Building wire is used to carry electricity into or within buildings and structures, and can be employed for a variety of commercial and residential applications – including electrical wiring systems, power generators, motors and electrical lights. ACWU and NMWU, in particular, are well-suited for direct earth burial and wiring in hazardous locations. Stranded copper wire is often used for overhead electrical transmission and distribution, and for grounding electrical systems where high conductivity and flexibility is required.
450/750V PVC Insulated (Non-Sheathed) Cables to BS 6004
Reference No 6491X
Single Core PVC Insulated
| Size of conductor | Nominal thickness of insulation mm |
Mean overall diameter Upper limit mm |
Approx. net weight per km kg |
|
| Nominal cross-sectional area mm2 |
Number and diameter of wires no./mm |
|||
| 1.0 | 1/1.13 | 0.6 | 2.8 | 14 |
| 1.5 | 1/1.38 | 0.7 | 3.3 | 20 |
| 1.5 | 7/0.50 | 0.7 | 3.4 | 20 |
| 2.5 | 1/1.78 | 0.8 | 3.9 | 33 |
| 2.5 | 7/0.67 | 0.8 | 4.2 | 34 |
| 4 | 1/2.25 | 0.8 | 4.4 | 51 |
| 4 | 7/0.85 | 0.8 | 4.8 | 51 |
| 6 | 1/2.76 | 0.8 | 4.9 | 67 |
| 6 | 7/1.04 | 0.8 | 5.4 | 71 |
| 10 | 1/3.57 | 1.0 | 6.4 | 110 |
| 10 | 7/1.35 | 1.0 | 6.8 | 120 |
| 16 | 1/4.50 | 1.0 | 7.3 | 170 |
| 16 | 7/1.70 | 1.0 | 8.0 | 180 |
| 25 | 7/2.14 | 1.2 | 9.8 | 285 |
| 35 | 19/1.53 | 1.2 | 11.0 | 380 |
| 50 | 19/1.78 | 1.4 | 13.0 | 510 |
| 70 | 19/2.14 | 1.4 | 15.0 | 715 |
| 95 | 19/2.52 | 1.6 | 17.0 | 990 |
| 120 | 37/2.03 | 1.6 | 19.0 | 1230 |
| 150 | 37/2.25 | 1.8 | 21.0 | 1510 |
| 185 | 37/2.52 | 2.0 | 23.5 | 1900 |
| 240 | 61/2.25 | 2.2 | 26.5 | 2490 |
| 300 | 61/2.52 | 2.4 | 29.5 | 3050 |
| 400 | 61/2.85 | 2.6 | 33.5 | 3900 |
| 500 | 61/3.20 | 2.8 | 37.0 | 4880 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.
2.Colors of standard: red, black, blue, white,brown, grey, green, yellow,
450/750V PVC Insulated (Non-Sheathed) Flexible Conductor General Purpose Cables to BS 6004
Harmonized Code
Designation H07V-K
Single Core PVC Insulated
| Size of conductor | Nominal thickness of insulation mm |
Mean overall diameter Upper limit mm |
jytopcable.en. weight per km kg |
|
| Nominal cross-sectional area mm2 |
Number and diameter of wires no./mm |
|||
| 1.0 | 32/0.20 | 0.6 | 3.0 | 16 |
| 1.5 | 30/0.25 | 0.7 | 3.5 | 21 |
| 2.5 | 50/0.25 | 0.8 | 4.2 | 33 |
| 4 | 56/0.30 | 0.8 | 4.8 | 50 |
| 6 | 84/0.30 | 0.8 | 6.3 | 70 |
| 10 | 80/0.40 | 1.0 | 7.6 | 120 |
| 16 | 126/0.40 | 1.0 | 8.8 | 175 |
| 25 | 196/0.40 | 1.2 | 11.0 | 290 |
| 35 | 276/0.40 | 1.2 | 12.5 | 400 |
| 50 | 396/0.40 | 1.4 | 14.5 | 565 |
| 70 | 360/0.50 | 1.4 | 17.0 | 770 |
| 95 | 475/0.50 | 1.6 | 19.0 | 1010 |
| 120 | 608/0.50 | 1.6 | 21.0 | 1260 |
| 150 | 756/0.50 | 1.8 | 23.5 | 1580 |
| 185 | 925/0.50 | 2.0 | 26.0 | 1900 |
| 240 | 1221/0.50 | 2.2 | 29.5 | 2500 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.
