Quick Details
Product Details
IEC 60502 cable, XLPE cables
1.Applications
These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors,
in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants,
where there is no risk of mechanical damage.
2.Construction
1)Conductors
The conductors shall be either of Class 1 or Class 2 of plain or metal-coated annealed copper or of plain aluminium or aluminium alloy,
or of Class 5 of plain or metal-coated copper in accordance with IEC 60228.
2)Insulation
XLPE material and thickness shall be as per IEC 60502 or BS 5467 rated for 90C continuous operation.
3)Colour Code
Colour Code (1)
| 1 Core | Red or Black |
| 2 Cores | Red, Black |
| 3 Cores | Red, Yellow, Blue |
| 4 Cores | Red, Yellow, Blue, Black |
| 5 Cores | Red, Yellow, Blue, Black, Green |
| Above 5 Cores | Black Cores with White numerals |
Colour Code (2)
| 1 Core | Brown or Blue |
| 2 Cores | Brown, Blue |
| 3 Cores | Brown, Black, Grey |
| 4 Cores | Blue, Brown, Black, Grey |
| 5 Cores | Green/Yellow, Blue, Brown, Black, Grey |
| Above 5 Cores | Black Cores with White numerals |
Other colours can be manufactured upon request.
4)Assembly / Inner Covering
The inner coverings may be extruded or lapped. For cables with circular cores, except cables with more than five cores,
a lapped inner covering shall be permitted only if the interstices between the cores are substantially filled.
A suitable binder is permitted before application of an extruded inner covering.
The material is compatible with the insulating material,
The materials used for inner coverings and fillers shall be suitable for the operating temperature of the cable and compatible with
the insulating material.For halogen free cables, the inner covering and fillers shall also be halogen free compound.
5)Armour
Aluminum/galvanized steel/steel wires applied helically over the Inner Covering as per IEC 60502-1,
or double aluminum/steel tapes and copper/tinned copper wire can also be manufactured upon request.
6)Outer Sheath
Outer sheath shall be of extruded PVC Type ST1/ST2 as per IEC 60502-1, Polyethylene type ST3/ST7,
Halogen free compound ST8, Polychloroprene, chlorosulfonated polyethylene or similar polymers, type SE1 are also available on request.
7)Fire Performance of Cable Sheaths
Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22,
IEC 60332-3-23 and IEC 60332-3-24, Halogen Free material comply to IEC60754-1/2 and IEC 60684-2.
