Bare Conductor of AAAC Conductor All Aluminum
Bare Conductor of AAAC Conductor All Aluminum image
Get Latest Price Request a quote
Basic Info.
Product Description
APPLICATION:
Used as bare overhead conductor for primary and secondary distribution. Designed for utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics.
1.AAAC conductors are extensively used for overhead distribution and transmission lines adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction.
2. The aluminum alloy conductors are used in replace of singlelayer ACSR conductors to reduce power loss in overhead distribution and transmission lines,when replacing the aluminum conductor steel reinforced , the AAAC can save 5-8% of the construction cost.
3.AAAC referred to have higher strength but lower conductivity than pure aluminum.Being lighter, alloy conductors can sometimes be used to replace the conventional ACSR.
STANDARDS:
ASTM B399, BS EN50183 ,BS 3242,DIN 48201,IEC 61089
| All Aluminium Alloy Conductors(AAAC) ASTM B 399 | |||||||
| AREA | Stranding | Wire Dia. | Approx. overall diameter |
Weight | Nominal Breaking Load |
Nom. DC resistance at 20 Deg. |
|
| Nominal | Actual | ||||||
| AWGorMCM | (mm2) | (mm) | (mm) | (kg/km) | (kN) | (ohm/km) | |
| 6 | 13.3 | 7 | 1.554 | 4.67 | 37 | 4.22 | 2.5199 |
| 4 | 21.15 | 7 | 1.961 | 5.89 | 58 | 6.71 | 1.5824 |
| 2 | 33.63 | 7 | 2.474 | 7.42 | 93 | 10.68 | 0.9942 |
| 1/0 | 53.48 | 7 | 3.119 | 9.36 | 148 | 16.97 | 0.6256 |
| 2/0 | 67.42 | 7 | 3.503 | 10.51 | 186 | 20.52 | 0.4959 |
| 3/0 | 85.03 | 7 | 3.932 | 11.8 | 234 | 25.86 | 0.3936 |
| 4/0 | 107.23 | 7 | 4.417 | 13.26 | 296 | 32.63 | 0.3119 |
| 250 | 126.66 | 19 | 2.913 | 14.57 | 349 | 38.93 | 0.2642 |
| 300 | 152.1 | 19 | 3.193 | 15.97 | 419 | 46.77 | 0.2199 |
| 350 | 177.35 | 19 | 3.447 | 17.24 | 489 | 52.25 | 0.1887 |
| 400 | 202.71 | 19 | 3.686 | 18.43 | 559 | 59.74 | 0.1650 |
| 450 | 228 | 19 | 3.909 | 19.55 | 629 | 67.19 | 0.1467 |
| 500 | 253.35 | 19 | 4.12 | 20.6 | 698 | 74.64 | 0.1321 |
| 550 | 278.6 | 37 | 3.096 | 21.67 | 768 | 83.80 | 0.1202 |
| 600 | 303.8 | 37 | 3.233 | 22.63 | 838 | 91.38 | 0.1102 |
| 650 | 329.25 | 37 | 3.366 | 23.56 | 908 | 97.94 | 0.1016 |
| 700 | 354.55 | 37 | 3.493 | 24.45 | 978 | 102.20 | 0.0944 |
| 750 | 380.2 | 37 | 3.617 | 25.32 | 1049 | 109.60 | 0.0880 |
| 800 | 405.15 | 37 | 3.734 | 26.14 | 1117 | 116.80 | 0.0826 |
| 900 | 456.16 | 37 | 3.962 | 27.73 | 1258 | 131.50 | 0.0733 |
| 1000 | 506.71 | 37 | 4.176 | 29.23 | 1399 | 146.10 | 0.0660 |
| AAAC (Characteristics of A2 Conductors) IEC 61089 | |||||||
| Code number | Area | Number of wires |
Diameter | Linear mass |
Rated strength |
D.C resistance | |
| Wire | Cond | ||||||
| mm2 | mm | mm | kg/km | kN | Ohm/km | ||
| 16 | 18.4 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 1.7896 |
| 25 | 28.8 | 7 | 2.29 | 6.86 | 78.7 | 8.49 | 1.1453 |
| 40 | 46 | 7 | 2.89 | 8.68 | 125.9 | 13.58 | 0.7158 |
| 63 | 72.5 | 7 | 3.63 | 10.9 | 198.3 | 21.39 | 0.4545 |
| 100 | 115 | 19 | 2.7 | 13.9 | 316.3 | 33.95 | 0.2877 |
| 125 | 144 | 19 | 3.1 | 15.5 | 395.4 | 42.44 | 0.2302 |
| 160 | 184 | 19 | 3.51 | 17.6 | 506.1 | 54.32 | 0.1798 |
| 200 | 230 | 19 | 3.93 | 19.6 | 632.7 | 67.91 | 0.1439 |
| 250 | 288 | 19 | 4.39 | 22 | 790.8 | 84.88 | 0.1151 |
| 315 | 363 | 37 | 3.53 | 24.7 | 998.9 | 106.95 | 0.0916 |
| 400 | 460 | 37 | 3.98 | 27.9 | 1268.4 | 135.81 | 0.0721 |
| 450 | 518 | 37 | 4.22 | 29.6 | 1426.9 | 152.79 | 0.0641 |
| 500 | 575 | 37 | 4.45 | 31.2 | 1585.5 | 169.76 | 0.0577 |
| 560 | 645 | 61 | 3.67 | 33 | 1778.4 | 190.14 | 0.0516 |
| 630 | 725 | 61 | 3.89 | 35 | 2000.7 | 213.9 | 0.0458 |
| 710 | 817 | 61 | 4.13 | 37.2 | 2254.8 | 241.07 | 0.0407 |
| 800 | 921 | 61 | 4.38 | 39.5 | 2540.6 | 271.62 | 0.0361 |
| 900 | 1036 | 91 | 3.81 | 41.8 | 2861.1 | 305.68 | 0.0321 |
| 1000 | 1151 | 91 | 4.01 | 44.1 | 3179 | 339.53 | 0.0289 |
| 1120 | 1289 | 91 | 4.25 | 46.7 | 3560.5 | 380.27 | 0.0258 |
| 1250 | 1439 | 91 | 4.49 | 49.4 | 3973.7 | 424.41 | 0.0231 |
| All Aluminlum Alloy Conductors(AAAC) BS EN 50183 | |||||||
| Code Name | Area | No.of wires | Diameter | Mass per unit length |
Rated strength | DC resistance | |
| Wire | Cond. | ||||||
| mm2 | mm | mm | kg/km | kN | Ω/km | ||
| BOX | 18.8 | 7 | 1.85 | 5.55 | 51.4 | 5.55 | 1.7480 |
| ACACLA | 23.8 | 7 | 2.08 | 6.24 | 64.9 | 7.02 | 1.3828 |
| ALMOND | 30.1 | 7 | 2.34 | 7.02 | 82.2 | 8.88 | 1.0926 |
| CEDAR | 35.5 | 7 | 2.54 | 7.62 | 96.8 | 10.46 | 0.9273 |
| DEODAR | 42.2 | 7 | 2.77 | 8.31 | 115.2 | 12.44 | 0.7797 |
| FIR | 47.8 | 7 | 2.95 | 8.85 | 130.6 | 14.11 | 0.6875 |
| HAZEL | 59.9 | 7 | 3.3 | 9.90 | 163.4 | 17.66 | 0.5494 |
| PLNE | 71.6 | 7 | 3.61 | 10.8 | 195.6 | 21.14 | 0.4591 |
| HOLLY | 84.1 | 7 | 3.91 | 11.7 | 229.5 | 24.79 | 0.3913 |
| WILLOW | 89.7 | 7 | 4.04 | 12.1 | 245.0 | 26.47 | 0.3665 |
| OAK | 118.9 | 7 | 4.65 | 14.0 | 324.5 | 35.07 | 0.2767 |
