Electric Wire Bare Aluminum Alloy AAAC Conductor
Electric Wire Bare Aluminum Alloy AAAC Conductor image
Get Latest Price Request a quote
Quick Details
Product Details
APPLICATION:
Used as bare overhead conductor for primary and secondary distribution. Designed for utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics.
- AAAC conductors are extensively used for overhead distribution and transmission lines adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction.
- The aluminum alloy conductors are used in replace of single-layer ACSR conductors to reduce power loss in overhead distribution and transmission lines,when replacing the aluminum conductor steel reinforced , the AAAC can save 5-8% of the construction cost.
3. AAAC referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to replace the conventional ACSR.
CONSTRUCTION:
AAAC is concentric-lay- stranded, similar in
construction and appearance with1350 grade aluminum conductors. They were developed to the need of economical conductor for overhead applications requiring higher strength than that of 1350 grade aluminum conductors, but without a steel core.
STANDARDS:
ASTM B399, BS EN50183 ,BS 3242,DIN 48201,IEC 61089
| All Aluminium Alloy Conductors(AAAC) ASTM B 399 | |||||||
| AREA | Stranding | Wire Dia. | Approx. overall diameter |
Weight | Nominal Breaking Load |
Nom. DC resistance at 20 Deg. |
|
| Nominal | Actual | ||||||
| AWGorMCM | (mm2) | (mm) | (mm) | (kg/km) | (kN) | (ohm/km) | |
| 6 | 13.3 | 7 | 1.554 | 4.67 | 37 | 4.22 | 2.5199 |
| 4 | 21.15 | 7 | 1.961 | 5.89 | 58 | 6.71 | 1.5824 |
| 2 | 33.63 | 7 | 2.474 | 7.42 | 93 | 10.68 | 0.9942 |
| 1/0 | 53.48 | 7 | 3.119 | 9.36 | 148 | 16.97 | 0.6256 |
| 2/0 | 67.42 | 7 | 3.503 | 10.51 | 186 | 20.52 | 0.4959 |
| 3/0 | 85.03 | 7 | 3.932 | 11.8 | 234 | 25.86 | 0.3936 |
| 4/0 | 107.23 | 7 | 4.417 | 13.26 | 296 | 32.63 | 0.3119 |
| 250 | 126.66 | 19 | 2.913 | 14.57 | 349 | 38.93 | 0.2642 |
| 300 | 152.1 | 19 | 3.193 | 15.97 | 419 | 46.77 | 0.2199 |
| 350 | 177.35 | 19 | 3.447 | 17.24 | 489 | 52.25 | 0.1887 |
| 400 | 202.71 | 19 | 3.686 | 18.43 | 559 | 59.74 | 0.1650 |
| 450 | 228 | 19 | 3.909 | 19.55 | 629 | 67.19 | 0.1467 |
| 500 | 253.35 | 19 | 4.12 | 20.6 | 698 | 74.64 | 0.1321 |
| 550 | 278.6 | 37 | 3.096 | 21.67 | 768 | 83.80 | 0.1202 |
| 600 | 303.8 | 37 | 3.233 | 22.63 | 838 | 91.38 | 0.1102 |
| 650 | 329.25 | 37 | 3.366 | 23.56 | 908 | 97.94 | 0.1016 |
| 700 | 354.55 | 37 | 3.493 | 24.45 | 978 | 102.20 | 0.0944 |
| 750 | 380.2 | 37 | 3.617 | 25.32 | 1049 | 109.60 | 0.0880 |
| 800 | 405.15 | 37 | 3.734 | 26.14 | 1117 | 116.80 | 0.0826 |
| 900 | 456.16 | 37 | 3.962 | 27.73 | 1258 | 131.50 | 0.0733 |
| 1000 | 506.71 | 37 | 4.176 | 29.23 | 1399 | 146.10 | 0.0660 |
