Halogen-Free Fire Performance Cable Nhxh-J Fe180 E90 3X1, 5mm2 3X2.5
Halogen-Free Fire Performance Cable Nhxh-J Fe180 E90 3X1, 5mm2 3X2.5 image
Get Latest Price Request a quote
Quick Details
Product Details
Cable structure
- 1. Bare copper conductor, solid or stranded according to 0295 IEC 60228 cl. 1 or 2
- 2. Double core insulation of mica tape and cross-linked polymer compound
- 3. Cores color coded according to DIN VDE 0293-308, green-yellow earth core (from 3 cores above)
- 4. Cores stranded in layers and wrapped with glass-fibre tape as flame-protection
- For version (N)HXCH concentric conductor of copper tape and copper wires
- 5. Orange sheath of halogen-free polymer compound according to DIN VDE 0207 part 24, flame retardant
Technical data
- Halogen-free, flame-resistant cable according to DIN VDE 0266, orange
- Insulation integrity under the impact of flames 180 min according to IEC 60331, DIN VDE 0472 part 814
- Function integrity according to DIN VDE 4102 part 12 E90
- Temperature range flexing from -40°C to +70°C; max. permitted temperature at conductor +90°C
- Nominal voltage Uo/U 0,6/1 kV
- Test voltage a.c.4000 V
- Minimum bending radius approx. 15 x cable diameter
- Radiation resistance up to 200 x 106 cJ/kg (up to 200 Mrad)
Tests
- Flame-retardant to DIN VDE 0482 part 266-2/HD 405.3/BS 4066 PT3/EN 50266-2/IEC 60332-3
- Low corrosiveness of combustion gases to DIN VDE 0482 part 267/BS 6425 PT2/EN 50267-2-2/IEC 60754-2
- Halogen-free to DIN VDE 0482 part 267/BS 6425 PT1/EN 50267-2-1/IEC 60754-1
- Smoke density to DIN VDE 0482 part 268/HD 606/BS 7622 PT1,PT2/EN 50268-1,-2/IEC 61034-1,-2
- Insulation integrity under direct flame propagation according to DIN VDE 0472 part 814, IEC 60331
- Function integrity according to DIN VDE 4102 part 12 of electrical cable system for a period of 90 min.
Color codes of NHXCH
- 2-core cable: blue/brown
- 3-core cable: brown/black/grey
- 4-core cable: blue/brown/black/grey
- from 7 cores above, black cores with white numbering
Application
These flame-resistant cables are used for all locations where a special protection against fire and fire damage to human life and equipment is necessary such as in industry complexes, power stations, public buildings, hotels, airports, subways, theatres, hospitals etc. These cables are suitable for fixed installation in dry or wet areas but not suitable as a direct burrial into water or earth. For installation in conduits all precautions must be taken to prevent an accumulation of water in the pipes.
| FE180: | Insulation integrity for 180 min. Test according to IEC 60331 and DIN VDE 0472 part 814 Insulation integrity under direct impact of flames for a period of 180 minutes |
|---|---|
| E90: | Function integrity according to DIN VDE 4102 part 12 of electrical cable system for a period of min. 90 minutes assures the functional performance of water-pressure rising systems to avoid smoke and heat in safety stairs, machine rooms, emergency lifts, extract systems etc. |
Note:
- CE = the product is conformed with the EC Low-Voltage Directive 73/23/EEC.
- Conforms to RoHS.
