House Wire Copper Core Power Cable Conductor PVC Insulated Flexible Electrical Round Wire

China 
                        House Wire Copper Core Power Cable Conductor PVC Insulated Flexible Electrical Round Wire
                      manufacture and supplier

House Wire Copper Core Power Cable Conductor PVC Insulated Flexible Electrical Round Wire image

Get Latest Price Request a quote

Quick Details

House Wire Copper Core Power Cable Conductor PVC Insulated Flexible Electrical Round Wire

Zhonghua

CE, CCC

Electrical Device/Domestic Appliance, etc

Round Wire

PVC

None

Electrical Device/Domestic Appliance, etc

Solid

Insulated

Black, Red, Yellow, Blue, White

ZHONGHUA

Roll in

1.5-400mm2

Hubei, Wuhan

8544110000

Product Details

450/750V Copper Core PVC Insulated Electric Wire 

Application 
A. It can be applied to be installation and connection for electrical device, equipment power device, domestic appliance, instrument,lighting circuit, and automation device.
B. The feature of flame retardant cable is not easy to be fired and can control the flame into certain restriction and slow the fire speed after fire. So it can be applied to the occasion with high request of  flame retardant.
C. Flame cable can be divided into 4 grade: A,B,C,D and the Grade A is the best flame retardant grade.
D. Beside the cable can transfer power at the normal condition, it can also keep a period of safe operation under fire. It can be applied for the occasion with request of fire resistance.

Pruduct Structure

Reference Data of the Product Structure:  IEC 60227
1. 01(BV)Cable

Nominal Section
of the conductor
(mm2)
Conductor Types Cable Reference Diameter
(mm)
Cable Average Diameter
(mm)
Cable Reference Weight
(kg/km)
Maximum Resistance of the conductor at 20ºC
(/km)
Minumum Insulation Resistance at 70ºC
(M·km)
Reference Current
(Ambient temperature is 40ºC,highest temperature is 70ºC)
(A)
BV Minimum Maximum BV
1.5 1 2.82 2.6 3.2 19.70 12.1 0.011 18
1.5 2 3.00 2.7 3.3 20.31 12.1 0.010 18
2.5 1 3.43 3.2 3.9 31.20 7.41 0.010 25
2.5 2 3.69 3.3 4.0 32.82 7.41 0.009 25
4 1 3.90 3.6 4.4 46.08 4.61 0.0085 33
4 2 4.20 3.8 4.6 47.45 4.61 0.0077 33
6 1 4.41 4.1 5.0 65.71 3.08 0.0070 42
6 2 4.77 4.3 5.2 67.19 3.08 0.0065 42
10 1 5.65 5.3 6.4 109.09 1.83 0.0070 58
10 2 6.13 5.6 6.7 113.07 1.83 0.0065 58
16 2 7.18 6.4 7.8 170.90 1.15 0.0050 78
25 2 8.92 8.1 9.7 268.52 0.727 0.0050 105
35 2 10.06 9.0 10.9 362.82 0.524 0.0043 130
50 2 11.81 10.6 12.8 492.15 0.387 0.0043 155
70 2 13.61 12.1 14.6 694.19 0.268 0.0035 200
95 2 15.93 14.1 17.1 959.23 0.193 0.0035 250
120 2 17.54 15.6 18.8 1197.15 0.153 0.0032 290
150 2 19.49 17.3 20.9 1472.95 0.124 0.0032 335
185 2 21.80 19.3 23.3 1846.14 0.0991 0.0032 390
240 2 24.83 22.0 26.6 2416.54 0.0754 0.0032 470
300 2 27.67 24.5 29.6 3023.55 0.0601 0.0030 540
400 2 31.06 27.5 33.2 3851.72 0.0470 0.0028 635

 
2.02(RV)Cable

Nominal Section
of the conductor
(mm2)
Conductor Types Cable Reference Diameter
(mm)
Cable Average Diameter
(mm)
Cable Reference Weight
(kg/km)
Maximum Resistance of the conductor at 20ºC
(Ω/km)
Minumum Insulation Resistance at 70ºC
(MΩ·km)
Reference Current
(Ambient temperature is 40ºC,highest temperature is 70ºC)
(A)
RV Minimum Maximum RV
1.5 5 3.00 2.8 3.4 20.30 13.3 0.010 18
2.5 5 3.64 3.4 4.1 31.59 7.98 0.009 25
4 5 4.21 3.9 4.8 47.54 4.95 0.0070 33
6 5 4.81 4.4 5.3 67.42 3.3 0.0060 42
10 5 6.28 5.7 6.8 118.00 1.81 0.0056 58
16 5 7.20 6.7 8.1 169.44 1.21 0.0046 78
25 5 10.10 8.4 10.2 269.71 0.78 0.0044 105
35 5 11.23 9.7 11.7 364.35 0.554 0.0038 130
50 5 13.75 11.5 13.9 522.86 0.386 0.0037 155
70 5 15.40 13.2 16.0 720.89 0.272 0.0032 200
95 5 18.15 15.1 18.2 953.89 0.206 0.0032 250
120 5 19.70 16.7 20.2 1199.28 0.161 0.0029 290
150 5 21.10 18.6 22.5 1485.62 0.129 0.0029 335
185 5 24.03 20.6 24.9 1824.52 0.106 0.0029 390
240 5 26.70 23.5 28.4 2389.69 0.0801 0.0028 470

