Basic Info.

Model NO.
AAC

Certification
ISO9001, CE, SABS

Brand
Henan Jiapu

Delivery Length
Accord with The Request

Standards
ASTM B231, CSA C 49, BS 215, DIN 48201, IEC 61089

Capacity
2000ton/Month

MOQ
1km

Transport Package
Wooden Drum

Specification
IEC, ASTM, DIN, BS, GB, Any standard

Trademark
Jiapu

Origin
Henan China

HS Code
7614900000

Production Capacity
2000ton/Month

Product Description

AAC  with BS 215, DIN48201, CSA C49, ASTM B231 

Capacity: 2000ton/month
Delivery Length: accord with the request 
Min.Order Qty : 1km
 
Application
The conductors are suitable for use in spans on wood poles, transmission towers,and other structures where tensile strength and temperature ratings are not required. Application range from extra high voltage(EHV) transmission lines to sub-service spans at distribution or utilization voltages on private premises.
AAC(All aluminum conductor) is the most economical bare overhead conductor due to its lighter weight. It offers easier handing during installation and use of simpler fittings. The conductor is corrosion resistant due to its homogeneous construction.
 
 
Construction
Aluminum 1350 wires are concentrically stranded and wrapped helically around a central wire. Each successive layer has six wires more than the previous underlying layer. Outer layer is right hand lay and reversed in successive layers.


FAQ

1. How many years has Henan Jiapu Cable Group been in production?

Founded in October 1998 by Mr. Gu, our facility has three separate manufacturing workshops within its 100,000-sq.-ft. building. In 2012, we operates in a new 666,000 sq. foot state-of-the-art facility in Xiaodian Industry Park.,Xinxiang, Henan ,China

 

2. What kinds of products does Jiapu Cable manufacture?

1)Bare Conductor ,such as AAC,AAAC,ACSR,ACAR,AACSR,ACSR/AW and so on;

2)Aerial Bundled Cable (1kV-35kV ),such as Duplex,Triplex,Quadruplex Drop Wires and so on;

3)PVC Insulated (Flexible ) Wire ;

4) PVC Insulated and Sheathed (Armoured) Power Cable;

5)Low, Medium, High Voltage (1kV-220kV) XLPE Insulated (Armoured) Power Cable;

6)Welding Cable, Control Cable, Concentric Cable, Rubber Sheathed Cable and so on;

 

3. What kind of certifications do you have?

SABS, CE, ISO9001-2000, SGS

 

4.Which markets do you involve mainly in?

Our products have been exported mainly to Africa, Middle East, South-east Asia, South America,Central America,North America, Europe ,Australia, etc.

 

5. Which standards do you comply with when you produce the electrical wires and cables ?

We are able to produce electrical wires and cables based on GB, JB, IEC, BS, DIN, ASTM, JIS, NF, AS/NZS, CSA, etc. Meanwhile, we can design and manufacture the cables according to the samples and technical specification the customer supply.

 

6. What is the min.order quantity ?

It depends on the type and size of electrical wires and cables. For some small electrical wires, 100 meters can be accepted .But for the power cables with medium or high voltage, that should comply with the property of installed equipments. Anyhow,we will try our best to solve the problem and meet with the requirement If you have special request.

 

7. What is the production capacity per week or per month ?

For the bare conductor, we can finish 3000 tons within one month. For power cables, that depends on the type and size. The total output value per month is approx. USD3,000,000.00 for insulated aluminum cables and that is approx. USD8,000,000.00 for insulated copper cables.

 

8. Do you supply the customers with installation service in foreign country ?

We don’t have professional installation teams in foreign country.But if that is necessary, we will recommend our partners to cooperate with you.