Technical characteristics
NHXH FE180/E90
| Number of cores | × | core cross-section[mm2] | Approx. outer ø [mm] | Copper weight [kg/km] | Approx. cable weight [kg/km] | |
|---|---|---|---|---|---|---|
| 3 | × | 1,5 | re | 15,0 | 43 | 350 |
| 3 | × | 2,5 | re | 16,0 | 72 | 390 |
| 3 | × | 4 | re | 17,0 | 115 | 475 |
| 3 | × | 6 | re | 18,5 | 173 | 560 |
| 3 | × | 10 | re | 19,5 | 288 | 720 |
| 3 | × | 16 | rm | 22,0 | 461 | 970 |
| 3 | × | 25 | rm | 26,0 | 720 | 1400 |
| 3 | × | 35 | rm | 29,0 | 1008 | 1770 |
| 3 | × | 35+16 | rm | 29,5 | 1162 | 1930 |
| 3 | × | 50+25 | rm | 33,5 | 1680 | 2610 |
| 3 | × | 70+35 | rm | 38,0 | 2352 | 3470 |
| 3 | × | 95+50 | rm | 43,0 | 3216 | 4670 |
| 3 | × | 120+70 | rm | 47,0 | 4128 | 5810 |
| 3 | × | 150+70 | rm | 51,0 | 4992 | 6840 |
| 3 | × | 185+95 | rm | 57,0 | 6240 | 8600 |
| 3 | × | 240+120 | rm | 62,5 | 8064 | 10900 |
| 4 | × | 1,5 | re | 16,0 | 58 | 380 |
| 4 | × | 2,5 | re | 18,0 | 96 | 465 |
| 4 | × | 4 | re | 19,0 | 154 | 560 |
| 4 | × | 6 | re | 20,0 | 230 | 650 |
| 4 | × | 10 | re | 22,0 | 384 | 880 |
| 4 | × | 16 | rm | 24,0 | 614 | 1190 |
| 4 | × | 25 | rm | 28,0 | 960 | 1730 |
| 4 | × | 35 | rm | 31,0 | 1344 | 2200 |
| 4 | × | 50 | rm | 35,0 | 1920 | 2890 |
| 4 | × | 70 | rm | 40,0 | 2688 | 3920 |
| 4 | × | 95 | rm | 45,0 | 3648 | 5210 |
| 4 | × | 120 | rm | 49,0 | 4608 | 6370 |
| 5 | × | 1,5 | re | 18,0 | 72 | 475 |
| 5 | × | 2,5 | re | 19,0 | 120 | 500 |
| 5 | × | 4 | re | 20,0 | 192 | 600 |
| 5 | × | 6 | re | 21,0 | 288 | 710 |
| 5 | × | 10 | re | 24,0 | 480 | 930 |
| 5 | × | 16 | rm | 26,0 | 768 | 1430 |
| 5 | × | 25 | rm | 30,0 | 1200 | 1910 |
| 5 | × | 35 | rm | 34,0 | 1680 | 2800 |
| 5 | × | 50 | rm | 39,0 | 2500 | 3730 |
| 7 | × | 1,5 | re | 19,0 | 101 | 560 |
| 7 | × | 2,5 | re | 21,0 | 168 | 750 |
| 10 | × | 1,5 | re | 23,0 | 144 | 750 |
| 10 | × | 2,5 | re | 24,8 | 240 | 900 |
| 12 | × | 1,5 | re | 25,0 | 173 | 850 |
| 12 | × | 2,5 | re | 26,1 | 288 | 990 |
NHXCH FE180/E90
| Number of cores | × | core cross-section[mm2] | Approx. outer ø [mm] | Copper weight [kg/km] | Approx. cable weight [kg/km] | |
|---|---|---|---|---|---|---|
| 3 | × | 1,5/1,5 | re | 16,9 | 66 | 370 |
| 3 | × | 2,5/2,5 | re | 18,0 | 104 | 430 |
| 3 | × | 4/4 | re | 19,0 | 161 | 530 |
| 3 | × | 6/6 | re | 20,1 | 240 | 640 |
| 3 | × | 10/10 | re | 21,8 | 408 | 850 |
| 3 | × | 16/16 | rm | 24,5 | 643 | 1130 |
| 3 | × | 25/16 | rm | 29,0 | 874 | 1550 |
| 3 | × | 35/16 | rm | 30,0 | 1162 | 2000 |
| 3 | × | 50/25 | rm | 33,0 | 1680 | 2600 |
| 3 | × | 70/35 | rm | 37,0 | 2352 | 3480 |
| 3 | × | 95/50 | rm | 43,0 | 3216 | 4680 |
| 3 | × | 120/70 | rm | 47,0 | 4128 | 5800 |
| 3 | × | 150/70 | rm | 52,0 | 4992 | 6850 |
| 3 | × | 185/95 | rm | 57,0 | 6240 | 8600 |
| 3 | × | 240/120 | rm | 63,0 | 8064 | 10980 |
| 4 | × | 1,5/1,5 | re | 18,0 | 81 | 430 |
| 4 | × | 2,5/2,5 | re | 18,9 | 128 | 500 |
| 4 | × | 4/4 | re | 20,1 | 200 | 600 |
| 4 | × | 6/6 | re | 21,2 | 297 | 730 |
| 4 | × | 10/10 | re | 23,0 | 504 | 1060 |
| 4 | × | 16/16 | im | 25,2 | 796 | 1360 |
| 4 | × | 25/16 | rm | 30,0 | 1142 | 1900 |
| 4 | × | 35/16 | rm | 33,5 | 1526 | 2410 |
| 4 | × | 50/25 | rm | 38,0 | 2203 | 3180 |
| 4 | × | 70/35 | rm | 42,5 | 3082 | 4385 |
| 4 | × | 95/50 | rm | 47,5 | 4208 | 5800 |
| 4 | × | 120/70 | rm | 51,5 | 5388 | 7225 |
| 4 | × | 150/70 | rm | 57,0 | 6540 | 8710 |
| 4 | × | 185/95 | rm | 63,5 | 8159 | 10700 |
| 4 | × | 240/120 | rm | 71,0 | 10546 | 13935 |
| 7 | × | 1 5/2,5 | re | 20,8 | 133 | 670 |
| 12 | × | 1,5/2,5 | re | 27,0 | 205 | 1050 |
| 24 | × | 1,5/6 | re | 36,5 | 413 | 1900 |
| 30 | × | 1,5/6 | re | 39,0 | 499 | 2200 |
| 7 | × | 2,5/2,5 | re | 21,2 | 200 | 680 |
| 12 | × | 2,5/4 | re | 27,0 | 334 | 1050 |
| 24 | × | 2,5/10 | re | 37,0 | 696 | 1900 |
| 30 | × | 2,5/10 | re | 39,0 | 840 | 2200 |
Contact us
Looking forward to cooperation with you.If you have any question or need our certification and sample.Pls contact me freely.You can talk with me by Email or chat software.
Vivian Yuan
Mobile:+86 15838290725
We are China Halogen-Free Fire Performance Cable Nhxh-J Fe180 E90 3X1, 5mm2 3X2.5 manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Halogen Free Cable Products
Freetox Halogen-Free N2xoh 0, 6/1 Kv 3X120+1X70 mm2 Multipolar Cable
0.6/1kv N2xh Flame-Retardant Halogen-Free Cable for Public Buildings
Lsfh LSZH Lsoh Fire-Resistant Flame Retardant Mineral Insulated Power Cable
2491b/6701b H05z-K/H07z-K Single Core Halogen Free Cable
Five-Core XLPE Insulation LSZH Sheath Halogen Free Power Cables
Cu or Al-XLPE-Cu-Po Unarmoured XLPE Insulation Flame Retardant Halogen Free Medium Voltage Cables
Popular Nhxh Products
Nhxh Fe180/E30 Fireproof Mains Cables LSZH
Popular Nhxh Cable Products
Ppgng /Nhxh Cable 4X120mm2 for Underground Armoured Power Cable
Popular zzhongdacable Products
The "Low Smoke" Element of LSZH Cables
2X10mm2 Concentric Service Cable with Communication Cores
Cu PVC1.5 2.5 6mm2 Black Wire House Building Wire
PVC Insulation 7 Wire Stranded Copper Conductor Wire Cable Thw 8 AWG 600V
25kv 15kv Urd Cable Mv Tr-XLPE, Medium Voltage Tr-XLPE Insulated Urd Cable
12kv 15kv 25kv XLPE Space Aerial Power Cable Sac
Tags: Halogen Free Cable, Nhxh, Nhxh Cable, zzhongdacable