2.Colors of standard: red, black, brown, grey,orange, white, violet, pink, green/yellow, yellow
300/500V PVC Insulated PVC Sheathed Cables to BS 6004
Reference No 6181y
Single Core PVC Insulated and PVC Sheathed
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Mean overall diameter |
jytopcable.en. weight per km kg |
||
| Nominal cross-sectional area mm2 |
Number and diameter of wires mm |
Lower limit mm |
Upper limit mm |
|||
| 1.0 | 1/1.13 | 0.6 | 0.8 | 3.8 | 4.5 | 28 |
| 1.5 | 1/1.38 | 0.7 | 0.8 | 4.2 | 4.9 | 35 |
| 2.5 | 1/1.78 | 0.8 | 0.8 | 4.8 | 5.8 | 50 |
| 4 | 7/0.85 | 0.8 | 0.9 | 5.4 | 6.8 | 75 |
| 6 | 7/1.04 | 0.8 | 0.9 | 6.0 | 7.4 | 100 |
| 10 | 7/1.35 | 1.0 | 0.9 | 7.2 | 8.8 | 155 |
| 16 | 7/1.70 | 1.0 | 1.0 | 8.4 | 10.5 | 225 |
| 25 | 7/2.14 | 1.2 | 1.1 | 10.0 | 12.5 | 340 |
| 35 | 19/1.53 | 1.2 | 1.1 | 11.0 | 13.5 | 445 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.sheathed with PVC compound.
2.Core colors: red, black.Sheath colour: grey or white.
Reference No 6192y
Flat Twin
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Mean overall dimensions |
Approx. net weight per km kg |
||
| Nominal cross-sectional area mm2 |
Number and diameter of wires mm |
Lower limit mm |
Upper limit mm |
|||
| 1.0 | 1/1.13 | 0.6 | 0.9 | 4.0*6.2 | 4.7*7.4 | 55 |
| 1.5 | 1/1.38 | 0.7 | 0.9 | 4.4*7.0 | 5.4*8.4 | 70 |
| 2.5 | 1/1.78 | 0.8 | 1.0 | 5.2*8.4 | 6.2*9.8 | 105 |
| 4 | 7/0.85 | 0.8 | 1.0 | 5.6*9.6 | 7.2*11.5 | 150 |
| 6 | 7/1.04 | 0.8 | 1.1 | 6.4*10.5 | 8.0*13.0 | 205 |
| 10 | 7/1.35 | 1.0 | 1.2 | 7.8*13.0 | 9.6*16.0 | 325 |
| 16 | 7/1.70 | 1.0 | 1.3 | 9.0*15.5 | 11.0*18.5 | 465 |
Notes
1.Conductor of high conductivity copper,wires insulated with PVC compound.sheathed with PVC compound.
2.Color of sheath:grey or white,
300/500V PVC Insulated PVC Sheathed Cables to BS 6004
Reference No 6193y
Three Core (Flat)
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Mean overall diameter |
Approx. net weight per km kg |
||
| Nominal cross-sectional area mm2 |
Number and diameter of wires mm |
Lower limit mm |
Upper limit mm |
|||
| 1.0 | 1/1.13 | 0.6 | 0.9 | 4.0*8.4 | 4.7*9.8 | 77 |
| 1.5 | 1/1.38 | 0.7 | 0.9 | 4.4*9.8 | 5.4*11.5 | 100 |
| 2.5 | 1/1.78 | 0.8 | 1.0 | 5.2*11.5 | 6.2*13.5 | 150 |
| 4 | 7/0.85 | 0.8 | 1.1 | 5.8*13.5 | 7.4*16.5 | 230 |
| 6 | 7/1.04 | 0.8 | 1.1 | 6.4*15.0 | 8.0*18.0 | 300 |
| 10 | 7/1.35 | 1.0 | 1.2 | 7.8*19.0 | 9.6*22.5 | 485 |
| 16 | 7/1.70 | 1.0 | 1.3 | 9.0*22.0 | 11.0*26.5 | 700 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.Sheathed with PVC compound.
2.Core colors: red, yellow and blue,(yellow in centre) Sheath colors: grey or white.