 
3.05(BV)Cable

Nominal Section
of the conductor
(mm2)
Conductor Types Cable Reference Diameter
(mm)
Cable Average Diameter
(mm)
Cable Reference Weight
(kg/km)
Maximum Resistance of the conductor at 20ºC
(Ω/km)
Minumum Insulation Resistance at 70ºC
(MΩ·km)
Reference Current
(Ambient temperature is 40ºC,highest temperature is 70ºC)
(A)
BV Minimum Maximum BV
0.5 1 2.04 1.9 2.3 8.16 36.0 0.015 9
0.75 1 2.21 2.1 2.5 10.71 24.5 0.012 12
1 1 2.37 2.2 2.7 13.48 18.1 0.011 14

 
4.06(RV)Cable

Nominal Section
of the conductor
(mm2)
Conductor Types Cable Reference Diameter
(mm)
Cable Average Diameter
(mm)
Cable Reference Weight
(kg/km)
Maximum Resistance of the conductor at 20ºC
(Ω/km)
Minumum Insulation Resistance at 70ºC
(MΩ·km)
Reference Current
(Ambient temperature is 40ºC,highest temperature is 70ºC)
(A)
RV Minimum Maximum RV
0.5 5 2.18 2.1 2.5 8.58 39.0 0.013 9
0.75 5 2.43 2.2 2.7 11.50 26.0 0.011 12
1 5 2.52 2.4 2.8 14.00 19.5 0.010 14

 
5.10(BVV)Cable

Core No.×Nominal Section
of the conductor
(mm2)
Conductor Types Cable Reference Diameter
(mm)
Cable Average Diameter
(mm)
Cable Reference Weight
(kg/km)
Maximum Resistance of the conductor at 20ºC
(Ω/km)
Minumum Insulation Resistance at 70ºC
(MΩ·km)
Reference Current
(Ambient temperature is 40ºC,highest temperature is 70ºC)
(A)
BVV Minimum Maximum BVV
2×1.5 1 9.36 7.6 10.0 98.94 12.1 0.011 18
2×1.5 2 9.72 7.8 10.5 103.09 12.1 0.010 18
2×2.5 1 10.56 8.6 11.5 130.99 7.41 0.010 25
2×2.5 2 11.08 9.0 12.0 138.55 7.41 0.009 25
2×4 1 11.50 9.6 12.5 171.31 4.61 0.0085 33
2×4 2 12.10 10.0 13.0 179.24 4.61 0.0077 33
2×6 1 12.52 10.5 13.5 218.41 3.08 0.0070 42
2×6 2 13.24 11.0 14.0 227.77 3.08 0.0065 42
2×10 1 15.64 13.0 16.5 361.55 1.83 0.0070 65
2×10 2 16.70 13.5 17.5 384.71 1.83 0.0065 65
2×16 2 18.80 15.5 20.0 532.01 1.15 0.0052 87
2×25 2 22.64 18.5 24.0 798.61 0.727 0.0050 110
2×35 2 25.72 21.0 27.5 1055.97 0.524 0.0044 140
3×1.5 1 9.8 8.0 10.5 124.61 12.1 0.011 15
3×1.5 2 10.19 8.2 11.0 129.71 12.1 0.010 15
3×2.5 1 11.10 9.2 12.0 168.94 7.41 0.010 21
3×2.5 2 11.66 9.4 12.5 178.67 7.41 0.009 21
3×4 1 12.12 10.0 13.0 228.20 4.61 0.0085 28
3×4 2 12.76 10.5 13.5 238.21 4.61 0.0077 28
3×6 1 13.62 11.5 14.5 307.47 3.08 0.0070 36
3×6 2 14.40 12.0 15.5 319.96 3.08 0.0065 36
3×10 1 16.52 14.0 17.5 476.74 1.83 0.0070 56
3×10 2 17.67 14.5 19.0 507.40 1.83 0.0065 56
3×16 2 20.34 16.5 21.5 726.41 1.15 0.0052 74
3×25 2 24.05 20.5 26.0 1074.22 0.727 0.0050 98
3×35 2 27.31 22.0 29.0 1431.17 0.524 0.0044 120
4×1.5 1 10.51 8.6 11.5 159.43 12.1 0.011 15
4×1.5 2 10.95 9.0 12.0 165.62 12.1 0.010 15
4×2.5 1 11.96 10.0 13.0 216.48 7.41 0.010 21
4×2.5 2 12.59 10.0 13.5 228.55 7.41 0.009 21
4×4 1 13.49 11.5 14.4 296.50 4.61 0.0085 28
4×4 2 14.22 12.0 15.0 309.46 4.61 0.0077 28
4×6 1 15.13 12.5 16.0 398.92 3.08 0.0070 36
4×6 2 15.99 13.0 17.0 414.94 3.08 0.0065 36
4×10 1 17.93 15.5 19.0 594.97 1.83 0.0070 56
4×10 2 19.20 16.0 20.5 633.59 1.83 0.0065 56
4×16 2 22.14 18.0 35.5 916.62 1.15 0.0052 74
4×25 2 27.09 22.5 28.5 1414.08 0.727 0.0050 98
4×35 2 28.84 24.5 32.0 1826.39 0.524 0.0044 120
5×1.5 1 11.31 9.4 12.0 191.08 12.1 0.011 15
5×1.5 2 11.79 9.8 12.5 198.39 12.1 0.010 15
5×2.5 1 12.93 11.0 14.0 260.97 7.41 0.010 21
5×2.5 2 13.63 11.0 14.5 275.46 7.41 0.009 21
5×4 1 15.00 12.5 16.0 370.96 4.61 0.0085 28
5×4 2 15.81 13.0 17.0 387.08 4.61 0.0077 28
5×6 1 16.37 13.5 17.5 482.44 3.08 0.0070 36
5×6 2 17.34 14.5 18.5 501.42 3.08 0.0065 36
5×10 1 19.50 17.0 21.0 725.11 1.83 0.0070 56
5×10 2 20.94 17.5 22.0 771.84 1.83 0.0065 56
5×16 2 24.57 20.5 26.0 1142.09 1.15 0.0052 74
5×25 2 29.61 24.5 31,5 1732.02 0.727 0.0050 98
5×35 2 33.09 27.0 35.0 2272.06 0.524 0.0044 120