| AAAC (Characteristics of A2 Conductors) IEC 61089 | |||||||
| Code number |
Area | Number of wires |
Diameter | Linear mass |
Rated strength |
D.C resistance at 20 Deg. |
|
| Wire | Cond | ||||||
| mm2 | mm | mm | kg/km | kN | Ohm/km | ||
| 16 | 18.4 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 1.7896 |
| 25 | 28.8 | 7 | 2.29 | 6.86 | 78.7 | 8.49 | 1.1453 |
| 40 | 46 | 7 | 2.89 | 8.68 | 125.9 | 13.58 | 0.7158 |
| 63 | 72.5 | 7 | 3.63 | 10.9 | 198.3 | 21.39 | 0.4545 |
| 100 | 115 | 19 | 2.7 | 13.9 | 316.3 | 33.95 | 0.2877 |
| 125 | 144 | 19 | 3.1 | 15.5 | 395.4 | 42.44 | 0.2302 |
| 160 | 184 | 19 | 3.51 | 17.6 | 506.1 | 54.32 | 0.1798 |
| 200 | 230 | 19 | 3.93 | 19.6 | 632.7 | 67.91 | 0.1439 |
| 250 | 288 | 19 | 4.39 | 22 | 790.8 | 84.88 | 0.1151 |
| 315 | 363 | 37 | 3.53 | 24.7 | 998.9 | 106.95 | 0.0916 |
| 400 | 460 | 37 | 3.98 | 27.9 | 1268.4 | 135.81 | 0.0721 |
| 450 | 518 | 37 | 4.22 | 29.6 | 1426.9 | 152.79 | 0.0641 |
| 500 | 575 | 37 | 4.45 | 31.2 | 1585.5 | 169.76 | 0.0577 |
| 560 | 645 | 61 | 3.67 | 33 | 1778.4 | 190.14 | 0.0516 |
| 630 | 725 | 61 | 3.89 | 35 | 2000.7 | 213.9 | 0.0458 |
| 710 | 817 | 61 | 4.13 | 37.2 | 2254.8 | 241.07 | 0.0407 |
| 800 | 921 | 61 | 4.38 | 39.5 | 2540.6 | 271.62 | 0.0361 |
| 900 | 1036 | 91 | 3.81 | 41.8 | 2861.1 | 305.68 | 0.0321 |
| 1000 | 1151 | 91 | 4.01 | 44.1 | 3179 | 339.53 | 0.0289 |
| 1120 | 1289 | 91 | 4.25 | 46.7 | 3560.5 | 380.27 | 0.0258 |
| 1250 | 1439 | 91 | 4.49 | 49.4 | 3973.7 | 424.41 | 0.0231 |
| AAAC (Characteristics of A3 Conductors) IEC 61089 | |||||||
| Code number |
Area | Number of wires |
Diameter | Linear mass |
Rated strength |
D.C resistance at 20 Deg. |
|
| Wire | Cond | ||||||
| mm2 | mm | mm | kg/km | kN | Ohm/km | ||
| 16 | 18.6 | 7 | 1.84 | 5.52 | 50.8 | 6.04 | 1.7896 |
| 25 | 29 | 7 | 2.3 | 6.9 | 79.5 | 9.44 | 1.1453 |
| 40 | 46.5 | 7 | 2.91 | 8.72 | 127.1 | 15.1 | 0.7158 |
| 63 | 73.2 | 7 | 3.65 | 10.9 | 200.2 | 23.06 | 0.4545 |
| 100 | 116 | 19 | 2.79 | 14 | 319.3 | 37.76 | 0.2877 |
| 125 | 145 | 19 | 3.12 | 15.6 | 399.2 | 47.2 | 0.2302 |
| 160 | 186 | 19 | 3.53 | 17.6 | 511 | 58.56 | 0.1798 |
| 200 | 232 | 19 | 3.95 | 19.7 | 638.7 | 73.2 | 0.1439 |
| 250 | 290 | 19 | 4.41 | 22.1 | 798.4 | 91.5 | 0.1151 |
| 315 | 366 | 37 | 3.55 | 24.8 | 1008.4 | 115.29 | 0.0916 |
| 400 | 465 | 37 | 4 | 28 | 1280.5 | 146.4 | 0.0721 |
| 450 | 523 | 37 | 4.24 | 29.7 | 1440.5 | 164.7 | 0.0641 |
| 500 | 581 | 37 | 4.47 | 31.3 | 1600.6 | 183 | 0.0577 |
| 560 | 651 | 61 | 3.69 | 33.2 | 1795.3 | 204.96 | 0.0516 |
| 630 | 732 | 61 | 3.91 | 35.2 | 2019.8 | 230.58 | 0.0458 |
| 710 | 825 | 61 | 4.15 | 37.3 | 2276.2 | 259.86 | 0.0407 |
| 800 | 930 | 61 | 4.4 | 39.6 | 2564.8 | 292.8 | 0.0361 |
| 900 | 1046 | 91 | 3.83 | 42.1 | 2888.3 | 329.4 | 0.0321 |
