Bare Overhead Aluminum Stranded Conductor AAC Conductor BS215 for Power Transmission
Bare Overhead Aluminum Stranded Conductor AAC Conductor BS215 for Power Transmission image
Get Latest Price Request a quote
Quick Details
Product Details
(1)Production capacity:2000 ton/month
(2)MOQ:1km
(3)Delivery:5~15 officail days.
(4)Standards:IEC,ASTM,DIN,BS; or according to customers’ requirements.
(5)Delivery length:as per customers’ request.
1.Description
AAC Conductor, All Aluminium Conductor
AAC conductor is widely used in power transmission lines with various voltage levels.
2. Construction
Aluminum alloy 1350-H-19 wires. Additional corrosion protection is available through the application of grease to the corrosion or infusion of the complete cable with grease.
3. Refered Standards
(1). IEC 61089: Round wire concentric lay overhead electrical stranded conductors
(2). DIN 48 201-5: All Aluminium Conductors
(3). BS 215-1: Aluminium strander conductors
(4). ASTM B231: Stranded Specification for Concentric-Lay-Stranded Aluminium 1350 Conductors
(5). AS 1531: Conductors-Bare overhead-Aluminium and aluminium alloy
4.Your best choice: Huatong Cable Inc.
(1) ,More than 30 years experience.
(2) ,100,000m² factory,200 staffs,annual output 100,000 metic tons.
(3) ,Sound Quality Control
– Material inspection;
– manufacturing inspection;
– Finished products inspection;
– Inspection before delivery.
– Third party inspection.
– Inspection of storage at port of departure.
(4),ISO Certificated.
(5),Plenty of material and lobor gurantee the delivery prompt and price competitive.
(6),24/7 service.
5.Bare Conductor Types
(1) all aluminum conductor (AAC)
(2) all aluminum alloy conductor(AAAC)
(3) aluminum conductor steel reinforced (ACSR)
(4) anti-corrosion type ACSR
(5) aluminum conductor aluminum clad steel reinforced(ACSR/AW)
(6) rear earth aluminum conductor steel reinforced(ACSR/RE)
(7) aluminum conductor aluminum alloy reinforced(ACAR)
6.BS215 Part1 Standard
| Code name | Nominal aluminum area |
Stranding and wire diameter |
Sectional area |
Overall diameter |
Linear mass |
Max. DC resistance at 20 ºC |
Rated strength | Final modulus of elasticity |
Coefficient of linear expansion |
| mm 2 | mm | mm 2 | mm | kg/km | Ω/km | daN | hbar | /ºC | |
| Midge | 22 | 7/2.06 | 23.33 | 6.18 | 63.8 | 1.227 | 399 | 5900 | 23.0×10 -6 |
| Aphis | 25 | 3/3.35 | 26.40 | 7.2 | 73 | 1.081 | 411 | 5900 | 23.0×10 -6 |
| Gnat | 25 | 7/2.21 | 26.8 | 6.6 | 73 | 1.066 | 459 | 5900 | 23.0×10 -6 |
| Weevil | 30 | 3/3.66 | 31.6 | 7.9 | 86 | 0.9082 | 486 | 5900 | 23.0×10 -6 |