Notes: Conductor Types–1st type is solid conductor;2nd type is stranded conductor;5th type is stranded soft conductor;
     which are suitable for different applications.

We are China House Wire Copper Core Power Cable Conductor PVC Insulated Flexible Electrical Round Wire manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular 450/750V Cable Products

PVC Insulation and Flexible Cable

1.5 2.5mm2 4sqmm H07V-R 450/750V House Building Electric Wire Cable

Flexible Cooper Core PVC Insulation Electrical Wire Cables 4mm 6mm

Hot 1.5mm 2.5mm 4mm 6mm 10mm Single Core Copper PVC Flexibility House Electrical Wires and Cable

450/750kv Braided Screened Flexible Control Cable

BS Standard Solid Stranded Conductor Resistant Heat BVV Bvr BV House Building Overhead Flexible Insulating Sheath PVC Copper Cable Electric Wire

Popular Cable Products

Power/PVC/PE/XLPE/Copper/Insulated/Copper/Rubber Cable

High Quality XLPE Insulation Steel Wire Armour Cable

DIN Standard Overhead Aluminum Alloy Wire Stranded Electrical Cable 70mm2 Bare AAAC Conductor

Coal Mining Machine Rubber Soft Cable (UC UCP UCP MY MYP MCP)

Thhn/Thwn Wire ASTM AWG #10 #12 #14 Available and Free

Customized Multicore 10sqmm Copper Wire Control Cable Factory Price

Popular Power Cable Products

LV/Flame Redartant/Steel Tape Armored/XLPE Insulated Electric Power Cable Manufacturer

Underground Electrical Power Cable Copper Power Cable

Electric 185mm2 240mm2 300mm2 400mm2 500mm2 630mm2 PVC Insulated Single Core Copper Underground Power Wire Cable

11kv, 10kv, 12kv, 6/10kv, 3core 400sqmm XLPE Copper Cable

12kv XLPE Insulation Copper or Aluminium Swa Power Cable

ABC Cable Aerial Bundled Conductor Alluminum Cable 25mm2

Popular wuhancable Products

Copper Conductor XLPE/PVC Insulated PE/PVC Sheathed Armored Electrical Power Cable

IEC61089 All Aluminum Alloy Condcutor AAAC 40

Bare Conductor Overhead Conductor AAAC All Aluminium Alloy Bare Conductor AAAC

British Sizes 3242 All Aluminum Alloy Condcutor AAAC Ash

USA Sizes ASTM B232 Overhead Conductor Steel Reinforced ACSR Flamingo

British Sizes 3242 All Aluminum Alloy Condcutor AAAC Willow

Tags: , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION