FN18 series Indoor High Voltage Load Break Switch Nalf Air Insulation Switch Breakers Fuses
FN18 is a general purpose, three-pole, load break switch that offers switchgear owners and assemblers the advantages of an advanced interrupting technology and proven, dependable performance in a compact design. The switch is available to switchgear assemblers as a building block for metal-enclosed and pad-mounted switchgear applications in ratings from 12-40.5 kV.
The standard FN18 switch includes a heavy-duty steel frame with stand-off insulators, a unique puffer-type arc extinguishing system, an operating mechanism and current-carrying components, including blade-type interrupters with cast hinges and jaw connectors.
Optional accessories and features include a variety of operating handles, a motor operator, auxiliary switches, a shunt trip device, fuse bases, mechanical fuse tripping, grounding switches, mechanical door interlocking and key interlocking.
FN18 series indoor high-voltage load switch has the advantages of easy design, operation, compact structure, small volume, full function, light weight, fast breaking and closing speed and high reliability. It is suitable for AC 50Hz, rated voltage 12kV, 24kV, rated current 630A and three-phase distribution system, especially for city network construction and renovation projects, high-rise buildings, ring network power supply of public facilities, and is an ideal product for box-type substation and transformer protection.
Technical parameter
| Rated voltage | Unit | 12kV | 17.5kV | 24kV | 36kV | 40.5kV | |||||||||||
| Rated current | A | 400 | 630 | 1250 | 400 | 630 | 1250 | 400 | 630 | 1250 | 630 | 800 | 1000 | 630 | 800 | 1000 | |
| Max. rated current | A | 400 | 630 | 1250 | 400 | 630 | 1250 | 400 | 630 | 1250 | 630 | 800 | 800 | 630 | 800 | 800 | |
| Short circuit making capacity | KA peak | 67 | 50 | 50 | 50 | 50 | |||||||||||
| Peak withstand current | KA peak | 82 | 82 | 82 | 66 | 66 | |||||||||||
| Short time current | 1 sec. | KA eff |
31.5 25 20 |
31.5 25 20 |
31.5 25 20 |
31.5 25 |
31.5 25 |
31.5 25 |
25 25 16 |
25 25 16 |
31.5 25 16 |
25 | 25 | 25 | 25 | 25 | 25 |
| 2 sec. | |||||||||||||||||
| 3 sec. | |||||||||||||||||
| Mainly active load breaking capacity 21 (test duty 1 and, IEC 60265-1( 265)) | A | 400 | 630 | 1250 | 400 | 630 | 1250 | 400 | 630 | 1250 | 630 | 800 | 630 | 800 | 630 | 800 | |
| Mainly capacitive breaking capacity (test duty 4, IEC 60265-1 (IEC 265)) | A | 150 | 45 | 80 | 50 | 50 | |||||||||||
| Mainly inductive breaking capacity cosφ=0.15 | A | 16 | 16 | 16 | 16 | 16 | |||||||||||
| Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11) | A | 1600 | 1600 | 1600 | 1600 | 900 | 900 | 300 | 300 | 300 | 300 | 300 | 300 | ||||
|
Power frequency withstand voltage 50 Hz 1 min. -to earth and between poles -across isolating distance |
kV |
42 45 |
45 60 |
55 70 |
80 88 |
95 120 |
|||||||||||
|
Impulse withstand voltage 1.2/50 μs – to earth and between poles – across isolating distance |
kV |
75 85 |
95 110 |
125 145 |
170 195 |
190 220 |
|||||||||||
| Pole distance | mm | 150, 170, 210 | 170, 210 | 170, 235, 275 | 360 | 360 | |||||||||||
|
Max. operating torque at: -closing K/A mech. -opening K/A mech. |
Nm | 115-120 Nm K-mech.120 Nm/A-mech. 3Nm |
80-100 Nm K-mech.80-100 Nm |
||||||||||||||
| Operating angle on the shaft | degree | 130 | 120 | ||||||||||||||
| Opening time | ms | 40-60 | 60 | ||||||||||||||
Structure
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Fn18 Series Indoor 630A H. V. Vacuum Load Break Switch Lbs and Fuse Combination manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Air Insulation Switch Breakers Products
Indoor High Voltage Load Break Switch Nalf Air Insulation Switch Breakers Fuses
Popular Fn18 Series Indoor 630A H. V. Vacuum Load Break Switch Lbs and Fuse Combination Products
Popular liyond Products
Vsg/C-12 Lateral Type Indoor Insulation Cylinder 12kv Vacuum Circuit Breaker Vcb
Dxn8d Series Indoor Type Hv Live Display Device
Indoor AC High Voltage 24kv Ek6 Isolator Earthing Switch for Kyn28 Metal-Clad Switchgear
Lyb251-Lyb254 Red Copper Patented Silicone Rubber 630A Contact Arm for Vacuum Circuit Breaker
10kv 11kv 12kv Vsg Types of Vacuum Circuit Breaker Vcb Panel
F10-12 8no 8nc Vacuum Circuit Breaker Auxiliary Switch
Popular Load Break Switch Products
33kv 630A Motorized Sf6 Lbs Pole Mounted Load Break Switch
Fln36-40.5kv 36kv 40.5kv 350mm 630A Sf6 Air Load Break Switch
L&R Air Breaker Isolator Switch Silicone Rubber Porcelain
11kv 33kv 63A Isolator Switch, DC Isolator Switch
630A High Voltage Rmu Lbs Load Break Switch
De-energized Cage-form Tap-changer (66kv and below) For Transformer
Tags: Air Insulation Switch Breakers, Fn18 Series Indoor 630A H. V. Vacuum Load Break Switch Lbs and Fuse Combination, liyond, Load Break Switch