3.Cable Parameters
1)Single core low voltage cables (unarmoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal Sheath Thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm |
| 1×1.5 | 1.4 | 0.7 | 1.4 | 5.6 |
| 1×2.5 | 1.8 | 0.7 | 1.4 | 6.0 |
| 1×4 | 2.3 | 0.7 | 1.4 | 6.5 |
| 1×6 | 2.8 | 0.7 | 1.4 | 7.0 |
| 1×10 | 3.6 | 0.7 | 1.4 | 7.8 |
| 1×16 | 4.5 | 0.7 | 1.4 | 8.7 |
| 1×25 | 5.6 | 0.9 | 1.4 | 10.2 |
| 1×35 | 6.7 | 0.9 | 1.4 | 11.3 |
| 1×50 | 8.0 | 1 | 1.4 | 12.8 |
| 1×70 | 9.4 | 1.1 | 1.4 | 14.4 |
| 1×95 | 11.0 | 1.1 | 1.5 | 16.1 |
| 1×120 | 12.4 | 1.2 | 1.5 | 17.8 |
| 1×150 | 13.8 | 1.4 | 1.6 | 19.8 |
| 1×185 | 15.3 | 1.6 | 1.6 | 21.8 |
| 1×240 | 17.5 | 1.7 | 1.7 | 24.4 |
| 1×300 | 19.5 | 1.8 | 1.8 | 26.7 |
| 1×400 | 22.6 | 2 | 1.9 | 30.5 |
| 1×500 | 25.2 | 2.2 | 2.0 | 33.7 |
| 1×630 | 28.3 | 2.4 | 2.2 | 37.4 |
| 1×800 | 31.9 | 2.6 | 2.3 | 41.7 |
| 1×1000 | 35.7 | 2.8 | 2.4 | 46.2 |
2)Two cores low voltage cables (unarmoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal Sheath Thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm |
| 2×1.5 | 1.4 | 0.7 | 1.8 | 9.2 |
| 2×2.5 | 1.8 | 0.7 | 1.8 | 10.0 |
| 2×4 | 2.3 | 0.7 | 1.8 | 11.0 |
| 2×6 | 2.8 | 0.7 | 1.8 | 12.0 |
| 2×10 | 3.6 | 0.7 | 1.8 | 13.6 |
| 2×16 | 4.5 | 0.7 | 1.8 | 15.4 |
| 2×25 | 5.6 | 0.9 | 1.8 | 18.4 |
| 2×35 | 6.7 | 0.9 | 1.8 | 20.6 |
| 2×50 | 8.0 | 1 | 1.8 | 23.6 |
| 2×70 | 9.4 | 1.1 | 1.8 | 26.8 |
| 2×95 | 11.0 | 1.1 | 1.9 | 30.2 |
| 2×120 | 12.4 | 1.2 | 2.0 | 33.7 |
| 2×150 | 13.8 | 1.4 | 2.2 | 37.5 |
| 2×185 | 15.3 | 1.6 | 2.3 | 41.6 |
| 2×240 | 17.5 | 1.7 | 2.5 | 46.7 |
| 2×300 | 19.5 | 1.8 | 2.6 | 51.4 |
| 2×400 | 22.6 | 2 | 2.9 | 58.9 |
3)Three cores low voltage cables (unarmoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal Sheath Thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm |
| 3×1.5 | 1.4 | 0.7 | 1.8 | 9.6 |
| 3×2.5 | 1.8 | 0.7 | 1.8 | 10.5 |
| 3×4 | 2.3 | 0.7 | 1.8 | 11.6 |
| 3×6 | 2.8 | 0.7 | 1.8 | 12.6 |
| 3×10 | 3.6 | 0.7 | 1.8 | 14.4 |
| 3×16 | 4.5 | 0.7 | 1.8 | 16.3 |
| 3×25 | 5.6 | 0.9 | 1.8 | 19.5 |
| 3×35 | 6.7 | 0.9 | 1.8 | 21.9 |
| 3×50 | 8.0 | 1 | 1.8 | 25.1 |
| 3×70 | 9.4 | 1.1 | 1.9 | 28.7 |
| 3×95 | 11.0 | 1.1 | 2.0 | 32.4 |
| 3×120 | 12.4 | 1.2 | 2.1 | 36.1 |
| 3×150 | 13.8 | 1.4 | 2.3 | 40.3 |
| 3×185 | 15.3 | 1.6 | 2.4 | 44.6 |
| 3×240 | 17.5 | 1.7 | 2.6 | 50.2 |
