Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard
Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard image
Get Latest Price Request a quote
Basic Info.
Product Description
NFC33-226 is a medium voltage power cable with a rated voltage of 12kV to 20kV. The cables are available in single core or 3×1 construction and are suitable for buried, direct burial in soil or free air laying. The cable can be supplied with sheath colors according to the installation code: red for underground connections, gray for aerial, surface/underground and technical applications.
Specifically, product features and parameters of NFC33-226 cables may include:
1.Suitable for medium voltage power system from 12kV to 20kV;
2.Single core or 3×1 (clover) structure available;
3.It can be laid underground, directly buried in soil or in free air;
4.Sheath color can be selected according to installation specifications;
5.Aluminum material as a conductor;
6.XLPE and PE materials as insulation and sheath materials.
Features
- It can be applied to medium-voltage power systems from 12kV to 20kV, providing an efficient and reliable power transmission solution;
- Single core or 3×1 structure can be provided according to application requirements, which can meet the needs of different circuit connection methods;
- It can be laid underground, directly buried in soil or in free air, suitable for different application scenarios;
- Different colors of sheaths can be selected according to installation specifications, which helps to distinguish different types of cables and realize management and maintenance;
- Aluminum material is used as the conductor, which is not only light in weight and low in cost, but also has good electrical conductivity, thermal conductivity and corrosion resistance;
- XLPE and PE materials are used as insulation and sheath materials, which have good performances such as voltage resistance, heat resistance, and welding resistance.
Application
NFC33-226 cables are suitable for medium voltage power systems, with rated voltages between 12kV and 20kV. It can be used as a distribution line to transmit power, lighting and control signals, and can be applied in different scenarios, such as directly buried in the ground, laid in free air or buried in the soil.
More specifically, the application areas of NFC33-226 may include
1.Municipal engineering
Applied in the power distribution network of urban public facilities, streets and other areas
2.Industrial and mining enterprises:
Used in the construction and transformation of power distribution trunk lines in factories, mines and other places;
3.Residential quarters
Used as power distribution lines in residential quarters and villas.
Construction
Medium-voltage power cables have shielding and sheathing, and non-magnetic armoring can be used under necessary conditions. Refer to the figure below for the structure of conventional cables.
Performance
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 3.4 | 23.1 | 53.4 | 2603 | 0.387 | 230 | 235 |
| 3×1×70 | 3.4 | 24.9 | 57.5 | 3316 | 0.268 | 285 | 295 |
| 3×1×95 | 3.4 | 26.6 | 61.2 | 4153 | 0.193 | 340 | 360 |
| 3×1×120 | 3.4 | 28.3 | 64.9 | 4953 | 0.153 | 385 | 420 |
| 3×1×150 | 3.4 | 29.9 | 67.9 | 5815 | 0.124 | 430 | 475 |
| 3×1×185 | 3.4 | 31.5 | 72.0 | 6947 | 0.0991 | 485 | 550 |
| 3×1×240 | 3.4 | 34.0 | 77.6 | 8704 | 0.0754 | 560 | 650 |
NFC 33-226 Medium voltage cables (non-aerial) 6/10kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 3.4 | 23.1 | 53.4 | 1739 | 0.641 | 180 | 185 |
| 3×1×70 | 3.4 | 24.9 | 57.5 | 2070 | 0.443 | 220 | 230 |
| 3×1×95 | 3.4 | 26.6 | 61.2 | 2420 | 0.320 | 260 | 280 |
| 3×1×120 | 3.4 | 28.3 | 64.9 | 2769 | 0.253 | 300 | 325 |
| 3×1×150 | 3.4 | 29.9 | 67.9 | 3115 | 0.206 | 335 | 370 |
| 3×1×185 | 3.4 | 31.5 | 72.0 | 3574 | 0.164 | 380 | 425 |
| 3×1×240 | 3.4 | 34.0 | 77.6 | 4267 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 6/10kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 4.5 | 25.5 | 58.6 | 2892 | 0.387 | 230 | 245 |
| 3×1×70 | 4.5 | 27.3 | 62.7 | 3626 | 0.268 | 280 | 305 |
| 3×1×95 | 4.5 | 29.0 | 66.4 | 4481 | 0.193 | 335 | 375 |
| 3×1×120 | 4.5 | 30.7 | 70.1 | 5299 | 0.153 | 385 | 425 |
| 3×1×150 | 4.5 | 32.3 | 73.1 | 6176 | 0.124 | 430 | 485 |
