Easy Installation High Voltage 33kv Cold Shrink Indoor Terminal
Easy Installation High Voltage 33kv Cold Shrink Indoor Terminal image
Get Latest Price Request a quote
- Overview
- Product Description
- Detailed Photos
- Product Parameters
- Recommended Product
- Company Profile
- Packaging & Shipping
- FAQ
Basic Info.
Packaging & Delivery
Product Description
Cold-shrinkable cable termination kit & straight joint kit
0.6/1KV-Cold Shrinkable Cable Accessories
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
0.6/1kV 3-cores Cold Shrinkable Termination Kits | VLZ-1/3.0 | 10~16 | 0.6/1kV 3-cores Cold Shrinkable Joint | VLJ-1/3.0 | 10~16 |
VLZ-1/3.1 | 25~50 | VLJ-1/3.1 | 25~50 | ||
VLZ-1/3.2 | 70~120 | VLJ-1/3.2 | 70~120 | ||
VLZ-1/3.3 | 150~240 | VLJ-1/3.3 | 150~240 | ||
VLZ-1/3.4 | 300~400 | VLJ-1/3.4 | 300~400 | ||
0.6/1kV 4-cores Cold Shrinkable Termination Kits | VLZ-1/4.0 | 10~16 | 0.6/1kV 4-cores Cold Shrinkable Joint | VLJ-1/4.0 | 10~16 |
VLZ-1/4.1 | 25~50 | VLJ-1/4.1 | 25~50 | ||
VLZ-1/4.2 | 70~120 | VLJ-1/4.2 | 70~120 | ||
VLZ-1/4.3 | 150~240 | VLJ-1/4.3 | 150~240 | ||
VLZ-1/4.4 | 300~400 | VLJ-1/4.4 | 300~400 | ||
0.6/1kV 5-cores Cold Shrinkable Termination Kits | VLZ-1/5.0 | 10~16 | 0.6/1kV 5-cores Cold Shrinkable Joint | VLJ-1/5.0 | 10~16 |
VLZ-1/5.1 | 25~50 | VLJ-1/5.1 | 25~50 | ||
VLZ-1/5.2 | 70~120 | VLJ-1/5.2 | 70~120 | ||
VLZ-1/5.3 | 150~240 | VLJ-1/5.3 | 150~240 | ||
VLZ-1/5.4 | 300~400 | VLJ-1/5.4 | 300~400 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage Test | 4kV/1min,No breakdown no flashover | Pass,meet the requirements | |||
Power Frequency Voltage Test | 2.4kV/4 hours,No breakdown no flashover | Pass,meet the requirements |
8.7/15KV-Cold Shrinkable Cable Accessories
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
8.7/15kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-10/1.1 | 25~50 |
VLN-10/3.2 | 70~120 | VLN-10/1.2 | 70~120 | ||
VLN-10/3.3 | 150~240 | VLN-10/1.3 | 150~240 | ||
VLN-10/3.4 | 300~400 | VLN-10/1.4 | 300~400 | ||
VLN-10/3.5 | 500~630 | VLN-10/1.5 | 500~630 | ||
8.7/15kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-10/1.1 | 25~50 |
VLW-10/3.2 | 70~120 | VLW-10/1.2 | 70~120 | ||
VLW-10/3.3 | 150~240 | VLW-10/1.3 | 150~240 | ||
VLW-10/3.4 | 300~400 | VLW-10/1.4 | 300~400 | ||
VLW-10/3.5 | 500~630 | VLW-10/1.5 | 500~630 | ||
8.7/15kV 3-cores Cold Shrinkable Joint | VLJ-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Joint | VLJ-10/1.1 | 25~50 |
VLJ-10/3.2 | 70~120 | VLJ-10/1.2 | 70~120 | ||
VLJ-10/3.3 | 150~240 | VLJ-10/1.3 | 150~240 | ||
VLJ-10/3.4 | 300~400 | VLJ-10/1.4 | 300~400 | ||
VLJ-10/3.5 | 500~630 | VLJ-10/1.5 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 39kV 5min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 15kV, Discharge volume≤10pc | Pass | |||
Impulse Voltage Test | Under 95kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 23kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC) | Under 15kV, Discharge volume≤10pc | Pass | |||
Constant load Cycle Test | The conductor applied voltage 23kV, and heated to (95-100ºC). In which the temperature stability 2h, cooling 3h, a total of 60 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC,and at ambient temperature) | Under 15kV, Discharge volume≤10pc | Pass | |||
Thermal Stability Test | Under 23 KA, Short circuit 2 times, No visible damage | Pass | |||
Dynamic Stability Test | Under 81 KA, Short circuit 1 time, No visible damage | Pass | |||
Impulse Voltage Test | 95kV, ±10 times | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 23kV, 15min | Not Flashover and Not Breakdown | |||
Tide Temperature Test | 11kV, 300h | Not Flashover,Not Breakdown and No Overcurrent Release | |||
Salt Spray Test | 11kV, 1000h | Not Flashover,Not Breakdown and No Overcurrent Release |
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
18/20kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-10/1.1 | 35~70 |
VLN-20/3.2 | 95~185 | VLN-10/1.2 | 95~185 | ||
VLN-20/3.3 | 240~400 | VLN-10/1.3 | 240~400 | ||
VLN-20/3.4 | 500~630 | VLN-10/1.4 | 500~630 | ||
18/20kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-10/1.1 | 35~70 |
VLW-20/3.2 | 95~185 | VLW-10/1.2 | 95~185 | ||
VLW-20/3.3 | 240~400 | VLW-10/1.3 | 240~400 | ||
VLW-20/3.4 | 500~630 | VLW-10/1.4 | 500~630 | ||
18/20kV 3-cores Cold Shrinkable Joint | VLJ-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Joint | VLJ-10/1.1 | 35~70 |