| 3×300 | 19.5 | 1.8 | 2.7 | 55.2 |
| 3×400 | 22.6 | 2 | 3.0 | 63.3 |
4)Three cores+1 low voltage cables (unarmoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal Sheath Thickness | Overall Diameter (Approx.) | ||
| mm^2 | (3)mm | (1)mm | (3)mm | (1)mm | mm | mm |
| 3x 16/10 | 4.5 | 3.6 | 0.7 | 0.7 | 1.8 | 17.5 |
| 3x 25/16 | 5.6 | 4.5 | 0.9 | 0.7 | 1.8 | 21.2 |
| 3x 35/16 | 6.7 | 4.5 | 0.9 | 0.7 | 1.8 | 23.8 |
| 3x 50/25 | 8 | 5.6 | 1 | 0.9 | 1.8 | 27.5 |
| 3x 70/35 | 9.4 | 6.7 | 1.1 | 0.9 | 2.0 | 31.7 |
| 3x 95/50 | 11 | 8 | 1.1 | 1 | 2.1 | 35.8 |
| 3×120/70 | 12.4 | 9.4 | 1.2 | 1.1 | 2.3 | 39.9 |
| 3×150/70 | 13.8 | 9.4 | 1.4 | 1.1 | 2.4 | 44.6 |
| 3×185/95 | 15.3 | 11 | 1.6 | 1.1 | 2.6 | 49.5 |
| 3×240/120 | 17.5 | 12.4 | 1.7 | 1.2 | 2.8 | 55.7 |
| 3×300/150 | 19.5 | 13.8 | 1.8 | 1.4 | 3.0 | 61.4 |
| 3×400/185 | 22.6 | 15.3 | 2 | 1.6 | 3.2 | 70.4 |
5)Four cores low voltage cables (unarmoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal Sheath Thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm |
| 4×1.5 | 1.4 | 0.7 | 1.8 | 10.4 |
| 4×2.5 | 1.8 | 0.7 | 1.8 | 11.3 |
| 4×4 | 2.3 | 0.7 | 1.8 | 12.5 |
| 4×6 | 2.8 | 0.7 | 1.8 | 13.7 |
| 4×10 | 3.6 | 0.7 | 1.8 | 15.7 |
| 4×16 | 4.5 | 0.7 | 1.8 | 17.8 |
| 4×25 | 5.6 | 0.9 | 1.8 | 21.5 |
| 4×35 | 6.7 | 0.9 | 1.8 | 24.1 |
| 4×50 | 8.0 | 1 | 1.8 | 27.8 |
| 4×70 | 9.4 | 1.1 | 2.0 | 32.0 |
| 4×95 | 11.0 | 1.1 | 2.1 | 36.1 |
| 4×120 | 12.4 | 1.2 | 2.3 | 40.2 |
| 4×150 | 13.8 | 1.4 | 2.4 | 44.9 |
| 4×185 | 15.3 | 1.6 | 2.6 | 49.8 |
| 4×240 | 17.5 | 1.7 | 2.8 | 56.0 |
| 4×300 | 19.5 | 1.8 | 3.0 | 61.7 |
| 4×400 | 22.6 | 2 | 3.2 | 70.7 |
6)Multi-cores low voltage cables(unarmoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation Thickness | Nominal Sheath Thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm |
| 5×1.5 | 1.4 | 0.7 | 1.8 | 11.2 |
| 7×1.5 | 1.4 | 0.7 | 1.8 | 12.0 |
| 10×1.5 | 1.4 | 0.7 | 1.8 | 14.8 |
| 12×1.5 | 1.4 | 0.7 | 1.8 | 15.2 |
| 14×1.5 | 1.4 | 0.7 | 1.8 | 16.0 |
| 19×1.5 | 1.4 | 0.7 | 1.8 | 17.6 |
| 21×1.5 | 1.4 | 0.7 | 1.8 | 18.4 |
| 24×1.5 | 1.4 | 0.7 | 1.8 | 20.4 |
| 30×1.5 | 1.4 | 0.7 | 1.8 | 21.6 |
| 40×1.5 | 1.4 | 0.7 | 1.8 | 26.0 |
| 48×1.5 | 1.4 | 0.7 | 1.8 | 26.4 |
| 61×1.5 | 1.4 | 0.7 | 1.9 | 29.0 |
| 5×2.5 | 1.8 | 0.7 | 1.8 | 12.2 |
| 7×2.5 | 1.8 | 0.7 | 1.8 | 13.2 |
| 10×2.5 | 1.8 | 0.7 | 1.8 | 16.4 |
| 12×2.5 | 1.8 | 0.7 | 1.8 | 16.9 |
| 14×2.5 | 1.8 | 0.7 | 1.8 | 17.7 |