| 1000 | 1162 | 91 | 4.03 | 44.4 | 3209.3 | 366 | 0.0289 |
| 1120 | 1301 | 91 | 4.27 | 46.9 | 3594.4 | 409.92 | 0.0258 |
| All Aluminlum Alloy Conductors(AAAC) BS EN 50183 | |||||||
| Code Name |
Area | No.of wires |
Diameter | Mass per unit length |
Rated strength |
DC resistance at 20 Deg. |
|
| Wire | Cond. | ||||||
| mm2 | mm | mm | kg/km | kN | Ω/km | ||
| BOX | 18.8 | 7 | 1.85 | 5.55 | 51.4 | 5.55 | 1.7480 |
| ACACLA | 23.8 | 7 | 2.08 | 6.24 | 64.9 | 7.02 | 1.3828 |
| ALMOND | 30.1 | 7 | 2.34 | 7.02 | 82.2 | 8.88 | 1.0926 |
| CEDAR | 35.5 | 7 | 2.54 | 7.62 | 96.8 | 10.46 | 0.9273 |
| DEODAR | 42.2 | 7 | 2.77 | 8.31 | 115.2 | 12.44 | 0.7797 |
| FIR | 47.8 | 7 | 2.95 | 8.85 | 130.6 | 14.11 | 0.6875 |
| HAZEL | 59.9 | 7 | 3.3 | 9.90 | 163.4 | 17.66 | 0.5494 |
| PLNE | 71.6 | 7 | 3.61 | 10.8 | 195.6 | 21.14 | 0.4591 |
| HOLLY | 84.1 | 7 | 3.91 | 11.7 | 229.5 | 24.79 | 0.3913 |
| WILLOW | 89.7 | 7 | 4.04 | 12.1 | 245.0 | 26.47 | 0.3665 |
| OAK | 118.9 | 7 | 4.65 | 14.0 | 324.5 | 35.07 | 0.2767 |
| MULBERRY | 150.9 | 19 | 3.18 | 15.9 | 414.3 | 44.52 | 0.2192 |
| ASH | 180.7 | 19 | 3.48 | 17.4 | 496.1 | 53.31 | 0.1830 |
| ELM | 211 | 19 | 3.76 | 18.8 | 579.2 | 62.24 | 0.1568 |
| POPLAR | 239.4 | 37 | 2.87 | 20.1 | 659.4 | 70.61 | 0.1387 |
| SYCAMORE | 303.2 | 37 | 3.23 | 22.6 | 835.2 | 89.40 | 0.1095 |
| UPAS | 362.1 | 37 | 3.53 | 24.7 | 997.5 | 106.82 | 0.0917 |
| YEW | 479 | 37 | 4.06 | 28.4 | 1319.6 | 141.31 | 0.0693 |
| TOTARA | 498.1 | 37 | 4.14 | 29.0 | 1372.1 | 146.93 | 0.0666 |
| RUBUS | 586.9 | 61 | 3.5 | 31.5 | 1622.0 | 173.13 | 0.0567 |
| SORBUS | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
| ARAUCARIA | 821.1 | 61 | 4.14 | 37.3 | 2269.4 | 242.24 | 0.0406 |
| REDWOOD | 996.2 | 61 | 4.56 | 41.0 | 2753.2 | 293.88 | 0.0334 |
| All Aluminium Alloy Conductors (AAAC) BS EN 50183 | |||||||
| Designation | Area | Stranding wire Dia. |
Overall Diameter |
Nominal Breaking Load |
Nominal DC Resistance at 20ºC |
Standard Weight |
|
| mm2 | No | Φ | mm | kN | Ohm/km | kg/km | |
| ASTER 22 | 22 | 7 | 2 | 6 | 7.15 | 1.4989 | 60 |
| ASTER 34.4 | 34.4 | 7 | 2.5 | 7.5 | 11.17 | 0.9593 | 93.8 |
| ASTER 54.6 | 54.6 | 7 | 3.15 | 9.45 | 17.73 | 0.6042 | 148.9 |
| ASTER 75.5 | 75.5 | 19 | 2.25 | 11.3 | 24.55 | 0.4388 | 207.4 |
| ASTER 117 | 117 | 19 | 2.8 | 14 | 38.02 | 0.2833 | 321.2 |
| ASTER 148 | 148.1 | 19 | 3.15 | 15.8 | 48.12 | 0.2239 | 406.5 |
| ASTER 181.6 | 181.6 | 37 | 2.5 | 17.5 | 59.03 | 0.1831 | 500.3 |
| ASTER 228 | 227.8 | 37 | 2.8 | 19.6 | 74.04 | 0.146 | 627.6 |
| ASTER 288 | 288.3 | 37 | 3.15 | 22.1 | 93.71 | 0.1154 | 794.3 |
| ASTER 366 | 366.2 | 37 | 3.55 | 24.9 | 115.36 | 0.0908 | 1008.9 |
| ASTER 570 | 570.2 | 61 | 3.45 | 31.1 | 185.33 | 0.0585 | 1576 |
| ASTER 851 | 850.7 | 91 | 3.45 | 38 | 276.47 | 0.0394 | 2360.7 |