Specifications:

AAC with DIN48201 Standard      
Code Number Calculated Cross Section No./Dia.of Stranding Wire  Overall Diameter Linear Mass Calculated Breaking Load Max.D.C. Resistance       
     
mm² mm² mm mm kg/km daN Ω/km      
16 15.89 7/1.70 5.1 44 290 1.8018      
25 24.25 7/2.10 6.3 67 425 1.1808      
35 34.36 7/2.50 7.5 94 585 0.8332      
50 49.48 7/3.00 9 135 810 0.5786      
50 48.36 19/1.80 9 133 860 0.595      
70 65.82 19/2.10 10.5 181 1150 0.4371      
95 93.27 19/2.50 12.5 256 1595 0.3084      
120 117 19/2.80 14 322 1910 0.2459      
150 147.1 37/2.25 15.2 406 2570 0.196      
185 181.6 37/2.50 17.5 501 3105 0.1587      
240 242.54 61/2.25 20.2 670 4015 0.1191      
300 299.43 61/2.50 22.5 827 4850 0.0965      
400 400.14 61/2.89 26 1105 6190 0.0722      
500 499.83 61/3.23 29.1 1381 7600 0.0578      
625 626.2 91/2.96 32.6 1733 9690 0.04625      
800 802.1 91/3.35 36.8 2219 12055 0.0361      
1000 999.71 91/3.74 41.1 2766 14845 0.029      
AAC with BS 215 Standard      
Code Name Nominal  Cross Section No./Dia.of Stranding Wires Overall Diameter Approx. Weight Max.D.C Resistance  of Conductor  Calculated Breaking Load Final Modulus of Elasticity Coefficient of Linear Expansion  
mm 2 No./mm mm kg/km ohm/km daN hbar    
Midge 22 7/2.06 6.18 64 1.227 399 5900 23 x 10 -6  
Aphis 25 3/3.35 7.2 73 1.081 411 5900 23 x 10 -6  
Gnat 25 7/2.21 6.6 73 1.066 459 5900 23 x 10 -6  
Weevil 30 3/3.66 7.9 86 0.9082 486 5900 23 x 10 -6  
Mosquito 35 7/2.59 7.8 101 0.7762 603 5900 23 x 10 -6  
Ladybird 40 7/2.79 8.4 117 0.6689 687 5900 23 x 10 -6  
Ant 50 7/3.10 9.3 145 0.5419 828 5900 23 x 10 -6  
Fly 60 7/3.40 10.2 174 0.4505 990 5900 23 x 10 -6  
Bluebottle 70 7/3.66 11 202 0.3881 1134 5900 23 x 10 -6  
Earwing 75 7/3.78 11.4 215 0.3644 1194 5900 23 x 10 -6  
Grasshopper 80 7/3.91 11.7 230 0.3406 1278 5900 23 x 10 -6  
Clegg 90 7/4.17 12.5 262 0.2994 1453 5900 23 x 10 -6  
Wasp 100 7/4.39 13.17 290 0.2702 1600 5900 23 x 10 -6  
Beetle 100 19/2.67 13.4 293 0.2704 1742 5600 23 x 10 -6  
Bee 125 7/4.90 14.7 361 0.2169 1944 5900 23 x 10 -6  
Cricket 150 7/5.36 16.1 432 0.1818 2385 5900 23 x 10 -6  
Hornet 150 19/3.25 16.25 434 0.1825 2570 5600 23 x 10 -6  
Caterpillar 175 19/3.53 17.7 512 0.1547 2863 5600 23 x 10 -6  
Chafer 200 19/3.78 18.9 587 0.1349 3240 5600 23 x 10 -6  
Spider 225 19/3.99 20 652 0.1211 3601 5600 23 x 10 -6  
Cockroach 250 19/4.22 21.1 731 0.1083 4040 5600 23 x 10 -6  
Butterfly 300 19/4.65 23.25 888 0.08916 4875 5600 23 x 10 -6  
Moth 350 19/5.00 25 1027 0.07711 5637 5600 23 x 10 -6  
Drone 350 37/3.58 25.1 1029 0.07741 5745 5600 23 x 10 -6  
Locust 400 19/5.36 26.8 1179 0.0671 6473 5600 23 x 10 -6  
Centipede 400 37/3.78 26.46 1145 0.06944 6310 5600 23 x 10 -6  
Maybug 450 37/4.09 28.6 1342 0.05931 7401 5600 23 x 10 -6  
Scorpion 500 37/4.27 29.9 1460 0.05441 7998 5600 23 x 10 -6  
Cicada 600 37/4.65 32.6 1733 0.04588 9495 5600 23 x 10 -6  
Tarantula 750 37/5.23 36.6 2191 0.03627 12010 5600 23 x 10 -6  
AAC with CSA C49 Standard  
Code Name KCMIL or AWG Cross Section of Aluminum Size Total Mass Rated Tensile Strength Max.D.C. Resistance   
No.of Wires Dia.of Wires Dia.of Conductor  
    mm²  – mm  mm kg/km     kN Ω/km  
