Hot Sales 15kv Overhead ABC Cable
Hot Sales 15kv Overhead ABC Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Detailed Product Description
ABC cable
(Service drop cable)
1. Stranded aluminium conduct
2. PE or XLPE insulation
3. ACSR, AAAC Messenger wire
Application
It is preferred to use of service drop (ABC cables) instead of uninsulated conductors
At low voltage networks. Service drop (ABC cables)are especially used at areas
Where the cost of underground networks is expensive and also
For electrification of rural areas like villages.
Voltage
Rated voltage U0 / U = 0.6 /1 kV
VAC test voltage 5 kV
Technical Data
Maximum operating temperature 90 degree
Maximum short-circuit temperature 250 degree. Service drop( ABC cables) are especially used at areas where the cost of underground networks is expensive and also for electrification of rural areas like villages
Specification:
(1)Self-supporting
Phase | Phase | Phase | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20ºC | |||
AAC+UV-XLPE | Compact Conductor | UV-XLPE Insulation | |||||
No.X Normal Cross Section of Cores | No.of Al Wires | Overall Diameter | Normal Thickness | Min. | Diameter | ||
No. X mm2 | – | mm | mm | mm | mm | mm | ohm/km |
1 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 6.05 | 3.08 |
1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 7.20 | 1.91 |
1 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 8.40 | 1.20 |
1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 9.80 | 0.868 |
1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 11.10 | 0.641 |
1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 12.60 | 0.443 |
1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 14.80 | 0.320 |
1 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 16.20 | 0.253 |
1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 18.20 | 0.206 |
1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 20.20 | 0.164 |
1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 22.80 | 0.125 |
2 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 12.10 | 3.08 |
2 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 14.40 | 1.91 |
2 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 16.80 | 1.20 |
2 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 19.60 | 0.868 |
2 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 22.20 | 0.641 |
2 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 25.20 | 0.443 |
2 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 29.60 | 0.320 |
2 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 32.40 | 0.253 |
2 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 36.40 | 0.206 |
2 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 40.40 | 0.164 |
2 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 45.60 | 0.125 |
3 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 13.07 | 3.08 |
3 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 15.55 | 1.91 |
3 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 18.14 | 1.20 |
3 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 21.17 | 0.868 |
3 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 23.98 | 0.641 |
3 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 27.22 | 0.443 |
3 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 31.97 | 0.320 |
3 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 34.99 | 0.253 |
3 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 39.31 | 0.206 |
3 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 43.63 | 0.164 |
3 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 49.25 | 0.125 |
4 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 14.64 | 3.08 |
4 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 17.42 | 1.91 |
4 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 20.33 | 1.20 |
4 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 23.72 | 0.868 |
4 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 26.86 | 0.641 |
4 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 30.49 | 0.443 |
4 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 35.82 | 0.320 |
4 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 39.20 | 0.253 |
4 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 44.04 | 0.206 |
4 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 48.88 | 0.164 |
4 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 55.18 | 0.125 |
(2) Phase + Neutral
Phase | Neutral | Phase | Neutral | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20ºC | ||||
AAC+UV-XLPE | AAAC | Compact Conductor | UV-XLPE Insulation | Conductor | |||||
Phase | Neutral | ||||||||
No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No.of Al.Wire | Overall Dia. | Normal Thickness | Min. | No./Dia. of Al Alloy Wire | |||
No. X mm2 | No. X mm2 | – | mm | mm | Min. | No./mm | mm | ohm/km | ohm/km |
1 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 12.30 | 1.91 | 2.217 |
1 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 14.70 | 1.20 | 1.393 |
1 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 17.30 | 0.868 | 1.007 |
1 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 20.10 | 0.641 | 0.744 |
1 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 23.10 | 0.443 | 0.514 |
1 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 27.30 | 0.320 | 0.371 |
1 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 30.20 | 0.253 | 0.294 |
1 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 33.95 | 0.206 | 0.239 |
1 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 37.70 | 0.164 | 0.190 |
1 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 43.05 | 0.125 | 0.145 |
2 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 14.04 | 1.91 | 2.217 |
2 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 16.63 | 1.20 | 1.393 |
2 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 19.51 | 0.868 | 1.007 |
2 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 22.46 | 0.641 | 0.744 |
2 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 25.70 | 0.443 | 0.514 |
2 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 30.31 | 0.320 | 0.371 |
2 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 33.41 | 0.253 | 0.294 |
2 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 37.55 | 0.206 | 0.239 |
2 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 41.69 | 0.164 | 0.190 |
2 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 47.41 | 0.125 | 0.145 |
3 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 16.15 | 1.91 | 2.217 |
3 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 19.06 | 1.20 | 1.393 |
3 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 22.32 | 0.868 | 1.007 |
3 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 25.59 | 0.641 | 0.744 |
3 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 29.22 | 0.443 | 0.514 |
3 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 34.42 | 0.320 | 0.371 |
3 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 37.87 | 0.253 | 0.294 |
3 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 42.56 | 0.206 | 0.239 |
3 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 47.25 | 0.164 | 0.190 |
3 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 53.63 | 0.125 | 0.145 |
(3) Phase + Neutral + Service Connection
Phase | Neutral | Service Connection | Phase | Neutral | Service Connection | Approx.Overall Diameter of Bundled Cable | |||||
AAC+UV-XLPE | AAAC+UV-XLPE | AAC+UV-XLPE | Conductor | UV-XLPE | Conductor | UV-XLPE | Compact Conductor | UV-XLPE | |||
No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No. of Al. Wire | Overall Dia. | Normal Thickness |
No./Dia. of Al. Wire | Normal Thickness |
No. of Al. Wire | Overall Dia. | Normal Thickness |
|
No. X mm2 | No. X mm2 | No. X mm2 | – | mm | mm | mm | mm | No./mm | mm | mm | mm |
3 X 16 | 1 X 50 | 1 X 16 | 7 | 4.8 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 26.2 |
3 X 25 | 1 X 50 | 1 X 16 | 7 | 6 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 28.6 |
3 X 35 | 1 X 50 | 1 X 16 | 7 | 7.0 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 31.4 |
3 X 50 | 1 X 50 | 1 X 16 | 7 | 8.3 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 34 |
3 X 70 | 1 X 50 | 1 X 16 | 19 | 9.8 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 37 |
3 X 95 | 1 X 50 | 1 X 16 | 19 | 11.6 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 41.4 |
3 X 120 | 1 X 50 | 1 X 16 | 19 | 13 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 44.2 |
3 X 16 | 1 X 50 | 2 X 16 | 7 | 4.8 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 26.2 |
3 X 25 | 1 X 50 | 2 X 16 | 7 | 6 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 28.6 |
3 X 35 | 1 X 50 | 2 X 16 | 7 | 7.0 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 31.4 |
3 X 50 | 1 X 50 | 2 X 16 | 7 | 8.3 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 34 |
3 X 70 | 1 X 50 | 2 X 16 | 19 | 9.8 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 37 |
3 X 95 | 1 X 50 | 2 X 16 | 19 | 11.6 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 41.4 |
3 X 120 | 1 X 50 | 2 X 16 | 19 | 13 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 44.2 |
We are China Hot Sales 15kv Overhead ABC Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular ABC Cable Products
3*16 ABC Aluminum Cable XLPE/PE/PVC/HDPE/MDPE/LDPE
10kv Overhead Aluminum Conductor Covered Line Wire
0.6/1kv ABC Cable 4X95 +2X25 mm2
33kv (3+1) Core Alumium Aerial Bundle Cable (ABC Cable NFC 33-226
Popular Insulated Cable Products
Low Voltage XLPE PVC Insulated Armoured Flexible Electric
Cable Aerial Bundled Cable All Aluminum Conductor XLPE Insulated Overhead Cable
PVC Insulated Power Electric Control Cable
Aerial Bundled Cable Selling to Malaysia
Copper/Aluminium Conductor XLPE PVC Insulated and Sheathed Power Cable.
Popular jpcable99 Products
Two Cores Aluminum Conductor XLPE Insulated ABC Cable
Copper Conductor PVC Insulated Underground Power Cables (VV/VV22/VV32)
High Quality Flame Retardant Cable
AAC Ant/Bee/Locust/Centipede All Aluminium Conductor
Popular Overhead ABC Cable Products
AAAC Conductor Service Drop Cable Twisted Aluminum Overhead ABC Cable
Aluminum Conductor XLPE Inslation ABC Cable 25mm2 35mm2 50mm2
Low Voltage Quadruplex Service Drop/ACSR (ABC Cable)
ABC Wholesalers 10kv Quadruplex ABC Cable for Yemen
ASTM Standard Triplex ABC Cable Aerial Bundled Conductor
XLPE Insulated Triplex Service Drop-Aluminum Conductor, Overhead ABC Cable
Tags: ABC Cable, Insulated Cable, jpcable99, Overhead ABC Cable