| 19×2.5 | 1.8 | 0.7 | 1.8 | 19.6 |
| 21×2.5 | 1.8 | 0.7 | 1.8 | 20.6 |
| 24×2.5 | 1.8 | 0.7 | 1.8 | 22.8 |
| 30×2.5 | 1.8 | 0.7 | 1.8 | 24.1 |
| 40×2.5 | 1.8 | 0.7 | 1.9 | 29.4 |
| 48×2.5 | 1.8 | 0.7 | 1.9 | 29.9 |
| 61×2.5 | 1.8 | 0.7 | 2.0 | 32.8 |
7)Single core low voltage cables ( aluminum wire armoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation thickness | Nominal Inner Covering thickness | Nominal Alum Wire dia. | Nominal Sheath thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm | mm | mm |
| 1×4 | 2.3 | 0.7 | 1.0 | 0.8 | 1.8 | 10.9 |
| 1×6 | 2.8 | 0.7 | 1.0 | 0.8 | 1.8 | 11.4 |
| 1×10 | 3.6 | 0.7 | 1.0 | 0.8 | 1.8 | 12.2 |
| 1×16 | 4.5 | 0.7 | 1.0 | 0.8 | 1.8 | 13.1 |
| 1×25 | 5.6 | 0.9 | 1.0 | 0.8 | 1.8 | 14.6 |
| 1×35 | 6.7 | 0.9 | 1.0 | 1.25 | 1.8 | 16.6 |
| 1×50 | 8.0 | 1 | 1.0 | 1.25 | 1.8 | 18.1 |
| 1×70 | 9.4 | 1.1 | 1.0 | 1.25 | 1.8 | 19.7 |
| 1×95 | 11.0 | 1.1 | 1.0 | 1.6 | 1.8 | 22.0 |
| 1×120 | 12.4 | 1.2 | 1.0 | 1.6 | 1.8 | 23.6 |
| 1×150 | 13.8 | 1.4 | 1.0 | 1.6 | 1.8 | 25.4 |
| 1×185 | 15.3 | 1.6 | 1.0 | 1.6 | 1.8 | 27.4 |
| 1×240 | 17.5 | 1.7 | 1.0 | 1.6 | 1.9 | 29.9 |
| 1×300 | 19.5 | 1.8 | 1.0 | 2.0 | 2.0 | 33.1 |
| 1×400 | 22.6 | 2 | 1.2 | 2.0 | 2.2 | 37.3 |
| 1×500 | 25.2 | 2.2 | 1.2 | 2.0 | 2.3 | 40. |
8)Two cores low voltage cables (Galvanized steel wire armoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation thickness | Nominal Inner Covering thickness | Nominal Steel Wire dia. | Nominal Sheath thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm | mm | mm |
| 2×1.5 | 1.4 | 0.7 | 1.0 | 0.8 | 1.8 | 12.8 |
| 2×2.5 | 1.8 | 0.7 | 1.0 | 0.8 | 1.8 | 13.6 |
| 2×4 | 2.3 | 0.7 | 1.0 | 0.8 | 1.8 | 14.6 |
| 2×6 | 2.8 | 0.7 | 1.0 | 1.25 | 1.8 | 16.5 |
| 2×10 | 3.6 | 0.7 | 1.0 | 1.25 | 1.8 | 18.1 |
| 2×16 | 4.5 | 0.7 | 1.0 | 1.25 | 1.8 | 19.9 |
| 2×25 | 5.6 | 0.9 | 1.0 | 1.6 | 1.8 | 23.6 |
| 2×35 | 6.7 | 0.9 | 1.0 | 1.6 | 1.8 | 25.8 |
| 2×50 | 8.0 | 1 | 1.0 | 1.6 | 1.9 | 29.0 |
| 2×70 | 9.4 | 1.1 | 1.0 | 2.0 | 2.0 | 33.2 |
| 2×95 | 11.0 | 1.1 | 1.2 | 2.0 | 2.1 | 37.1 |
| 2×120 | 12.4 | 1.2 | 1.2 | 2.0 | 2.3 | 40.5 |
| 2×150 | 13.8 | 1.4 | 1.2 | 2.5 | 2.4 | 45.4 |
| 2×185 | 15.3 | 1.6 | 1.4 | 2.5 | 2.6 | 49.9 |
| 2×240 | 17.5 | 1.7 | 1.4 | 2.5 | 2.7 | 55.1 |
| 2×300 | 19.5 | 1.8 | 1.6 | 2.5 | 2.9 | 60.2 |
| 2×400 | 22.6 | 2 | 1.6 | 2.5 | 3.1 | 67.7 |