Anemone 874.5 443.12 37 3.9 27.3 1223 72.9 0.06509  
Cockscomb 900 456.04 37 3.96 27.72 1259 75.2 0.06324  
  927.2 469.82 37 4.02 28.14 1297 77.5 0.06139  
Magnolia 954 483.4 37 4.08 28.56 1334 79.8 0.05966  
Hawkweed 1000 506.71 37 4.18 29.26 1399 83.8 0.05692  
Bluebell 1033.5 523.68 37 4.25 29.75 1445 86.6 0.05507  
  1100 557.38 61 3.41 30.69 1541 94.7 0.05182  
Marigold 1113 563.97 61 3.43 30.87 1559 95.8 0.05121  
Hawthorn 1192.5 604.25 61 3.55 31.95 1670 103 0.0478  
  1200 608.05 61 3.56 32.04 1681 103 0.0475  
Narcissus 1272 644.54 61 3.67 33.03 1782 110 0.04481  
  1300 658.72 61 3.71 33.39 1821 112 0.04385  
Columbine 1351.5 684.82 61 3.78 34.02 1893 113 0.04218  
  1400 709.39 61 3.85 34.65 1961 117 0.04072  
Carnation 1431 725.1 61 3.89 35.01 2004 120 0.03983  
  1500 760.07 61 3.98 35.82 2101 125 0.038  
Gladiolus 1510.5 762.72 61 3.99 35.91 2110 123 0.0379  
Coreopsis 1590 805.67 61 4.1 36.9 2227 133 0.03585  
  1600 810.74 61 4.11 36.99 2241 134 0.03563  
  1700 861.41 61 4.24 38.16 2381 142 0.03353  
  1800 912.08 91 3.57 39.27 2524 155 0.0317  
Cowslip 2000 1013.42 91 3.77 41.47 2804 168 0.02853  
Sagebrush 2250 1140.1 91 3.99 43.89 3155 188 0.02536  
  2435.6 1234.14 91 4.16 45.76 3415 204 0.02343  
Lupine 2500 1266.78 91 4.21 46.31 3505 209 0.02283  
Bitterroo 2750 1393.45 91 4.42 48.62 3856 230 0.02075  
  3000 1520.13 91 4.61 50.71 4207 251 0.01902  
  3007.7 1524.03 91 4.62 50.82 4217 252 0.01897  
  3500 1773.49 91 4.98 54.78 4908 292 0.0163  
  3640 1844.42 91 5.08 55.88 5104 304 0.01568  
AAC with ASTM B231 Standard      
Code word Size of Conductor Stranding and Wire Diameter Overall Diameter Max.D.C. Resistance at 20°C Code word Size of Conductor Stranding and Wire Diameter Overall Diameter Max.D.C. Resistance 
AWG or MCM mm mm ohm/km AWG or MCM mm mm ohm/km
Peachbell 6 7/1.554 4.67 2.1692 Verbena 700 37/3.493 24.45 0.0813
Rose 4 7/1.961 5.89 1.3624 Nasturtium 715.5 61/2.75 24.76 0.0795
Lris 2 7/2.474 7.42 0.8577 Violet 715.5 37/3.533 24.74 0.0795
Pansey 1 7/2.776 8.33 0.6801 Cattail 750 61/2.817 25.35 0.0759
Poppy 1/0 7/3.119 9.36 0.539 Petunia 750 37/3.617 25.32 0.0759
Aster 2/0 7/3.503 10.51 0.4276 Lilac 795 61/2.90 26.11 0.0715
Phlox 3/0 7/3.932 11.8 0.339 Arbutus 795 37/3.724 26.06 0.0715
Oxlip 4/0 7/4.417 13.26 0.2688 Snapdragon 900 61/3.086 27.78 0.0632
Valerian 250 19/2.913 14.57 0.2275 Cockscomb 900 37/3.962 27.73 0.0632
Sneezewort 250 7/4.80 14.4 0.2275 Goldenrod 954 61/3.177 28.6 0.0596
Laurel 266.8 19/3.01 15.05 0.2133 Magnolia 954 37/4.079 28.55 0.0596
Daisy 266.8 7/4.96 14.9 0.2133 Camellia 1000 61/3.251 29.36 0.0569
Peony 300 19/3.193 15.97 0.1896 Hawkweed 1000 37/4.176 29.23 0.0569
Tulip 336.4 19/3.381 16.91 0.1691 Larkspur 1033.5 61/3.307 29.76 0.055
Daffodil 350 19/3.447 17.24 0.1625 Bluebell 1033.5 37/4.244 29.72 0.055
Canna 397.5 19/3.673 18.36 0.1431 Marigold 1113 61/3.432 30.89 0.0511
Goldentuft 450 19/3.909 19.55 0.1264 Hawthorn 1192.5 61/3.551 31.05 0.0477
Syringa 477 37/2.882 20.19 0.1193 Narcissus 1272 61/3.668 33.02 0.0477
Cosmos 477 19/4.023 20.12 0.1193 Columbine 1351.5 61/3.78 34.01 0.0421
Hyacinth 500 37/2.951 20.65 0.1138 Carnation 1431 61/3.89 35.03 0.0398
                   

