7/2.79 183.40 42.80 226.20 19.53 0.1576 79.80 842
175 18/3.61 1/3.61 184.20 10.30 194.50 18.05 0.1563 41.10 587
200 30/3.00 7/3.00 212.00 49.50 261.50 21.00 0.1363 92.25 974
225 30/3.18 7/3.18 238.50 55.60 294.20 22.26 0.1212 109.60 1095
250 30/3.35 7/3.35 264.00 61.60 325.60 23.45 0.1093 111.10 1213
300 30/3.71 7/3.71 324.30 75.70 400.00 25.97 0.0891 135.70 1489
350 30/3.99 7/3.99 374.10 87.30 461.40 27.93 0.07704 155.90 1718
350 54/2.97 7/2.97 373.10 48.40 421.50 26.73 0.07727 118.20 1411
350 54/3.00 7/3.00 381.80 49.50 431.30 27.00 0.07573 120.90 1444
200 18/3.86 1/3.86 210.60 11.70 222.30 19.30 0.013670 46.55 671
400 30/4.27 7/4.27 429.30 100.20 529.50 29.89 0.06726 178.50 1971
400 54/3.18 7/3.18 428.90 55.30 484.50 28.62 0.06740 131.90 1621
450 30/4.50 7/4.50 477.00 111.30 588.30 31.50 0.06056 198.20 2190
450 54/3.35 7/3.35 475.20 61.60 536.80 30.15 0.06073 145.70 1797
500 54/3.53 7/3.53 528.70 68.50 597.20 31.77 0.05470 161.10 1999

We are China Aluminum Conductor Alloy Reinforced Bare Overhead Concentric La Stranded Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular AAAC Conductor Products

High Quality AAAC (All Aluminium Alloy Conductors) for Overhead

95mm2 AAAC Conductor All Aluminum Alloy Conductor Bare Conductor

High Performance AAAC All Alumum Alloy Conductor

British Sizes 3242 All Aluminum Alloy Condcutor AAAC Box

IEC 61089 Standard AAAC Aluminium Conductor Overhead Power Cable

6201 Bare All Aluminum Alloy Conductor AAAC Electric Electrical Cable 25mm2 50mm2 70mm2 95mm2 120mm2 150mm2 240mm2 Power Cable

Popular ACSR Conductor Products

USA Sizes ASTM B232 Overhead Conductor Steel Reinforced ACSR Leghorn

ACSR 120/20 Aluminum Conductor Steel Reinforced Overhead Conductor

ACSR Aluminum Conductor Steel Reinforced DIN Types of ACSR Conductor

Bare Conductor ACSR 95/15, ACSR Conductor to DIN Standard

IEC61089 Aluminum Conductor Steel Reinforced A1/S1a Conductor ACSR 16mm2 25mm2 100mm2

Electrical Power Transmission Line, ACSR Aluminium Conductor Steel Reinforced, Overhead Bare Cable Wires.

Popular Aluminum Alloy Stranded Conductor Products

  • No related articles
  • Popular jsgroup Products

    600V 16mm 4 Core XLPE Insulation Underground Armoured Power Cable

    Power Electric Cable Service Concentric with Pilot Communication Wire Cable Electrical Pilot Cables

    Rubber Sheath Flexible Cable (GB 5013-1997, JB 8735-1998)

    AAC AAAC ACSR Acar for Power Transmission Bare Aluminum Conductor (95mm and customized)

    Flame Resistant Insulated Armoured PVC Power Cable

    450/750V H07bn4-F Flame Resistant Copper Rubber Cable Resistant for Medium Mechanical Stress

    Tags: , , ,