Reference No 6242y
Flat-Twin with Bare Earth-continuity Conductor
| Size of conductor | Nominal thickness of insulation mm |
Size of earth conductivity conductor no./mm |
Nominal thickness of sheath mm |
Mean overall dimensions |
Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires mm |
Lower limit mm |
Upper limit mm |
||||
| 1.0 | 1/1.13 | 0.6 | 1/1.13 | 0.9 | 4.0*7.2 | 4.7*8.6 | 70 |
| 1.5 | 1/1.38 | 0.7 | 1/1.13 | 0.9 | 4.4*8.2 | 5.4*9.6 | 85 |
| 2.5 | 1/1.78 | 0.8 | 1/1.13 | 1.0 | 5.2*9.4 | 6.2*11.0 | 120 |
| 4 | 7/0.85 | 0.8 | 1/1.38 | 1.0 | 5.6*10.5 | 7.2*13.0 | 175 |
| 6 | 7/1.04 | 0.8 | 1/1.78 | 1.1 | 6.4*12.5 | 8.0*15.0 | 240 |
| 10 | 7/1.35 | 1.0 | 7/0.85 | 1.2 | 7.8*15.5 | 9.6*19.0 | 390 |
| 16 | 7/1.70 | 1.0 | 7/1.04 | 1.3 | 9.0*18 | 11.0*22.0 | 560 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.Sheathed with PVC compound.
2.Core colors: red and black. Sheath colors:grey or white.
300/500V PVC Insulated PVC Sheathed Cables to BS 6004
Reference No 6243y
Three-core (Flat) with Bare
Earth-continuity Conductor
| Size of conductor | Nominal thickness of insulation mm |
Size of earth- conduct -ivity conductor No/mm |
Nominal thickness of sheath mm |
Mean overall dimensions |
Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires mm |
Lower limit mm |
Upper limit mm |
||||
| 1.0 | 1/1.13 | 0.6 | 1/1.13 | 0.9 | 4.0*9.6 | 4.7*11.0 | 92 |
| 1.5 | 1/1.38 | 0.7 | 1/1.13 | 0.9 | 4.4*10.5 | 5.4*12.5 | 115 |
| 2.5 | 1/1.78 | 0.8 | 1/1.13 | 1.0 | 5.2*12.5 | 6.2*14.5 | 170 |
| 4 | 7/0.85 | 0.8 | 1/1.38 | 1.1 | 5.8*14.5 | 7.4*18.0 | 255 |
| 6 | 7/1.04 | 0.8 | 1/1.78 | 1.1 | 6.4*16.5 | 8.0*20.0 | 340 |
| 10 | 7/1.35 | 1.0 | 7/0.85 | 1.2 | 7.8*21.0 | 9.6*25.5 | 550 |
| 16 | 7/1.70 | 1.0 | 7/1.04 | 1.3 | 9.0*24.5 | 11.0*29.5 | 790 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound. Sheathed with PVC compound.
2.Core colors: red, yellow and blue(yellow in centre) Sheath colors: grey or white.
300/300V PVC Insulated Parallel Flexible Cords to BS 6500
Reference No 2812X RVB
Twin Core
| Size of conductor | Nominal thickness of insulation mm |
Mean overall dimensions | Approx. net weight per km kg |
||
| Nominal cross-sectional area mm2 |
Number and diameter of wires no/mm |
Lower Limit mm |
Upper Limit Mm |
||
| 0.5 | 28/0.15 | 0.8 | 2.5×5.0 | 3.0×6.0 | 24 |
| 0.75 | 42/0.15 | 0.8 | 2.7×5.4 | 3.2×6.4 | 29 |
Notes
1.Conductors of high conductivity copper wires insulated with PVC compound.
2.One core with a ridge for identification.
300/500V and 450/750V PVC Insulated Flexible Cords to BS 6500/6004
Reference No 2491X
Single Core
| Size of conductor | Nominal thickness of insulation mm |
Mean overall diameter Upper limit mm |
Approx. net weight per km kg |
|
| Nominal cross-sectional area mm2 |
Number and diameter of wire no/mm |
|||
| 0.5 | 16/0.20 | 0.6 | 2.6 | 10 |
| 0.75 | 24/0.20 | 0.6 | 2.8 | 13 |
| 1.0 | 32/0.20 | 0.6 | 3.0 | 16 |
| 1.5* | 30/0.25 | 0.7 | 3.5 | 20 |
| 2.5* | 50/0.25 | 0.8 | 4.2 | 32 |
| 4.0* | 56/0.30 | 0.8 | 4.8 | 49 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.
2.Standard colors: red.black, white, blue,brown, grey and green/yellow.
*:Rating Voltage 450/750V
300/500V PVC Insulated Twisted Twin Flexible Cords to BS 6500
Reference No 2492X
Twisted Twin
| Size of conductor | Nominal thickness of insulation mm |
Mean overall diameter of each core Upper limit mm |
Approx. net weight per km kg |
|
| Nominal cross-sectional area mm2 |
Number and diameter of wires mm |
|||
| 0.5 | 16/0.20 | 0.6 | 4.6 | 20 |
| 0.75 | 24/0.20 | 0.6 | 5.0 | 26 |
| 1.0 | 32/0.20 | 0.6 | 5.4 | 33 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.