9)Three cores low voltage cables (Galvanized steel wire armoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation thickness | Nominal Inner Covering thickness | Nominal Steel Wire dia. | Nominal Sheath thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm | mm | mm |
| 3×1.5 | 1.4 | 0.7 | 1.0 | 0.8 | 1.8 | 13.2 |
| 3×2.5 | 1.8 | 0.7 | 1.0 | 0.8 | 1.8 | 14.1 |
| 3×4 | 2.3 | 0.7 | 1.0 | 0.8 | 1.8 | 15.2 |
| 3×6 | 2.8 | 0.7 | 1.0 | 1.25 | 1.8 | 17.1 |
| 3×10 | 3.6 | 0.7 | 1.0 | 1.25 | 1.8 | 18.9 |
| 3×16 | 4.5 | 0.7 | 1.0 | 1.25 | 1.8 | 20.8 |
| 3×25 | 5.6 | 0.9 | 1.0 | 1.6 | 1.8 | 24.7 |
| 3×35 | 6.7 | 0.9 | 1.0 | 1.6 | 1.8 | 27.2 |
| 3×50 | 8.0 | 1 | 1.0 | 1.6 | 1.9 | 30.6 |
| 3×70 | 9.4 | 1.1 | 1.0 | 2.0 | 2.1 | 35.2 |
| 3×95 | 11.0 | 1.1 | 1.2 | 2.0 | 2.2 | 39.3 |
| 3×120 | 12.4 | 1.2 | 1.2 | 2.0 | 2.3 | 43.0 |
| 3×150 | 13.8 | 1.4 | 1.4 | 2.5 | 2.5 | 48.6 |
| 3×185 | 15.3 | 1.6 | 1.4 | 2.5 | 2.7 | 53.0 |
| 3×240 | 17.5 | 1.7 | 1.4 | 2.5 | 2.8 | 58.5 |
| 3×300 | 19.5 | 1.8 | 1.6 | 2.5 | 3.0 | 64.0 |
| 3×400 | 22.6 | 2 | 1.6 | 3.15 | 3.3 | 73.5 |
10)Three cores+1 low voltage cables (Galvanized steel wire armoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation thickness | Nominal Inner Covering thickness | Nominal Steel Wire dia. | Nominal Sheath thickness | Overall Diameter (Approx.) | ||
| mm^2 | (3) mm | (1) mm | (3) mm | (1) mm | mm | mm | mm | mm |
| 3x 16/10 | 4.5 | 3.6 | 0.7 | 0.7 | 1 | 1.6 | 1.8 | 22.7 |
| 3x 25/16 | 5.6 | 4.5 | 0.9 | 0.7 | 1 | 1.6 | 1.8 | 26.5 |
| 3x 35/16 | 6.7 | 4.5 | 0.9 | 0.7 | 1 | 1.6 | 1.9 | 29 |
| 3x 50/25 | 8.0 | 5.6 | 1 | 0.9 | 1 | 1.6 | 2.1 | 33 |
| 3x 70/35 | 9.4 | 6.7 | 1.1 | 0.9 | 1.2 | 2 | 2.2 | 38 |
| 3x 95/50 | 11.0 | 8.0 | 1.1 | 1 | 1.2 | 2 | 2.3 | 42.4 |
| 3×120/70 | 12.4 | 9.4 | 1.2 | 1.1 | 1.2 | 2 | 2.5 | 48.0 |
| 3×150/70 | 13.8 | 9.4 | 1.4 | 1.1 | 1.4 | 2.5 | 2.7 | 52 |
| 3×185/95 | 15.3 | 11.0 | 1.6 | 1.1 | 1.4 | 2.5 | 2.8 | 57.2 |
| 3×240/120 | 17.5 | 12.4 | 1.7 | 1.2 | 1.6 | 2.5 | 3.1 | 64 |
| 3×300/150 | 19.5 | 13.8 | 1.8 | 1.4 | 1.6 | 2.5 | 3.2 | 69.8 |
| 3×400/185 | 22.6 | 15.3 | 2 | 1.6 | 1.6 | 3.15 | 3.6 | 78.6 |
11)Four cores low voltage cables (Galvanized steel wire armoured)
| Nominal Cross Section | Diameter of Conductor (Approx.) | Nominal Insulation thickness | Nominal Inner Covering thickness | Nominal Steel Wire dia. | Nominal Sheath thickness | Overall Diameter (Approx.) |
| mm^2 | mm | mm | mm | mm | mm | mm |