| ASTER 1144 | 1143.5 | 91 | 4 | 44 | 360.22 | 0.0293 | 3173.4 |
| ASTER 1600 | 1595.9 | 127 | 4 | 52 | 502.72 | 0.021 | 4427.5 |
4.Packing
Packing in wooden drums,steel wooden drums or as customer’s requirement.
5.Customer Visit
We have a professional sales team with each of them has engaged in this job for 3-10 years, so that we can provide the comprehensive and professional technology for you. With the perfect quality and after sales service, till now we have exported to more than 80 countries, welcome to visit us and establish win-win establish relationship!
6.Production process:
AAAC conductor producing process is drawing stranding and cabling,our factory possess 2 subsidiaries,Zhulin factory is professional bare conductor workshop with 20 production line.
7.Certificate
As first rank of the cable supplier in China, we have obtained CE, ISO9001, ISO14001, OHSAS certificates, passed the SGS and BV test, and our brand "RMJT" be given China famous brand.
8.About us:
People’s Cable Group Co., Ltd. was founded in 2007, located in Zhengzhou Gongyi economic development zone. Our company has 2 factories (Zhitian factory and Zhulin factory), occupies total area of more than 300,000 square meters, with building area 230,000 square meters.
9.Contacts
Vivian Wong
T: 86-371-55632835 | M: 86-17719852022
We are China Electric Wire Bare Aluminum Alloy AAAC Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAAC Products
High Quality Overhead Bare Aluminum Conductors ACSR AAC AAAC Acss Power Transmission Conductor
ASTM Standard Overhead AAAC Conductor for Transmission Aluminium Alloy Conductor
AAAC, ACSR, AAC Aluminum Stranded Conductor ACSR Cable
ASTM Standard Almelec Cable AAAC
Hot Selling Bare Electric Wire AAAC Aluminum Alloy Overhead Conductor
ASTM Standard Overhead Bare Conductor AAAC Conductor
Popular AAAC Conductor Products
50mm 70mm 95mm 240mm Aluminium Alloy Conductor AAAC Conductor
Aluminum Alloy AAAC Bare Stranded Conductor Cable Wire
Transmission Line Use All Aluminium Alloy Conductor for Overhead Use
High-Strength Aluminum Alloy Conductor (AAAC)
All Aluminium Conductor AAC/AAAC/ACSR Cable
AAAC Conductor Salfur Anaheim Azusa 2/0 Power Transmission
Popular Aluminium Cable Products
11kv Aluminium Armoured Cable with High Quality
U-1000 Arvfv Aluminium Conductor XLPE Insulated Low Voltage Cable
1/2/3/4/ 3+1/4+1core Aluminium Cable 95mm2 0.6/1kv Rated
Online Shopping 1kv / 35 Kv Copper Conductor XLPE Insulated Amoured Electric Power Cable
0.6/1kv NFC/ASTM/BS/IEC Standard Electric Cable ABC Cable
Aluminum Conductor Steel Reinforced Cable Conductor ACSR
Popular renmincable Products
4mm Copper Wire Bvr Housing Electrical Wire
H07V-K H07V-U H07V-R H05V-R H05V-K Copper PVC Wire 1.5mm2 2.5mm2