2.Two cores twisted together.
300/300V PVC Insulated PVC Sheathed Parallel Twin Light Flexible Cords to BS 6500
Reference No 2192Y
Parallel Twin
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Mean overall dimensions | Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires No./mm |
Upper Limit mm |
Upper Limit mm |
|||
| 0.5 | 16/0.20 | 0.5 | 0.6 | 3.0×4.8 | 3.6×6.0 | 27 |
| 0.75 | 24/0.20 | 0.5 | 0.6 | 3.2×5.2 | 3.9×6.4 | 34 |
Notes
1.Conductors of high conductivity copper wires insulated with PVC compound.sheathed with PVC compound.
2.Core colors: blue and brown . Sheathed colors: grey,white or black.
300/300V PVC/PVC Sheathed Circular Light Flexible Cords to BS 6500
Reference No 2182Y
Twin Core
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Mean overall dimensions | Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires No./mm |
Upper Limit mm |
Upper Limit mm |
|||
| 0.5 | 16/0.20 | 0.5 | 0.6 | 4.8 | 6.0 | 36 |
| 0.75 | 24/0.20 | 0.5 | 0.6 | 5.2 | 6.4 | 45 |
Notes
1.Conductors of high conductivity copper wires insulated with PVC compound. sheathed with PVC compound.
2.Core colors: blue and brown. Sheathed colors: grey,white or black.
Reference No 2183Y
Three Core
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of Sheath mm |
Mean overall dimensions | Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires no/mm |
Lower Limit mm |
Upper Limit mm |
|||
| 0.5 | 16/0.2 | 0.5 | 0.6 | 5.0 | 6.2 | 44 |
| 0.75 | 24/0.2 | 0.5 | 0.6 | 5.4 | 6.8 | 55 |
Notes
1.Conductor of high conductivity copper wires insulated with PVC compound. sheathed with PVC compound.
2.Core colors: green/ yellow blue and brown. Sheathed colors: grey,white or black.
300/500V PVC/PVC Sheathed Parallel Twin Flexible Cords to BS 6500
Reference No 3192Y
Parallel Twin
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of Sheath mm |
Mean overall dimensions | Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires No./mm |
Lower Limit mm |
Upper Limit mm |
|||
| 0.75 | 24/0.20 | 0.6 | 0.8 | 3.8*6.0 | 5.2*7.6 | 47 |
Notes
1.Conductors of high conductivity copper wires insulated with PVC compound.sheathed with PVC compound.
2.Core colors: blue and brown. Sheathed colors: grey white or black.
300/500VPVC/PVC Sheathed Circular Flexible Cords to BS 6500
Reference No 3182Y
Twin Core
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Mean overall dimensions | Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires no/mm |
Lower Limit mm |
Upper Limit mm |
|||
| 0.75 | 24/0.20 | 0.6 | 0.8 | 6.0 | 7.6 | 63 |
| 1.0 | 32/0.20 | 0.6 | 0.8 | 6.4 | 8.0 | 73 |
| 1.25 | 40/0.20 | 0.7 | 0.8 | 7.0 | 8.6 | 84 |
| 1.5 | 30/0.25 | 0.7 | 0.8 | 7.4 | 9.0 | 95 |
| 2.5 | 50/0.25 | 0.8 | 1.0 | 8.9 | 11.0 | 145 |
Notes
1.Conductors of high conductivity copper wires insulated with PVC compound.sheathed with PVC compound.
2.Core colors: blue and brown. Sheathed colors:grey. white or black.
300/500V PVC/PVC Sheathed Circular Flexible Cords to BS 6500
Reference No 3183Y
Three Core
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Mean overall dimensions | Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires no/mm |
Lower Limit mm |
Upper Limit mm |
|||
| 0.75 | 24/0.20 | 0.6 | 0.8 | 6.4 | 8.0 | 74 |
| 1.0 | 32/0.20 | 0.6 | 0.8 | 6.8 | 8.4 | 86 |
| 1.25 | 40/0.20 | 0.7 | 0.9 | 7.6 | 9.4 | 104 |
| 1.5 | 30/0.25 | 0.7 | 0.9 | 8.0 | 9.8 | 120 |
| 2.5 | 50/0.25 | 0.8 | 1.1 | 9.6 | 12.0 | 180 |
Notes
1.Conductors of high conductivity copper wires insulated with PVC compound.sheathed with PVC compound.