| Mosquito | 35 | 7/2.59 | 37.0 | 7.8 | 101 | 0.7762 | 603 | 5900 | 23.0×10 -6 |
| Ladybird | 40 | 7/2.79 | 42.8 | 8.4 | 117 | 0.6689 | 687 | 5900 | 23.0×10 -6 |
| Ant | 50 | 7/3.10 | 52.83 | 9.30 | 145 | 0.5419 | 828 | 5900 | 23.0×10 -6 |
| Fly | 60 | 7/3.40 | 63.55 | 10.20 | 174 | 0.4505 | 990 | 5900 | 23.0×10 -6 |
| Bluebottle | 70 | 7/3.66 | 73.7 | 11.0 | 202 | 0.3881 | 1134 | 5900 | 23.0×10 -6 |
| Earwig | 75 | 7/3.78 | 78.5 | 11.4 | 215 | 0.3644 | 1194 | 5900 | 23.0×10 -6 |
| Grasshopper | 80 | 7/3.91 | 84.1 | 11.7 | 230 | 0.3406 | 1278 | 5900 | 23.0×10 -6 |
| Clegg | 90 | 7/4.17 | 95.6 | 12.5 | 262 | 0.2994 | 1453 | 5900 | 23.0×10 -6 |
| Wasp | 100 | 7/4.39 | 106.0 | 13.17 | 290 | 0.2702 | 1600 | 5900 | 23.0×10 -6 |
| Beetle | 100 | 19/2.67 | 106.0 | 13.4 | 293 | 0.2704 | 1742 | 5600 | 23.0×10 -6 |
| Bee | 125 | 7/4.90 | 132.0 | 14.7 | 361 | 0.2169 | 1944 | 5600 | 23.0×10 -6 |
| Cricket | 150 | 7/5.36 | 157.9 | 16.1 | 432 | 0.1818 | 2385 | 5600 | 23.0×10 -6 |
| Hornet | 150 | 19/3.25 | 157.6 | 16.25 | 434 | 0.1825 | 2570 | 5600 | 23.0×10 -6 |
| Caterpillar | 175 | 19/3.53 | 186 | 17.7 | 512 | 0.1547 | 2863 | 5600 | 23.0×10 -6 |
| Chafer | 200 | 19/3.78 | 213.2 | 18.9 | 587 | 0.1349 | 3240 | 5600 | 23.0×10 -6 |
| Spider | 225 | 19/3.99 | 236.9 | 20.0 | 652 | 0.1211 | 3601 | 5600 | 23.0×10 -6 |
| Cockroach | 250 | 19/4.22 | 265.7 | 21.10 | 731 | 0.1083 | 4040 | 5600 | 23.0×10 -6 |
| Butterfly | 300 | 19/4.65 | 322.7 | 23.25 | 888 | 0.08916 | 4875 | 5600 | 23.0×10 -6 |
| Moth | 350 | 19/5.00 | 373.2 | 25.0 | 1027 | 0.07711 | 5637 | 5600 | 23.0×10 -6 |
| Drone | 350 | 37/3.58 | 373.3 | 25.1 | 1029 | 0.07741 | 5745 | 5600 | 23.0×10 -6 |
| Locust | 400 | 19/5.36 | 428.5 | 26.8 | 1179 | 0.06710 | 6473 | 5600 | 23.0×10 -6 |
| Centipede | 400 | 37/3.78 | 415.2 | 26.46 | 1145 | 0.06944 | 6310 | 5600 | 23.0×10 -6 |
| Maybug | 450 | 37/4.09 | 486.9 | 28.6 | 1342 | 0.05931 | 7401 | 5600 | 23.0×10 -6 |
| Scorpion | 500 | 37/4.27 | 529.5 | 29.9 | 1460 | 0.05441 | 7998 | 5600 | 23.0×10 -6 |
| Cicada | 600 | 37/4.65 | 628.6 | 32.6 | 1733 | 0.04588 | 9495 | 5600 | 23.0×10 -6 |
| Tarantula | 750 | 37/5.23 | 794.6 | 36.6 | 2191 | 0.03627 | 12010 | 5600 | 23.0×10 -6 |
7.ASTM B231 Standard
| Code word | Size of Conductor |
Stranding and Wire Diameter | Overall Diameter | Max.D.C. Resistance at 20°C | Code word | Size of Conductor | Stranding and Wire Diameter | Overall Diameter | Max.D.C. Resistance at 20°C |
| AWG or MCM | mm | mm | ohm/km | AWG or MCM | mm | mm | ohm/km | ||
| Peachbell | 6 | 7/1.554 | 4.67 | 2.1692 | Verbena | 700 | 37/3.493 | 24.45 | 0.0813 |
| Rose | 4 | 7/1.961 | 5.89 | 1.3624 | Nasturtium | 715.5 | 61/2.75 | 24.76 | 0.0795 |
| Lris | 2 | 7/2.474 | 7.42 | 0.8577 | Violet | 715.5 | 37/3.533 | 24.74 | 0.0795 |
| Pansey | 1 | 7/2.776 | 8.33 | 0.6801 | Cattail | 750 | 61/2.817 | 25.35 | 0.0759 |
| Poppy | 1/0 | 7/3.119 | 9.36 | 0.5390 | Petunia | 750 | 37/3.617 | 25.32 | 0.0759 |
| Aster | 2/0 | 7/3.503 | 10.51 | 0.4276 | Lilac | 795 | 61/2.90 | 26.11 | 0.0715 |
| Phlox | 3/0 | 7/3.932 | 11.80 | 0.3390 | Arbutus | 795 | 37/3.724 | 26.06 | 0.0715 |
| Oxlip | 4/0 | 7/4.417 | 13.26 | 0.2688 | Snapdragon | 900 | 61/3.086 | 27.78 | 0.0632 |
| Valerian | 250 | 19/2.913 | 14.57 | 0.2275 | Cockscomb | 900 | 37/3.962 | 27.73 | 0.0632 |
| Sneezewort | 250 | 7/4.80 | 14.4 | 0.2275 | Goldenrod | 954 | 61/3.177 | 28.6 | 0.0596 |
| Laurel | 266.8 | 19/3.01 | 15.05 | 0.2133 | Magnolia | 954 | 37/4.079 | 28.55 | 0.0596 |
| Daisy | 266.8 | 7/4.96 | 14.9 | 0.2133 | Camellia | 1000 | 61/3.251 | 29.36 | 0.0569 |
| Peony | 300 | 19/3.193 | 15.97 | 0.1896 | Hawkweed | 1000 | 37/4.176 | 29.23 | 0.0569 |
| Tulip | 336.4 | 19/3.381 | 16.91 | 0.1691 | Larkspur | 1033.5 | 61/3.307 | 29.76 | 0.0550 |
| Daffodil | 350 | 19/3.447 | 17.24 | 0.1625 | Bluebell | 1033.5 | 37/4.244 | 29.72 | 0.0550 |
| Canna | 397.5 | 19/3.673 | 18.36 | 0.1431 | Marigold | 1113 | 61/3.432 | 30.89 | 0.0511 |
| Goldentuft | 450 | 19/3.909 | 19.55 | 0.1264 | Hawthorn | 1192.5 | 61/3.551 | 31.05 | 0.0477 |
| Syringa | 477 | 37/2.882 | 20.19 | 0.1193 | Narcissus | 1272 | 61/3.668 | 33.02 | 0.0477 |
| Cosmos | 477 | 19/4.023 | 20.12 | 0.1193 | Columbine | 1351.5 | 61/3.78 | 34.01 | 0.0421 |
| Hyacinth | 500 | 37/2.951 | 20.65 | 0.1138 | Carnation | 1431 | 61/3.89 | 35.03 | 0.0398 |
| Zinnia | 500 | 19/4.12 | 20.6 | 0.1138 | Gladiolus | 1510.5 | 61/4.00 | 35.09 | 0.0376 |
| Dahlia | 556.5 | 19/4.346 | 21.73 | 0.1022 | Coreopsis | 1590 | 61/4.099 | 36.51 | 0.03568 |
| Mistletoe | 556.5 | 37/3.114 | 21.79 | 0.1022 | Jessamine | 1750 | 61/4.302 | 38.72 | 0.0325 |
| Meadowsweet | 600 | 37/3.233 | 22.63 | 0.0948 | Cowslip | 2000 | 91/3.76 | 41.40 | 0.02866 |
| Orchid | 636 | 37/3.33 | 23.31 | 0.0894 | Lupine | 2500 | 91/4.21 | 46.30 | 0.0230 |
| Heuchera | 650 | 37/3.366 | 23.56 | 0.0875 | Trillium | 3000 | 127/3.90 | 50.75 | 0.0192 |
| Flag | 700 | 61/2.72 | 24.48 | 0.0813 | Bluebonnet | 3500 | 127/4.21 | 54.80 | 0.01653 |
8.IEC 41089
| Code Number | Area | Number of Wires | Diameter | Linear Mass | Rated Strength | Max.D.C.Resistence at 20ºC | |
| mm2 | Wire | Cond. | kg/km | kN | Ω/km | ||
| 10 | 10 | 7 | 1.35 | 4.05 | 27.4 | 1.95 | 2.8633 |
| 16 | 16 | 7 | 1.71 | 5.12 | 43.8 | 3.04 | 1.7896 |
| 25 | 25 | 7 | 2.13 | 6.4 | 68.4 | 4.5 | 1.1453 |
| 40 | 40 | 7 | 2.7 | 8.09 | 109.4 | 6.8 | 0.7158 |
| 63 | 63 | 7 | 3.39 | 10.2 | 172.3 | 10.39 | 0.4545 |
| 100 | 100 | 19 | 2.59 | 12.9 | 274.8 | 17 | 0.2877 |
| 125 | 125 | 19 | 2.89 | 14.5 | 343.6 | 21.25 | 0.2302 |
| 160 | 160 | 19 | 3.27 | 16.4 | 439.8 | 26.4 | 0.1798 |
| 200 | 200 | 19 | 3.66 | 18.3 | 549.7 | 32 | 0.1439 |
| 250 | 250 | 19 | 4.09 | 20.5 | 687.1 | 40 | 0.1151 |
| 315 | 315 | 37 | 3.29 | 23 | 867.9 | 51.97 | 0.0916 |
| 400 | 400 | 37 | 3.71 | 26 | 1102 | 64 | 0.0721 |
| 450 | 450 | 37 | 3.94 | 27.5 | 1239.8 | 72 | 0.0641 |
| 500 | 500 | 37 | 4.15 | 29 | 1377.6 | 80 | 0.0577 |
| 560 | 560 | 37 | 4.39 | 30.7 | 1542.9 | 89.6 | 0.0515 |
| 630 | 630 | 61 | 3.63 | 32.6 | 1738.3 | 100.8 | 0.0458 |
| 710 | 710 | 61 | 3.85 | 34.6 | 1959.1 | 113.6 | 0.0407 |
| 800 | 800 | 61 | 4.09 | 36.8 | 2207.4 | 128 | 0.0361 |
| 900 | 900 | 61 | 4.33 | 39 | 2483.3 | 144 | 0.0321 |
| 1000 | 1000 | 61 | 4.57 | 41.1 | 2759.2 | 160 | 0.0289 |
| 1120 | 1120 | 91 | 3.96 | 43.5 | 3093.5 | 179.2 | 0.0258 |
| 1250 | 1250 | 91 | 4.18 | 46 | 3452.6 | 200 | 0.0231 |
| 1400 | 1400 | 91 | 4.43 | 48.7 | 3866.9 | 224 | 0.0207 |
| 1500 | 1500 | 91 | 4.58 | 50.4 | 4143.1 | 240 | 0.0193 |
9.din 48201
| Code Number | Caculated Area | Stranding and wire Diameter | Overall Diameter | Linear Mass | Calculated Breaking Load | Max D.C.Resistance at 20ºC |
| mm2 | mm2 | mm | mm | kg/km | daN | Ω,km |
| 16 | 15.89 | 7/1.70 | 5.1 | 44 | 290 | 1.8018 |
| 25 | 24.25 | 7/2.10 | 6.3 | 67 | 425 | 1.1808 |
| 35 | 34.36 | 7/2 50 | 7.5 | 94 | 585 | 0.8332 |
| 50 | 49.48 | 7/3.00 | 9 | 135 | 810 | 0.5786 |
| 50 | 48.36 | 19/1.80 | 9 | 133 | 860 | 0.595 |
| 70 | 65.82 | 19/2.10 | 10.5 | 181 | 1150 | 0.4371 |
| 95 | 93.27 | 19/2.50 | 12.5 | 256 | 1595 | 0.3084 |
| 120 | 117 | 19/2.50 | 14 | 322 | 1910 | 0.2459 |
| 150 | 147.1 | 37/2.25 | 15.2 | 406 | 2570 | 0.196 |
| 185 | 181.6 | 37/2.50 | 17.5 | 501 | 3105 | 0.1587 |
| 240 | 242.54 | 61/2.25 | 20.2 | 670 | 4015 | 0.1191 |
| 300 | 299.43 | 61/2.50 | 22.5 | 827 | 4850 | 0.0965 |
| 400 | 400.14 | 61/2.89 | 26 | 1105 | 6190 | 0.07221 |
| 500 | 499.83 | 61/3.23 | 29.1 | 1381 | 7600 | 0.05781 |
| 625 | 626.2 | 91/2.96 | 32.6 | 1733 | 9690 | 0.04625 |
| 500 | 802.1 | 91/3.35 | 36.8 | 2219 | 12055 | 0.03611 |
| 1000 | 999.71 | 91/3.74 | 41.1 | 2766 | 14845 | 0.02897 |
FAQ
1.How many years has Huatong Cable Inc. been in production?
Founded in 1993 , has made outstanding contribution to STATE GRID, CHINA SOUTH POWER GRID and the construction of domestic and foreign power market
2. What kinds of products does Huatong Cable manufacture?
1)Bare Conductor ,such as AAC,AAAC,ACSR,ACAR,AACSR,ACSR/AW and so on;
2)Aerial Bundled Cable (1kV-35kV ),such as Duplex,Triplex,Quadruplex Drop Wires and so on;
3)PVC Insulated (Flexible ) Wire ;
4)PVC Insulated and Sheathed (Armoured) Power Cable;
5)Low, Medium, High Voltage (1kV-220kV) XLPE Insulated (Armoured) Power Cable;
6)Welding Cable, Control Cable, Concentric Cable, Rubber Sheathed Cable and so on;
3. What kind of certifications do you have?
CCC, ISO9001-2000, SGS
4.Which markets do you involve mainly in?
Our products have been exported mainly to Africa, Middle East, South-east Asia, South America,Central America,North America, Europe ,Australia, etc.
5. Which standards do you comply with when you produce the electrical wires and cables ?
We are able to produce electrical wires and cables based on GB, JB, IEC, BS, DIN, ASTM, JIS, NF, AS/NZS, CSA, etc. Meanwhile, we can design and manufacture the cables according to the samples and technical specification the customer supply.
6. What is the min.order quantity ?
It depends on the type and size of electrical wires and cables. For some small electrical wires, 100 meters can be accepted .But for the power cables with medium or high voltage, that should comply with the property of installed equipments. Anyhow,we will try our best to solve the problem and meet with the requirement If you have special request.
7. What is the production capacity per week or per month ?
For the bare conductor, we can finish 5000 tons within one month. For power cables, that depends on the type and size.
8. Do you supply the customers with installation service in foreign country ?
We don’t have professional installation teams in foreign country.But if that is necessary, we will recommend our partners to cooperate with you.
We are China Bare Overhead Aluminum Stranded Conductor AAC Conductor BS215 for Power Transmission manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Aluminum Stranded Conductor Products
Aluminum Stranded Conductor Overhead AAC
Aluminum Stranded Conductor XLPE Insulation Aerial Twisted Cable Overhead ABC Cable
Bare Stranded Conductor All Aluminum Conductor AAC AAAC Cable
Overhead ACSR Wire Dog and AAC/All Aluminium Alloy Conductor Bare Conductor
Bare Copper Conductor Stranded Bare Conductor with ASTM B Standard for Overhead Power Transmission
Popular Bare Conductor AAC Products
Bare Conductor Cable AAC ACSR AAAC
Bare Aluminum Conductor AAC with ISO Certificate
Bare Conductor AAC, AAAC, ACSR for Overhead
Power Transmission Line Steel Reinforced Bare Conductor AAC, AAAC, ACSR for Overhead
Popular huatongcable Products
Aluminum Conductor Steel Reinforced/ACSR Conductor/Bare Conductor
CCS Copper Clad Steel Wire for Power Transmission Line
Overhead Triplex Service Drop Crayfish Aerial Bundled Cable for Transmission Line
PV1-F; Twin Core Solar PV Cable; 2X6mm2; TUV Certified
Wholesale Price for Bare Conductor AAC/AAAC/ACSR Conductor
Bare Conductor Acar Electrical Conductor 1200mm2
Popular Overhead Conductor Products
Overhead Bare Aluminum Conductor All Aluminum Conductor AAC
ASTM B231 Overhead Bare Stranded All Aluminum AAC Cowslip Conductor
Steel Reinforced Aluminum Alloy Coductor
Quadruplex Service Drop ACSR Neutral Conductor Gelding
USA Sizes ASTM B232 Overhead Conductor Steel Reinforced ACSR Starling
Cable 4X16mm2 Electrical Power XLPE/PVC Insulated Copper/Aluminum
Tags: Aluminum Stranded Conductor, Bare Conductor AAC, huatongcable, Overhead Conductor