| MULBERRY | 150.9 | 19 | 3.18 | 15.9 | 414.3 | 44.52 | 0.2192 |
| ASH | 180.7 | 19 | 3.48 | 17.4 | 496.1 | 53.31 | 0.1830 |
| ELM | 211 | 19 | 3.76 | 18.8 | 579.2 | 62.24 | 0.1568 |
| POPLAR | 239.4 | 37 | 2.87 | 20.1 | 659.4 | 70.61 | 0.1387 |
| SYCAMORE | 303.2 | 37 | 3.23 | 22.6 | 835.2 | 89.40 | 0.1095 |
| UPAS | 362.1 | 37 | 3.53 | 24.7 | 997.5 | 106.82 | 0.0917 |
| YEW | 479 | 37 | 4.06 | 28.4 | 1319.6 | 141.31 | 0.0693 |
| TOTARA | 498.1 | 37 | 4.14 | 29.0 | 1372.1 | 146.93 | 0.0666 |
| RUBUS | 586.9 | 61 | 3.5 | 31.5 | 1622.0 | 173.13 | 0.0567 |
| SORBUS | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
| ARAUCARIA | 821.1 | 61 | 4.14 | 37.3 | 2269.4 | 242.24 | 0.0406 |
| REDWOOD | 996.2 | 61 | 4.56 | 41.0 | 2753.2 | 293.88 | 0.0334 |
| All Aluminium Alloy Conductors (AAAC) BS EN 50183 | |||||||
| Designation | Area | Stranding wire Dia. | Overall Diameter |
Nominal Breaking Load |
Nominal DC Resistance at 20ºC |
Standard Weight | |
| mm2 | No | Φ | mm | kN | Ohm/km | kg/km | |
| ASTER 22 | 22 | 7 | 2 | 6 | 7.15 | 1.4989 | 60 |
| ASTER 34.4 | 34.4 | 7 | 2.5 | 7.5 | 11.17 | 0.9593 | 93.8 |
| ASTER 54.6 | 54.6 | 7 | 3.15 | 9.45 | 17.73 | 0.6042 | 148.9 |
| ASTER 75.5 | 75.5 | 19 | 2.25 | 11.3 | 24.55 | 0.4388 | 207.4 |
| ASTER 117 | 117 | 19 | 2.8 | 14 | 38.02 | 0.2833 | 321.2 |
| ASTER 148 | 148.1 | 19 | 3.15 | 15.8 | 48.12 | 0.2239 | 406.5 |
| ASTER 181.6 | 181.6 | 37 | 2.5 | 17.5 | 59.03 | 0.1831 | 500.3 |
| ASTER 228 | 227.8 | 37 | 2.8 | 19.6 | 74.04 | 0.146 | 627.6 |
| ASTER 288 | 288.3 | 37 | 3.15 | 22.1 | 93.71 | 0.1154 | 794.3 |
| ASTER 366 | 366.2 | 37 | 3.55 | 24.9 | 115.36 | 0.0908 | 1008.9 |
| ASTER 570 | 570.2 | 61 | 3.45 | 31.1 | 185.33 | 0.0585 | 1576 |
| ASTER 851 | 850.7 | 91 | 3.45 | 38 | 276.47 | 0.0394 | 2360.7 |
| ASTER 1144 | 1143.5 | 91 | 4 | 44 | 360.22 | 0.0293 | 3173.4 |
| ASTER 1600 | 1595.9 | 127 | 4 | 52 | 502.72 | 0.021 | 4427.5 |
| AAAC 6201- All Aluminium Alloy Conductor AS 1531 | |||||||
| Code Name | Strands/ Wire Diameter |
Overall Diameter (Approx) |
Calculated Equivalent Aluminium Area |
Sectional Area |
Approx. Mass |
Calculated Minimum Breaking Load |
D.C.Resistence at 20ºC |
| mm | mm | mm2 | mm2 | kg/km | kN | Ω/km | |
| Agate | 7/1.75 | 5.25 | 14.3 | 16.84 | 46 | 4.71 | 1.972 |
| Amethyst | 7/2.25 | 6.75 | 23.7 | 27.83 | 76 | 7.78 | 1.194 |
| Diamond | 7/2.50 | 7.50 | 29.3 | 34.36 | 94 | 9.64 | 0.967 |
| Dolomite | 7/2.75 | 8.25 | 35.4 | 41.58 | 114 | 11.6 | 0.799 |
| Emerald | 7/3.00 | 9.00 | 42.2 | 49.48 | 136 | 13.9 | 0.671 |
| Garnet | 7/3.75 | 11.3 | 65.8 | 77.28 | 211 | 21.7 | 0.43 |
| Jade | 7/4.50 | 13.5 | 94.8 | 111.3 | 304 | 31.2 | 0.298 |
| Jasper | 7/4.75 | 14.3 | 106 | 124.0 | 340 | 34.8 | 0.268 |
| Opal | 19/3.25 | 16.3 | 134 | 157.6 | 433 | 44.2 | 0.212 |
| Patronite | 19/3.50 | 17.5 | 155 | 182.80 | 502 | 51.3 | 0.183 |
| Pearl | 19/3.75 | 18.8 | 178 | 209.8 | 577 | 58.8 | 0.159 |
| Ruby | 37/3.00 | 21.0 | 221 | 261.60 | 720 | 73.5 | 0.128 |
| Ruthenium | 37/3.25 | 22.8 | 260 | 307.00 | 845 | 86.1 | 0.109 |
| Rutile | 19/4.75 | 23.8 | 285 | 336.7 | 925 | 94.4 | 0.09991 |
| Sapphire | 37/3.75 | 26.3 | 345 | 408.50 | 1125 | 115 | 0.0819 |
| Spinel | 61/3.25 | 29.3 | 427 | 506.10 | 1396 | 135 | 0.0662 |
| Tantalum | 61/3.50 | 31.5 | 495 | 586.90 | 1620 | 156 | 0.0572 |
| Topaz | 61/3.75 | 33.8 | 568 | 673.40 | 1858 | 179 | 0.0498 |
| Zircon | 91/4.50 | 49.5 | 1220 | 1447 | 3997 | 384 | 0.0232 |
We are China Bare Conductor of AAAC Conductor All Aluminum manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAAC Conductor Products
ACSR Bare Conductor Aluminum Conductor Steel Reinforced
AAAC Cable, Overhead All Aluminum Alloy Conductor for Power Transmission
Aluminum Alloy Price AAAC All Aluminium Alloy Conductor
BS Standard 175mm2 Aluminum Alloy Conductor AAAC Elm Conductor
AAAC Conductor En 50183 All Aluminum Alloy Conductor Bare Conductor for Overhead Transmission Lines
BS Standard Bare Conductor Dog ACSR
Popular Aluminum Alloy Conductor Products
British Sizes 3242 All Aluminum Alloy Condcutor AAAC Araucaria
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201 with Grease
Overhead Transmission Line Aluminium Conductor AAAC 54.6mm2
Overhead Almelec Conductor AAAC Bare Conductor 120mm2
75.5 Sq. mm Aster AAAC Conductor Bare Aluminum Alloy Conductor
Manufacturer All Aluminium Alloy Conductor-AAAC Conductor with BS EN50183
Popular Bare Conductor of AAAC Conductor All Aluminum Products
Popular renmincable Products
BS183galvanized Steel Wire Gsw Used for Guy/Stay Wire
N2xby N2xfy Ry Nyy N2xy Copper Aluminium Standard PVC XLPE Power Cable
Copper Core PVC Insulated Electrical Wire BV Wire
16mm Armoured Cable 3 Core Aluminum Conductor XLPE Insulated Cable
33kv PVC / XLPE Insulated Overhead Electric Transmission Aerial Bundled Cable
Tags: AAAC Conductor, Aluminum Alloy Conductor, Bare Conductor of AAAC Conductor All Aluminum, renmincable