2.Core colors green/yellow, blue and brown. Sheathed colors: grey.white or black.
300/500V PVC/PVC Sheathed Circular Flexible Cords to BS 6500
Reference No 3184Y
Four Core
| Size of conductor | Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Mean overall dimensions | Approx. net weight per km kg |
||
| Nominal cross- sectional area mm2 |
Number and diameter of wires no/mm |
Lower limit mm |
Upper limit mm |
|||
| 0.75 | 24/0.20 | 0.6 | 0.8 | 6.8 | 8.6 | 78 |
| 1.0 | 32/0.20 | 0.6 | 0.9 | 7.6 | 9.4 | 110 |
| 1. 5 | 30/0.25 | 0.7 | 1.0 | 9.0 | 11.0 | 150 |
| 2.5 | 50/0.25 | 0.8 | 1.1 | 10.5 | 13.0 | 220 |
Notes
1.Conductors of high conductivity copper wires insulated with PVC compound.sheathed with PVC compound.
2.Core colors green/yellow, black, blue and brown. Sheathed colors: grey. white or black.
Class No 802
Twin Core
| Size of conductor | Nominal thickness of insulation mm |
Nominal overall dimension mm |
Approx. net weight per km kg |
|
| Nominal cross-sectional area mm2 |
Number and diameter of wires no/mm |
|||
| 0. 5 | 16/0.20 | 0.5 | 1.95*3.90 | 15 |
| 0.75 | 24/0.20 | 0.5 | 2.15*4.30 | 21 |
Notes:
Conductors of high conductivity copper wires,Two conductors laid side by side,Both insulated with PVC compound formation,one core with a ridge for identification.
Class No 812
Twisted Twin
| Size of conductor | Nominal thickness of insulation mm |
Nominal overall diameter of each core mm |
Approx. net weight per km kg |
|
| Nominal cross-sectional area mm2 |
Number and diameter of wires mm |
|||
| 0. 5 | 16/0.20 | 0.5 | 1.95 | 16 |
| 0.75 | 24/0.20 | 0.5 | 2.15 | 22 |
Notes:
Conductors of high conductivity copper wires, insulated with PVC compound, two cores twisted together.
We are China BS6004 Standard 450/750V BV Single-Core PVC Insulated Non-Sheathed Wire Cables manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular BV Electric Wire Products
BV BVV Electrical PVC Insulated Copper Building Construction Cables Wire 2.5mm
High Quality Copper Material PVC Insulated BV Power Cable Solid Single Core Electrical Wire 2.5 mm
Cable GB5023.5-1997/GB/T5023.5-2008 PVC Cable/Cable PVC
BV, Low Voltage Electric Wires Cable Indoor and Outdoor Use Building Wire
Flexible Copper Rvv Cable 5 Core 4mm Electrical Wire
Electric Cable CCA Conductor BV Wire
Popular jytopcable Products
0.6/1kv Copper Conductor PVC Insulated PVC Jacket Electric Cable
Yavv Nayy Aluminum Cable PVC Insulated Cables with Aluminium Conductor
450V PVC Coated Electric Wire H07V-U
4 Core Copper XLPE Insulated Armoured Underground Cable
Flat TPS 3c Electric Cables for PVC Insulated and Sheath Wire to Australia Standard AS/NZS 5000.2
Medium Voltage Mv Tr-XLPE Insulated Urd Steel Wire Armoured Underground Cable
Popular PVC Insulated Wire Products
Three Core PVC Insulated Price Flat Electric Wire Solid Copper Wire BVVB
450/750V 2 Cores Twin and Earth Cable 6242Y Cable Flat PVC Cable
300/500V 450/750V Copper Core PVC Insulated Building Electrical Wire
450/750V Multi-Core Solid/Stranded Cooper Conductor Flat Twin & Earth Cable
Rvv Cable Twisted Size 2X0.75mm2 Black Electrical Wire Power Cable Wire
PVC Insulated Wire with Rated Voltage up to 450/750V
Popular Single Core PVC Wire Products
Single Core Flexible Copper Wire Double PVC Insulation Power Cable
Copper Cable 1.5 mm 2.5mm 4mm 6mm 10mm House Wiring Electrical Cable Copper Single Core PVC Wire
Tags: BV Electric Wire, jytopcable, PVC Insulated Wire, Single Core PVC Wire