| 3×1×185 | 4.5 | 33.9 | 77.2 | 7328 | 0.0991 | 490 | 560 |
| 3×1×240 | 4.5 | 36.4 | 82.8 | 9113 | 0.0754 | 560 | 660 |
NFC 33-226Medium voltage cables (non-aerial) 8.7/15kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 4.5 | 25.5 | 58.6 | 2028 | 0.641 | 180 | 190 |
| 3×1×70 | 4.5 | 27.3 | 62.7 | 2379 | 0.443 | 220 | 235 |
| 3×1×95 | 4.5 | 29.0 | 66.4 | 2748 | 0.320 | 260 | 290 |
| 3×1×120 | 4.5 | 30.7 | 70.1 | 3115 | 0.253 | 300 | 330 |
| 3×1×150 | 4.5 | 32.3 | 73.1 | 3476 | 0.206 | 335 | 375 |
| 3×1×185 | 4.5 | 33.9 | 77.2 | 3955 | 0.164 | 380 | 430 |
| 3×1×240 | 4.5 | 36.4 | 82.8 | 4676 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 8.7/15kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 5.5 | 28.0 | 63.4 | 3180 | 0.387 | 230 | 245 |
| 3×1×70 | 5.5 | 29.5 | 67.5 | 3932 | 0.268 | 280 | 305 |
| 3×1×95 | 5.5 | 31.2 | 71.2 | 4804 | 0.193 | 335 | 375 |
| 3×1×120 | 5.5 | 32.9 | 74.9 | 5639 | 0.153 | 385 | 425 |
| 3×1×150 | 5.5 | 34.5 | 77.9 | 6530 | 0.124 | 430 | 485 |
| 3×1×185 | 5.5 | 36.1 | 82.0 | 7701 | 0.0991 | 490 | 560 |
| 3×1×240 | 5.5 | 38.6 | 87.6 | 9511 | 0.0754 | 560 | 660 |
NFC 33-226 Medium voltage cables (non-aerial) 12/20kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 5.5 | 28.0 | 63.4 | 2316 | 0.641 | 180 | 190 |
| 3×1×70 | 5.5 | 29.5 | 67.5 | 2685 | 0.443 | 220 | 235 |
| 3×1×95 | 5.5 | 31.2 | 71.2 | 3071 | 0.320 | 260 | 290 |
| 3×1×120 | 5.5 | 32.9 | 74.9 | 3455 | 0.253 | 300 | 330 |
| 3×1×150 | 5.5 | 34.5 | 77.9 | 3830 | 0.206 | 335 | 375 |
| 3×1×185 | 5.5 | 36.1 | 82.0 | 4328 | 0.164 | 380 | 430 |
| 3×1×240 | 5.5 | 38.6 | 87.6 | 5074 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 12/20kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 8.0 | 33.1 | 75.2 | 3979 | 0.387 | 230 | 245 |
| 3×1×70 | 8.0 | 34.9 | 79.2 | 4777 | 0.268 | 280 | 305 |
| 3×1×95 | 8.0 | 36.8 | 83.4 | 5725 | 0.193 | 335 | 375 |
| 3×1×120 | 8.0 | 38.3 | 86.6 | 6565 | 0.153 | 385 | 425 |
| 3×1×150 | 8.0 | 39.9 | 89.6 | 7491 | 0.124 | 430 | 485 |
| 3×1×185 | 8.0 | 41.5 | 93.7 | 8707 | 0.0991 | 490 | 560 |
| 3×1×240 | 8.0 | 44.0 | 99.3 | 10579 | 0.0754 | 560 | 660 |
NFC 33-226 Medium voltage cables (non-aerial) 18/30kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
| Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
| No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
| 3×1×50 | 8.0 | 33.1 | 75.2 | 3115 | 0.641 | 180 | 190 |
| 3×1×70 | 8.0 | 34.9 | 79.2 | 3530 | 0.443 | 220 | 235 |
| 3×1×95 | 8.0 | 36.8 | 83.4 | 3992 | 0.320 | 260 | 290 |
| 3×1×120 | 8.0 | 38.3 | 86.6 | 4381 | 0.253 | 300 | 330 |
| 3×1×150 | 8.0 | 39.9 | 89.6 | 4790 | 0.206 | 335 | 375 |
| 3×1×185 | 8.0 | 41.5 | 93.7 | 5334 | 0.164 | 380 | 430 |
| 3×1×240 | 8.0 | 44.0 | 99.3 | 6143 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 18/30kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular chinajinshui Products
Cable Copper Conductor PVC Flexible 5 Core Power Cable
High Quality Multi Core Soft Sheathing Cable Electric Power Cable
Rubber Sheath or PVC Sheath Welding Cable Factory Prices
4 Core Armoured Cable for Underground PVC Outdoor Power Cable
Best Seller Copper 4 Core Aluminium Power Cable
Electric Cable 450/750V PVC Twisted Electric Wire with The Best Price
Popular Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard Products
Popular Medium Voltage Cable Products
Medium Voltage Armored XLPE Power Cables
0.6 / 1kv 3 Core Aluminum Conductor PVC Insulated Outer Covered Power Cable
Na2xs (FL) 2y 18/30 (36) Kv Medium Voltage Power Cable
5kv 8kv 15kv 25kv 35kv XLPE/PVC Insulated Cable
Medium Voltage Urd Cable UL1072 Standard 15kv 25kv 35kv Tr-XLPE Insulation Power Cable Mv105 Mv90
15kv 240mm2 300mm2 Single Core 3 Core XLPE Insulation Cws Shield Power Cable
Popular Overhead Cable Products
AWG ASTM Insulated XLPE Aluminum Alloy Overhead Aerial Bundle Cable Urd/ABC Cable
LV ABC Amka-T Cable 3X95+16+70 (0.6/1kV) with Insulated Almelec Messenger
0.6/1kv 2*4/0AWG+4/0AWG Triplex Aluminum Wire Conductor ABC Overhead Cable
Overhead Bare Aluminum Stranded Cable AAC AAAC ACSR ACSR Cable
AAAC, AAC, Acar Bare Aluminum Conductor
Tags: chinajinshui, Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard, Medium Voltage Cable, Overhead Cable