We are China Hot Selling BS 215 AAC Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular AAC Products

AAC Conductor, All Aluminium Conductor (UNE 21018)

ACSR-Aluminum Conductor Steel Reinforced, Power Transmission, Yifang Cable

Pre-assembled Aluminum Overhead Cable 3X70+1X50mm2 0.6/1kV

ASTM B399 Standard AAAC AAC ACSR Cable Conductor

ACSR/ AAC/ AAAC Conductor & Cable

Aluminum Wires 3*50mm2 AAC Cable

Popular AAC Conductor Products

IEC/BS/ASTM Standard Bare Aluminum Conductor Overhead AAC Conductor Sizes

Rose ASTM Standard AAC Conductor

AAC Narcissus Conductors

Aluminium Alloy Stranded Bare AAC Conductor

Bare Aluminum Cable All Aluminum Alloy Conductor ASTM B399

AAC Conductor ASTM B231 All Aluminum Conductor Stranded Bare Conductor AAC for Overhead Lines

Popular Hot Selling BS 215 AAC Conductor Products

  • No related articles
  • Popular jpcable99 Products

    Medium Voltage Armoured XLPE Power Cable (YJV22/YJV32/YJV)

    XLPE Insulated Power Cable

    Low Voltage XLPE Insulated Power Cable

    H07V-K Copper Conductor PVC Insulated Flexible Wire

    22kv Medium Voltage Underground XLPE Power Cable

    Bare Conductor Aluminum Clad Steel Wire/Strand

    Tags: , , ,

    FAST AND RELIABLE SERVICE FOR YOUR PROJECT

    Contact our trained experts today to find your perfect power solution.

    ASK A QUESTION