VLJ-20/3.2 | 95~185 | VLJ-10/1.2 | 95~185 | ||
VLJ-20/3.3 | 240~400 | VLJ-10/1.3 | 240~400 | ||
VLJ-20/3.4 | 500~630 | VLJ-10/1.4 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 54kV 5min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 20kV, Discharge volume≤10pc | Pass | |||
Impulse Voltage Test | Under 125kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 35kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC) | Under 20kV, Discharge volume≤10pc | Pass | |||
Constant load Cycle Test | The conductor applied voltage 35kV, and heated to (95-100ºC). In which the temperature stability 2h, cooling 3h, a total of 60 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC,and at ambient temperature) | Under 20kV, Discharge volume≤10pc | Pass | |||
Thermal Stability Test | Under 23 KA, Short circuit 2 times, No visible damage | Pass | |||
Dynamic Stability Test | Under 81 KA, Short circuit 1 time, No visible damage | Pass | |||
Impulse Voltage Test | 125kV, ±10 times | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 30kV, 15min | Not Flashover and Not Breakdown | |||
Tide Temperature Test | 15kV, 300h | Not Flashover,Not Breakdown and No Overcurrent Release | |||
Salt Spray Test | 15kV, 1000h | Not Flashover,Not Breakdown and No Overcurrent Release |
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
26/35kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-35/1.1 | 35~70 |
VLN-35/3.2 | 120~185 | VLN-35/1.2 | 95~185 | ||
VLN-35/3.3 | 240~400 | VLN-35/1.3 | 240~400 | ||
VLN-35/3.4 | 500~630 | VLN-35/1.4 | 500~630 | ||
26/35kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-35/1.1 | 35~70 |
VLW-35/3.2 | 120~185 | VLW-35/1.2 | 95~185 | ||
VLW-35/3.3 | 240~400 | VLW-35/1.3 | 240~400 | ||
VLW-35/3.4 | 500~630 | VLW-35/1.4 | 500~630 | ||
26/35kV 3-cores Cold Shrinkable Joint | VLJ-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Joint | VLJ-35/1.1 | 35~70 |
VLJ-35/3.2 | 120~185 | VLJ-35/1.2 | 95~185 | ||
VLJ-35/3.3 | 240~400 | VLJ-35/1.3 | 240~400 | ||
VLJ-35/3.4 | 500~630 | VLJ-35/1.4 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 105kV 1min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 39kV, Discharge volume≤10pc | Pass | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 23kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Impulse Voltage Test | Under 250kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
DC Voltage | 156kV, 15min | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 104kV, 4h | Not Flashover and Not Breakdown |
View more products,you can click photos…
66~500kV High Voltage Cable Accessories 1~35kV Heat Shrink Cable Accessories Grounding Box
Customized Silicone Rubber Protector Heat Shrinkable Tubing Explosion Proof Box
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Easy Installation High Voltage 33kv Cold Shrink Indoor Terminal manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Cold Shrink Joint Kit Products
35kv High Voltage Three-Core Cold Shrinkable Intermediate Connector Cable Joint Kits
3 Core High Voltage Cable Straight Joint Intermediate Joint
High Standard Cable Accessory Termination Kits Cold Shrink Straight Joint Kits
Outdoor 10kv 3 Cores Cold Shrinkable Cable Straight Joint
35kv Cable Accessories 3 Core Cold Shrinkable Cable Termination
Cold Insulation Cable Accessories Cold Shrink Cable Joint Kit
Popular Easy Installation High Voltage 33kv Cold Shrink Indoor Terminal Products
Popular Indoor Termination Kit Products
Outdoor Cold Shrinkable Termination Kits Indoor Cable Cold Shrink Joint Kit
1low Voltage 4-Core Cold Shrinkable Cable Accessories Termination Kit
Factory Direct Supply 1~35kv Cold Shrinkable Termination Kits
35kv Single Core Cold Shrinkable Joint Cable Termination Kits
Cable Accessories Supplier High Voltage Cold Shrinkable Outdoor Termination Kit
10kv 3 Cores Cold Shrink Cable Connector Set Straight Joint Kit
Popular jiuweielectric Products
High Standard 35kv Cable Fusion Repair Connector Excellent Performance Cable Fusing Head
High Rate Silicone Rubber Cold Shrinkable Insulation Tube
Low Voltage 5-Ways Heat Shrink Breakout Boot
1kv Heat Shrinkable Cable Termination Kit Heat Shrinkable Indoor Straight Joint Kit
Silicone Rubber High Rate Cold Shrinkable Tube
Tags: Cold Shrink Joint Kit, Easy Installation High Voltage 33kv Cold Shrink Indoor Terminal, Indoor Termination Kit, jiuweielectric