| 4×1.5 | 1.4 | 0.7 | 1.0 | 0.8 | 1.8 | 14.0 |
| 4×2.5 | 1.8 | 0.7 | 1.0 | 0.8 | 1.8 | 14.9 |
| 4×4 | 2.3 | 0.7 | 1.0 | 1.25 | 1.8 | 17.0 |
| 4×6 | 2.8 | 0.7 | 1.0 | 1.25 | 1.8 | 18.2 |
| 4×10 | 3.6 | 0.7 | 1.0 | 1.25 | 1.8 | 20.2 |
| 4×16 | 4.5 | 0.7 | 1.0 | 1.6 | 1.8 | 23.0 |
| 4×25 | 5.6 | 0.9 | 1.0 | 1.6 | 1.8 | 26.7 |
| 4×35 | 6.7 | 0.9 | 1.0 | 1.6 | 1.9 | 29.5 |
| 4×50 | 8.0 | 1 | 1.0 | 2.0 | 2.1 | 34.2 |
| 4×70 | 9.4 | 1.1 | 1.2 | 2.0 | 2.2 | 38.8 |
| 4×95 | 11.0 | 1.1 | 1.2 | 2.0 | 2.3 | 42.9 |
| 4×120 | 12.4 | 1.2 | 1.4 | 2.5 | 2.5 | 48.6 |
| 4×150 | 13.8 | 1.4 | 1.4 | 2.5 | 2.7 | 53.2 |
| 4×185 | 15.3 | 1.6 | 1.4 | 2.5 | 2.8 | 58.1 |
| 4×240 | 17.5 | 1.7 | 1.6 | 2.5 | 3.1 | 64.8 |
| 4×300 | 19.5 | 1.8 | 1.6 | 2.5 | 3.2 | 70.4 |
| 4×400 | 22.6 | 2 | 1.8 | 3.15 | 3.6 | 81.3 |
We are China IEC 60502 Cable, XLPE Cables manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular IEC 60502 Cable Products
IEC 60502 3*185sq mm Copper Core XLPE Insulated Galvanized Steel Wire Armoured Low Voltage Cable
IEC 60502 PVC Insulated PVC Sheathed Cable for Electricity Transmission
Low and Medium Voltage Cu/Al Core Power Cable IEC60502 Standard
Popular Low Voltage Cables Products
Electrical Wire PVC or XLPE Cover Electric Wire 3 Core Shielded Electrical Cable PVC Cable
Nysy Cu/PVC/Cts/PVC Copper Conductor PVC Insulated Low Voltage Cables
Low Voltage and Medium Voltage Copper XLPE Insulated Underground Armored Type of Cables
Custom Copper Conductor PVC Insulated Cables Low Voltage Ce IEC Standard
Nhxmh-J / Nhxmh-O Low Voltage Cables Ls0h Sheathed Single Core Cable
Popular luxingcable Products
VDE Standard Power Cable and Weight Copper Cable
Underground Armoured Power Cable Cu XLPE Swa PVC Size 120mm 240mm XLPE 4 Core Armoured Cable
0.6/1 Kv XLPE Single Core Cable 150mm
Low Voltage 3.6/6kv Cu/XLPE Insulation/PVC Sheath Power Cable
High Current Carrying Capacity Mc4 Solar Power Cable
Popular XLPE Cable Products
0.6/1kv Copper Conductor PVC or XLPE Insulated Power Cable
PVC Insulated Electrical Cable 16mm 2 Core Armoured 11kv Underground Cable
LV Power Cable Cu/XLPE/Swa/PVC Underground Power Cable
Na2xs2y, Power Cable, 6/10 Kv, 1/C, Al/XLPE/Cws/PE (HD 620/VDE 0276-620)
Low Voltage XLPE Cable 4c*25mm2 Cu/XLPE/Swa/PVC IEC60502
0.6/1kV Flame Retardant CU/XLPE/PVC LV Power Cable 3X2.5mm2 for Substation Lighting
Tags: IEC 60502 Cable, Low Voltage Cables, luxingcable, XLPE Cable